Error -200609 occurred at DAQmx Write: Selected Buffer Size Too Small

Hello, I'm writing some simple test VI's that I will eventually build upon to make an externally clocked analog output VI. I started with a very simple program to output finite samples using the onboard clock with the DAQmx Timing.VI. When I run the program, I almost immediately get an error. The error message is below.
Error -200609 occurred at DAQmx Write (Analog DBL 1Chan 1Samp).vi:1
Possible reason(s):
Generation cannot be started, because the selected buffer size is too small.
Increase the buffer size.
Conflicting Property
Property: Output.BufSize
Corresponding Value: 1
Minimum Supported Value: 2
Task Name: _unnamedTask<1C>
I have used DAQmx VI's before in similar applications and never encountered this error. Additionally, I read at the link below that DAQmx Timing.VI should be generating the buffer automatically. Any ideas as what could be causing this?
Specs:
Windows 7
Labview 2012
PCIe-6353 as DAQ board
Below is a picture of my block diagram and the VI is attached.
Solved!
Go to Solution.
Attachments:
FiniteSamplesTest.vi ‏18 KB

Oops. Just realized my very silly mistake: I forgot to add the Start Task VI. I did so and it works as designed.

Similar Messages

  • Error-50150 occured at DAQmx Write

    Hello,
        I am experiencing a seemingly random error in a large program. The error occurs in a part of the program that simulates tach signals to a CPLD. I have not been able to find out what conditions cause this error, it seems to be random in nature.
    The full error reads this:
    Error - 50150 occurred at DAQmx Write(Digital 1D U16 1Chan Nsamp).vi
    Possible Reasons:
    The software has entered an unknown state-usually as a result of a cascade failure induced by an unexpected series of state inputs. The operation could not be completed as specified and you should immediately terminate all further transactions if you are able to do so.
    Task Name:TackABC_Write Port0 U16
    The device we are using is a PCI-DIO-32HS, with Labview 7.1, NI-MAX 4.1, and DAQmx drivers 8.3.1. The task writes 3 signals to the CPLD, and it works most of the time, but every so often this error will occur. I was wondering what could be the cause of an error like this?
    Thanks, Steve

    Hello Brian, thanks for the response.
    I made a mistake in my last post, it is actually a DAQmx clear task in place of the stop task vi i mentioned. When we first received this error it had no clear task at the end, but I added one. Even with this the error has still shown up from time to time. Would it help at all to add a reset device vi afte the clear task vi?
    I took some screenshots for you as well. The first shot is of the function in question, the second is the same shot with the case turned to false, and the third is the inside of the main subvi. When the error occurs it focuses on the write vi that is inside the subvi. Let me know if there is more info I could grab that would make things mroe clear.
    Thanks,
    Steve
    Attachments:
    SS3.JPG ‏160 KB
    SS1.JPG ‏189 KB
    SS2.JPG ‏181 KB

  • Error -200428 Occurred at DAQmx Write (Digital Bool 1Line 1Point).vi

    The working program started giving this program after we have had a hard_disk crash. We are just using the program that was backed up. Will appreciate any suggestions on this one. 
    Naresh

    Have you read the explanation for the error and did you verify the task or virtual channels exist?

  • Error -200587 occurred at DAQmx Start Task.vi:7

    I am running the attached code Merrit_Coil_calibration, and I get the following error:
    Error -200587 occurred at DAQmx Start Task.vi:7
    Possible reason(s):
    Requested operation could not be performed, because the specified digital lines are either reserved or the device is not present in NI-DAQmx.
    It is possible that these lines are reserved by another task, the device is being used through the Traditional NI-DAQ interface, or the device is being reset. You might also get the error if the specified resource is currently in use by LabVIEW network variables bound to the DAQ Channel, or if the DAQ Channel is being used in any OPC Client software.
    If you are using these lines with another task, wait for the task to complete.  If you are using the device through the Traditional NI-DAQ interface, and you want to use it with NI-DAQmx, reset (initialize) the device using the Traditional NI-DAQ interface. If you are resetting the device, wait for the reset to finish.
    Device:  Dev2
    Task Name: _unnamedTask<F>
    I am calling the same DAQ, many different places in my code and I think that is the problem, but I can not figure out why or hw to fix it.  Anyone have any suggestions?
    Attachments:
    Final.zip ‏2434 KB

    Thank you both for your input.  I slightly changed my code to Merritt_Coil_calibration (updated code attached) and the first error went away, but now I have a different one which is:
    Error -200429 occurred at DAQmx Write (Digital U32 1Chan 1Samp).vi:1
    Possible reason(s):
    Value passed to the Task/Channels In control is an empty string (or I/O control).
    The value must refer to a valid task or valid channels.
    As far as what DAQ device I am using, it is the NI USB 6009.  I am only using digital port 0.  During different pieces of my code I send different values to port 0.  I am using this to drive some stepper motors.  I thus send square waves on the different pins on port 0.  I do not know if this is exactly what you were asking. 
    Whatever the case, I was wondering if anyone knows why this error occurs and how I could fix it. 
    thanks.
    Attachments:
    honorsproject.zip ‏256 KB

  • Error 63 occurred at DataSocket Write in getWavelength_v80 EDITED.vi, help? please!

    Hey guys, I am new to LabView and I have thought myself everything that I know.  I am an undergraduate student at NC A&T.
    Okay so I took a peice of code that I acquired from Bristol, and it's for a Bristol Wavemeter V1.22.  I first edited it to get a graph in there to show the data, and get a slope and Y intercept.  Now I am trying to connect it to a computer that controls a COntinuum ND6000.  We have existing code for the ND6000 that lets the two computers connect.  I took the code out of there that was the part that connects them and now when I wired everything up, I get the "Error 63 occurred at DataSocket Write in getWavelength_v80 EDITED.vi" error message.  it states; Possible reason(s):
    LabVIEW:  Serial port receive buffer overflow.
    =========================
    LabVIEW:  The network connection was refused by the server. For TCP/IP, make sure the server is running and listening on the port you are trying to use. Firewalls can also cause a server to refuse a connection. For VI Server, make sure you have enabled VI Server from Tools>>Options>>VI Server:Configuration."
    I tried making sure everything in the configuration was correct and it all is.  Can you guys please help me?
    Thank you. 
    I have attached the folder that it is located in because you do have to have the library function.  The file is located in the Bristol Wavelength Meter V1.22\Programming Interface\LabVIEW example I.
    Thank you again!
    Solved!
    Go to Solution.
    Attachments:
    6.jpg ‏153 KB
    7.jpg ‏112 KB

    So I went through and realized that I had the wrong port typed in by 1 number, I changed that and put in the correct port for the TCP address.  Now when I run it I get this error message 66....
    "LabVIEW:  The network connection was closed by the peer. If you are using the Open VI Reference function on a remote VI Server connection, verify that the machine is allowed access by selecting Tools>>Options>>VI Server:Machine Access on the server side."
    Any help?? I checked the Server Machine access and all of them are set to allow.

  • Warning 200015 occurred at DAQmx Write (Digital Wfm 1Chan NSamp).vi:4

    Hi,
    Attached is the VI I write. But there is a warning: Warning 200015 occurred at DAQmx Write (Digital Wfm 1Chan NSamp).vi:4
    I want to use digital channel to create an output. The duty cycle change from 30% to 50% to 70%. At the same time, measure the input of another 2 channels.
    Do you have any idea about this?
    Thanks.
    Attachments:
    Digital pulse_DO Channel-1_mod2.vi ‏39 KB

    Hello,
    The situation that you are seeing here can be identified as 'glitching'.  Glitching occurs where there is potential for previous samples in a buffer to be mixed in with newer samples written into the buffer, causing a signal output that is a mix between the old and new data you are trying to output.  In the DAQmx Help document, search for 'glitching' and you will be directed to an article which explains glitching, mentions Warning 200015 is thrown where there is a potential for this to happen, and then offers suggestions on how to work around this issue, as well as two pictures that clarifies what could happen with glitching.
    This warning pops up in your application since you are writing one set of data and then writing a second set of data afterwards.  If you do not see glitching on your signal, you can modify your code to ignore this warning.  Read through the help document for suggestions on modifications that will work for your application.
    Kyle A.
    National Instruments
    High Speed Digital I/O Product Support Engineer - R&D

  • Error 200745 occured at DAQmx

    Hello everyone.
    Does anybody knows about this "error-200745 occured at DAQmx"
    everytime I used 57.6KHz frequency and Initial delay of 1.
    Looking forward of your help..
    thanks and regards,
    Ludz

    Hi Ludz,
    Do you get the error for every duty cycle?  Do you know which frequency or frequency range the program will give you this error?  What example program did you start with? One example you can try is the PWM-Counter Output.vi located in the example finder.  You can find the example finder at Help>>Find Examples.  When this opens, select the search tab in the top left and search for PWM.  I would try running this example with the same settings as your other program to see if you see the same behavior.
    Regards,
    Jim Schwartz

  • Error -1073807346 occurred at VISA Write in rsspecan_core_write.vi

    Possible reason(s):
    VISA:  (Hex 0xBFFF000E) The given session or object reference is invalid.
    I'm using a USB to GPIB connection to a Rohde Schwarz FSV30 Spectrum Analizer from Windows 7.
    My program works 100% in LabView but the problem comes in when I've compiled the program into an executable.
    I have already installed the NI VISA Run Time Engine 5.0.1 and it still does not work.
    I've also installed the NI-488.2 2.73 drivers for the GPIB unit.
    Any ideas?
    Solved!
    Go to Solution.
    Attachments:
    Error -1073807346 occurred at VISA Write.png ‏30 KB

    Hey,
    the problem when building executables with LabVIEW is, that the driver core of the attribute based instrument drivers (esp.. the VIs which are creating this error) is linked while runtime dynamically to the VIs. The application builder which follows all dependencies and include them into the package fails in this case.
    To get a running executable please add manually all VIs for the folder <inst lib>\rzspecan\_utility\rsspecan_core\callbacks\ to the LabVIEW project and everything should work fine.
    For more details of this driver refer to http://www.rohde-schwarz.com/appnote/1ma170
    So long, juergen

  • Error-200220 occurred at daqmx create channel %28AO-Voltage-Basic%29.vi%3A3

    Hello  
    i need u r help  this  error apeears to me when i run my code on labview 
    and i dont know how i can solve it due  am still wake and dont have background on labviw 
    and coding 
    (error-200220 occurred at daqmx create channel (AO-Voltage-Basic).vi:3)

    ok the first problem is solved...
    but now in the another program
    its appearing:
    Error 1 occurred at Read File+ (string): Read File
    Possible reason(s):
    LabVIEW:  An input parameter is invalid. For example if the input is a path, the path might contain a character not allowed by the OS such as ? or @.
    =========================
    NI-488:  Command requires GPIB Controller to be Controller in Charge.

  • Error 229771 occurred at DAQmx Start Task - only in Labview project

    Labview 2011 sp1
    os: W7 32bits
    DAQmx 9.7.0f0
    ni-PCI 6251
    Hi,
    I'm working with a ni-PCI 6251 card. I got the error :  Error -229771 occurred at DAQmx Start Task. Possible reasons :Internal sofware error  occured in MIG software ... when I'm trying to launch my data acquisition vi. This error was already reported in this post :
    http://forums.ni.com/t5/Academic-Hardware-Products​-NI/Error-229771-occurred-at-DAQmx-Start-Task/td-p​...
    I tried to reinstall DAQmx as explained in the post but it unfurtunatly it did'nt fix my issue.
    I've notice the following points :
    1. This error appears randomly, after several reboots the vi will finally run without error
    2. The error only appears when the vi is included in project
    I will really appreciate any kind of help.
    sebastian
    Attachments:
    test_daq_2.vi ‏23 KB

    Bonjour,
    Je vous invite à jeter un oeil sur le lien suivant :
    http://digital.ni.com/public.nsf/allkb/03123D0E8A3​6C48E862577A4005B6BAA?OpenDocument
    Il devrait résoudre votre problématique.
    Cdlt,
    Matthieu RICORD
    National Instruments France
    #adMrkt{text-align: center;font-size:11px; font-weight: bold;} #adMrkt a {text-decoration: none;} #adMrkt a:hover{font-size: 9px;} #adMrkt a span{display: none;} #adMrkt a:hover span{display: block;}
    Été de LabVIEW 2014
    12 présentations en ligne, du 30 juin au 18 juillet

  • Error 200380 occurred at DAQmx perform bridge offset nulling operation

    I had a working VI that could balance a wheatstone half bridge and read and record measurements.  My sensors are attached to a SCXI-1314 modle in a 1520 box in channel 0 (positioned as in the manual for half bridge) with the completion resistors in the appt places in ch7.  It used 'custom voltage with excitation'.
    Wanted to improve this VI so that it would also do a shunt calibration.  I therefore connected the shunt resistor in the board over my active sensor as in the manual.  I tried then to create a virtual channel for it - but it wouldn't work.  So I gave up on that idea and tried to put things back how they were - deleted the virtual channel, and removed the connections to the shunt resistor.  Except now none of my previously working VIs will work.  I have built a new VI, and that can find a signal but not balance the bridge.  I get:
    error 200380 occurred at DAQmx perform bridge offset nulling operation.
    I have checked the hardware again, and it's all wired correctly - it seems like the VI can see the channel but doesn't know what to do with it.   Have running the VIs with and without a custom voltage with excitation channel created but nothing works.
    Help!

    Hi LucyWH
    Have you tried re identifying the chassis in Measurement and
    automation explorer?
    Have you changed the jumpers at all as when rewiring this is easily
    overlooked?
    I have found some links that you may find useful:
    Error -200380 When
    Calibrating SCXI-1520 in NI-DAQmx
    http://digital.ni.com/public.nsf/allkb/6E94108C9611910186256D43007C2584?OpenDocument
    Common NI-DAQmx Error
    Codes and Solutions: Codes -200300 to -200999
    http://digital.ni.com/public.nsf/allkb/8A0E097385A4269586256DBA0054E668?OpenDocument
    Regards
    Robert
    National Instruments UK & Ireland

  • Error -200220 occurred at DAQmx Create Channel (CO-Pulse Generation-Time).vi:1

    Hello,
    Just a couple of days ago I was given a task to complete. To transfer a Labview program from a desktop computer to laptop.
    The program itself uses a marlin camera to count the number of seeds.
    The transfer was fine I installed Labview 8.2, installed the DAQmx drivers and labview vision.
    I then transffered the program files over and ran the program on the laptop in labview and found an ERROR: Error -200220 occurred at DAQmx Create Channel (CO-Pulse Generation-Time).vi:1
    I remember that the desktop had a kind of board attached to it: some NI board dont know the model etc.
    can this be a problem? I have ensured that the problem is not the camera by checking it in MAX and it works fine.
    When i do step by step debugging the problem comes to a VI that uses a palette called DAQmx trigger - data acquisition palette.
    please see the attached picture!!
    Is this VI the problem then and is this palette the main problem that is not enabling this program to work??
    thankyou
    p.s. Will it be necessary to use the NI board then? if so i dont think it will work on the laptop then as you will need to install the daq card
    which can only be done on a desktop i think!! 

    Hello Rob W,
    Yes I only use a Firewire to connect the camera.
    And also i am sure that the device shows up in MAX under NI-DAQmx devices and not under Traditional DAQ. and it works under max.
    I am sure the problem is as shown in the image. because i have not connected to the NI board on the laptop and the program is designed to work with the board.
    but i have also tried removing the parts in the program that use the board but because of the complexity of the program i.e. wires i had some other problems i think
    must be the wiring etc
    thankyou

  • Vista & Outlook 2007: Sync with second XP & Outlook 2003 - The passed buffer is too small for the reply data

    Dear Community,
    I'm synchronising my T3 with two PCs. One with Vista & Outlook 2007 and the other with XP & Outlook 2003. Both with the latest conduit & Hotsync Manager versions installed for each OS based on the availability on the Palm Website. 
    My problem is that when I synchronise the T3 with either PC and then try to sync it with the other I'm receiving the following error message for the Calendar:
    Outlook Calendar
    The passed buffer is too small for the reply data.
    OLERR:0D-0008
    OLERR:0D-0004
    OLERR:0D-0001
    - Slow Sync
    Outlook Calendar synchronization failed
     The second time the sync is successful but takes a long time and the actual problem is that it creates duplicates for records previously changed on either PC - but with a sync in between those changes, i.e. no conflict in the sense that the same record was changed in both environments since the last sync. I have configured the conflict handling to establish a hierarchy PC1-T3-PC2 but try to avoid them by synchronising as often as possible.
    Has anyone come across that problem or any ideas? Can you somehow adjust the buffer size for the sync? I have been using Lotus Organiser & then the various Outlook versions for a number of years.
    Thank you
    Rainer
    Post relates to: Tungsten T3
    Post relates to: Tungsten T3

    As they say on TV, "Doh"!!!
    I figured out the problem. I started the Sync tool, selected "Settings", then "Mcrosoft Outlook" tab and then "Select Folders" button. I browsed to the proper folders in Outlook (Calendar, Tasks, etc). Select OK enough times and retried the sync.
    It worked.

  • Error 33172 occurred at Read & Write data transfer between two or more PF2010 controller

    Hi,i need to do data transfer between two or more FP2010 controller.e.g. FP2010(A) & FP2010(B).
    FP2010(A) need to transfer the measurement (from its I/O module) to FP2010(B) to do the data analysis.These data transfer should be synchronous btw two controller to prevent data lost.
    From the vi used in the attachment,i encountered some problems at:
    (1) Error 33172 occurred while publishing the data.Can i create and publish data under different item name?
    (2) How to synchronies the read & write btw contorller?
    All controller are communicating with each other directly without the need of a host computer to link them together
    Is there any other method to do fast data transfer betwe
    en controller?

    Hi YongNei,
    You were succesful in omiting enough information to make it very difficult to answer!
    Please post your example.
    Please tell us what version of LV-RT you are using.
    Please define what you concider "fast data transfer".
    Have you concidered mapping the FP tags of FP2010(A) to FP2010(B) and vise versa?
    WHat exactly has to be syncronized?
    If you have something that is close to working, share that.
    Well, that as far as I can go with the info you have provided. Depending on the details, what you are asking could be anything from trivial to impossible with the currently available technology. I just can't say.
    It would probably be a good idea to start over with a fresh question (sorry) because not many people are going to know what a a "
    PF2010" is and I can not guarentee that I will be able to get back to you personally until next week-end.
    Trying to help you get an answer,
    Ben
    Ben Rayner
    I am currently active on.. MainStream Preppers
    Rayner's Ridge is under construction

  • Error -201003 occurred at DAQmx Create Channel (AI-Temperature-Thermocouple).vi:4

      I get this error when using the NI USB-TC01 LabVIEW Temperature Logger and a J type thermocouple.
    So I tried creating my own VI, the daq assistant gives me a correct reading but only for 1 sample. If I try to change to continous or N samples it will then give me this error:
    Error -200077 occurred at DAQ
    Assistant
    Possible Reason(s):
    Requested value
    is not a supported value for this property. The property value may be invalid
    because it conflicts with another property.
    Property:
    SampTimingType
    Requested Value: Sample Clock
    You Can Select:
    On Demand
    What Is the problem?? I need to get a continous reading that I can use through a VI to get an excel file with  the data. I also need it to be continous so I can manipulate the sampling rate.
    By the way I also tried using the device on other computers and it still gives the same problem.
    Julian Sanchez
    Mechanical Engineering Student - University of Central Florida
    Research Intern | CASER
    C. 407.744.4174 | E. [email protected]

    Thank you for your reply,
    I am new to LabVIEW and I am not sure how to do what you explained. The DAQ assistant has a "number of samples" when you drag the bottom; is that where I need to create the loop??
    What is the maximum # of samples per second that I can get with this device?? That is my ultimate goal with this experiment, to be able to get the most readings per second.
    Julian Sanchez
    Mechanical Engineering Student - University of Central Florida
    Research Intern | CASER
    C. 407.744.4174 | E. [email protected]

Maybe you are looking for

  • !!!!!!!!!! HP C4180 ALl-IN-ONE printer ON a 175X external jetdirect printserve​r ISSUES

    Hi, its my first post here,   so HELLO to all i recently bought a printserver,   its a Hp 175x USB external jetdirect printserver  (can these names be any longer pfff) And my all in one printer is a HP C4180 .   I hooked everything up,  all lights ar

  • Information about acrobat 9.0

    Dear Sirs We have been informed by the TTF company that TTF software has been acquired by Adobe System. As end users of the software Project Reviewer, we would like to understand more details concernig how the whole "package" has been incorporated in

  • Audio not playing in Captivate 6

    Hello, I used the "Add Audio" option in Captivate 6 to add my voice to the course and when I publish in HTML5 I cannot hear my voice when it's in my LMS. I checked my headphones and audio on my computer and they are working fine so it must be somethi

  • Check if In the Middle

    How do you check if something is in the middle of a frame?

  • 3D TV 55TL515u buzzing sound

    Whenever there is an audio lull in whatever is on the screen, the TV will intermittently make a buzzing sound. It isn't constant, but intermittent. The buzz can be also heard through the normal audio level if the volume is reduced slightly. It is ver