Error concerning current measurement

I am trying to measure a voltage differential from a device (Magnehelic) which produces the 4-20mA output. I am using a DAQcard-6024. In the configuration window, I set the max and min input range with a 6 and 0. I have custom scaling with a slope of .375 and a y-intercept of -1.5. I keep receiving an error message saying that my max and min values don't fall within the appropriate range. It says the appropriate range is between -1.49... and -1.51...  Any ideas on what could be causing this problem?

Squinn21:
Regardless of scaling errors, I believe the 6024 can only read voltage inputs, not current. You would need to place a 250 ohm precision resistor across the DAQ input terminals to convert the 4-20mA into a 1-5V siganl the DAQ can read.
-AK2DM
~~~~~~~~~~~~~~~~~~~~~~~~~~
"It’s the questions that drive us.”
~~~~~~~~~~~~~~~~~~~~~~~~~~

Similar Messages

  • TestStand DC current measure

    Hi!
    I'm using TestStand 2012 with LabVIEW 2011 for measuring the current in my Sensor Interface module. In the TestStand program's setup part I initialize the DC current measurement channel, and as the VI's output I take the Session and error out. In the Main part in a for loop I measure the DC current, and save the value in an array. In the clean up part I close the DC current channel. I have 1200 iterration step in the for loop and after 2-300 step my computer get crashed, and I have to restart it, I can't do anything, can't move the mouse ... I in the for loop I tried to close and reinitialize the DC current channel after  100 and 200... step and this way it goes to 1183 ot 1200 and crashed.
    I use NI-PXI-4071 DMM, Windows 7 and PXI-1033
    Tomi

    Hi Tamas!
    I tried to reproduce the issue with a similar test sequence that I created, but without any success.
    I ran the main part of the sequence for 10000 steps. During that I had a look on the resource consumption of teststand. I saw that it uses circa 6-7 times more memory, and 20 % of CPU, but for me it did not froze down. 
    I guess you ran out of memory, and because of this your OS freezes. Did you monitor the resource consumption?
    Did you change anything in the settings of the VI call? How complex is your VI?
    Is it possible to tell more about your sequence?
    I have a suggestion, maybe it is worth to try it.
    You wrote, you use a for loop. So if you go to the run options of the VI, you should set the Test recoding option to Disable. Due to this, the results will be evaluated after the 1200 iterations.
    This solution is shown in picture TS_1.png
    Or, you could achieve the same results, with deleting the for loop end enabling the looping in the settings of the called VI. This is shown in the TS_02.png image.
    I suggest you to write an e-mail to [email protected] . If you can, please send the sequence, and I could have a look on it.
    Please let me know, if my solutions helped, or please write to [email protected]
    Best regards,
    Balazs Nagy
    Attachments:
    ts_1.png ‏39 KB
    ts_02.png ‏70 KB

  • Huey Pro calibrator- error message  display measurement Error

    i am using this huey pro calibration.. it had been a year without problem... but now i am trying to calibrate my apple cinema display LCD 30 inch it keep saying error message- display measurement error.. and huey support never answer my e-mail. any idea? how can i fix it.. i did re install software many times but same thing happen.. so right now i can;t calibrate my monitor.. any help please

    >a nice NVidia card... Please help Adobe!
    1a - what is the model nVidia card, and what is your driver version?
    1b - for instance, I have a GTX 285 and driver 296.10
    2a - aside from the occassional Adobe employee, this is a user to user forum, not Adobe suport
    2b - how to contact Adobe...
    Adobe contact information
    http://www.adobe.com/support/contact
    In the US - Adobe General support 800-833-6687 M-F 5am-7pm Pacific
    In the US - Adobe Install Problems 800-642-3623
    In the US - Adobe Activation 866-772-3623 Open 24/7

  • EPM 10 NW Report showing error - No Current connection

    Hi Team,
    We are using EPM NW 10 Version SP 15 Patch 1.NET 4
    When we Open the report from offline , The report is showing Error : " Error - No Current Connection"
    And also some reports showing Value error , While opening the report in the offline . In this report we used EPM retrieve formula
    This issue facing for one user machine
    Please suggest whether we need to change settings in the user machine

    Hi Andy,
    No Offline Mode.
    After refresh the EPM report , We saved the report locally in the desktop
    The problem is User send this report to another user
    So receiving user , When ever he opening that report , Its showing this Value error
    He using the Excel 2010 Version
    Please suggest

  • Trying to access our public library's ebooks. Downloaded the software, but am getting an error saying: Current version of MP Security is 2.5.0.0 and I need 2.

    Trying to access our public library's ebooks. Downloaded the software,(Overdrive Media Console) but am getting an error saying: Current version of MP Security is 2.5.0.0 and I need 2.5.0.1. How do I do that so I can read the ebooks? People have suggested to use IE but I much prefer Firefox HELP!

    Try updating the Media Player while using Internet Explorer. The Windows Updates site uses ActiveX to perform its' functions. Firefox doesn't support ActiveX.

  • Attempting to install Flash plugin 11.4 but getting error: application currently in use

    I try to get a support in the Adobe forum. While I am waiting for any responses, I might as well look for the same here. Maybe someone have an idea.
    Last night, my Firefox 16.0.2 prompted sites like Youtube to upgrade my Flash Player. First attempt at installation was successful (if I remember it), but somehow Firefox slowed down at confirmation. So, I try to uninstall and reinstall Flash Player. Yes, I did complete uninstallation. Any subsequent attempts led to error: application currently in use.
    Earlier today, I resetted my Firefox browser. First attempt at another installation was successful, but the browser seemed to hang or slow down for a while until the Flash confirmation page showed up. I thought for sometime, everything went fine. It did not when I was having trouble watching flash player content from a site. I figured I better uninstall and reinstall it again. Here I go again with the error message like the above.
    Any idea what I should do next or how should fix this? Any input is appreciated. I'm using Windows 7

    Please restart you computer after the uninstall then try installing again.
    Thanks!

  • Attempting to Upgrade to Flash Player 11.4 - Error: application currently in use

    I noticed that at least other have experienced this, but in a different browser.
    Since last night, sites like Youtube has prompted to install the latest version of Flash Player. So, I went ahead installing the new version by following the instructions. Somehow, I kept getting this message - Error: application currently in use. I tried uninstalling and reinstalling, but kept getting that error message.
    The browser with the problem is Firefox 16.0.2. I'm using Windows 7. The problem does not appear in Chrome and Chrome has not prompted me to upgrade to the latest version of Flash player.
    I appreciate any input.
    Thanks,
    G.
    Please don't refer back to that Flash Player Issues Link, because I have visited it many times. The guide there has not specifically address this issue much.

    Could you please download the installer from the following link: http://helpx.adobe.com/flash-player/kb/installation-problems-flash-player-windows.html#mai n-pars_header
    Then close all browsers and double-click the downloaded file.
    Thanks,
    Sunil

  • Upgrading to lion: concern currently i amMac OS X 10.6.8 (10K549) with a windows dual boot (boot camp)

    Upgrading to lion: concern currently i am running Mac OS X 10.6.8 (10K549) with a windows dual boot (boot camp) on a imac, hardward configuration is good. my question is if i upgrade to lion will it effect my boot camp windows environment in any manner shape or form or will it stay pristine and I will be able to access it with no problem.   as for the upgrade does it give you a clean install and upgrade options
    any insight would be appreciated.
    Also has anyone, added another partition and installed lion in their leaving the snow leopard partion intact.

    I would ask myself these questions first
    What features am I hoping to benefit from by upgrading?
    What apps do I have on OSX that I need to still fucntion? (research that they will)
    Just a cautionary note - I have had problems, but only upgraded to see what was new - needed nothing, lost a lot

  • Time to make a current measurement

    Hi,
    I am new to the PXI 4132. I am trying to measure current through a device using the PXI 1033 which has a PXI 4132 in it. I would like to know the lowest current that I can measure using this device(as I would be using this to measure leakage in a device) and also how much time would it take to make this lowest current measurement.

    I have never used this device but from the specification sheet it looks like measurement rates are dependent on the aperture time.  With longer aperture times you get less noise.  From Figure 5 and Table 2 it looks like the noise on a current measurement on the 10 uA range with 1 PLC aperture is about 20 pA RMS.  With that setting you can get a maximum of 59.9 or 49.9 readings per second, depending on your power line frequency.
    Lynn

  • #value error for datetime measure in SSAS

    HI,
    Iam getting #value error for datetime measure in SSAS.

    Hi jarugulalaks,
    If it is related to the SSAS, you could post this issue to the SSAS forum.
    The forum link:
    https://social.msdn.microsoft.com/Forums/en-US/home?forum=sqlanalysisservices
    Best Regards,
    Jack
    We are trying to better understand customer views on social support experience, so your participation in this interview project would be greatly appreciated if you have time. Thanks for helping make community forums a great place.
    Click
    HERE to participate the survey.

  • SCXI-1104 & 1102 Current Measurement

    1. Can SCXI-1104 be used for current measurement by soldering a precise resistor onto the board?
    2. If I use TC 2095 as multiplexer for SCXI 1102, and wire the input current through thermocouple plug, will that influence the current measurement?
    Thanks

    Hello,
    Both methods are equivalent, at the end the only difference is the location of the precision resistance. If you reconfigure your system frequently I think the 1303 method will be more convenient. However, if this system is designated for this test I think that soldering the resistances to the 1102 will be the best
    option.
    SCXI Resistor Kit:
    http://sine.ni.com/nips/cds/view/p/lang/en/nid/1644
    Regards,
    MCOTO

  • Constant Current Measurement VI.Which pins to use?

    I have got the constant current measurement vi from the examples portion of LABVIEW 6.0.I have got NI-DAQ 6024E and it's connector block CB-68LP.I have left the default parameters as it is of channel & device.I read the input current values on pins 68 & 67 but they are not accurate.Infact,they are too far from the actual values.I've a potentiometer of variable resistance which I use in series of this circuit.The Rs shown on front panel makes no difference to the readings.
    Also, is there any way I can increase the current limit of this program?
    I'm attaching the VI I have used.
    Attachments:
    cont_current_meas.vi ‏58 KB

    Is your DAQ card setup for differential input? If it is, you're using the wrong ground reference. You want to use pins 68 and 34 (AI0 is positive (68), AI8 is negative (34)).
    This is most likely your problem.
    Mark

  • Error while creating measurment documents for a counter (counter based strategy Plan)

    Dear Experts
    Pl suggest the possible solution for below case
    I have a counter based preventive maintenance Plan of 100km, 200km,.....  with op1,op2,..... respectively.
    Now I have done maintenance for 600 km and going to enter another reading in IK11.
    Here, system is giving error
    Counter reading in doc. 251591 larger than in subsequent doc. 251585
    Message no. IR171
    Diagnosis
    No counter overflow reading has been defined for the measuring point, and the counter reading that you have entered is larger than the one in the subsequent measurement document.
    This is not allowed, since the counter is not marked as running backwards.
    System Response
    Processing will not be continued.
    Procedure
    Check your entries and the counter data of the measuring point.
    screen shot for measurement document earlier created is as

    Hi Akhilesh
    okay . I have not found any error in my last and current reading date and time
    screen shot is attached again here for ur reference
    now, what thing I have to checked, pl suggest.

  • Deployment error when modifying measures and my heirarchy

    I am working on Lesson 3 on analysis services tutorial where i am modifying measures and my heirarchy
    and this is my error message.
    Warning 1 Dimension [Date] : Avoid visible attribute hierarchies for attributes used as levels in user-defined hierarchies. 0 0
    Warning 2 Dimension [Customer] : Avoid visible attribute hierarchies for attributes used as levels in user-defined hierarchies. 0 0
    Warning 3 Dimension [Product] : Avoid visible attribute hierarchies for attributes used as levels in user-defined hierarchies. 0 0
    Warning 4 Dimension [Product] : Define attribute relationships as 'Rigid' where appropriate. 0 0
    Warning 5 Errors in the OLAP storage engine: A duplicate attribute key has been found when processing: Table: 'dbo_DimDate', Column: 'CalendarQuarter', Value: '4'. The attribute is 'Calendar Quarter'. 0 0
    Error 6 Internal error: The operation terminated unsuccessfully. 0 0
    Error 7 Server: The current operation was cancelled because another operation in the transaction failed. 0 0
    What can i do to fix this?

    Hi Cook959,
    In your scenario, it seems that the issue was related to the error message.
    Errors in the OLAP storage engine: A duplicate attribute key has been found when processing: Table: 'dbo_DimDate', Column: 'CalendarQuarter', Value: '4'. The attribute is 'Calendar Quarter'. 0 0
    There are many reasons that can cause this issue, here are some blogs which list the reasons and explanation, please refer to the links below to see the details.
    http://ms-olap.blogspot.com/2009/11/duplicate-attribute-key-has-been-found.html
    http://blog.oraylis.de/2013/08/a-duplicate-attribute-key-has-been-found-during-processing-revisited/
    Hope this helps.
    Regards, 
    Charlie Liao
    TechNet Community Support

  • FP-1601 with FP-AI-110 current measurement troubleshooting

    Hello,
    i really need help here.
    i read every thread in this forum about my problem, i still dont know how to
    check my FP-1601 Ethernet module.
    my application need to measure current from sensor.
    but i dont know for sure that my FP-1601 module is work fine.
    so i want to check the FP-1601 without connecting sensor to it, is it possible ?
    i download the diagnostic program from this website to check
    my FP-1601 for series A and B , and the program cannot complete,
    i get error on timeout.
    Regards,
    mor

    Hello Mor. Thank you for contacting National Instruments. Is your FP controller showing up in the Measurement and Automation Explorer (MAX) under Remote Systems? Does it find your modules when you right click on the IP address and select Find Devices? If it does, expand Data Neighborhood>>Fieldpoint Items>>your IP address>>your controller. When you hit start are all of your items successful? If they are then everything is working properly.
    If your controller is not showing up under Remote Systems or Find Devices timeouts, reset your controller and change the network settings so that MAX suggests values for you. Please let me know if you have any questions. Have a great day!
    Marni S.
    National Instruments

Maybe you are looking for

  • I used to have a web page in mobile me and now is closed.  How can I get my webpage data back?

    I used to have a web page in mobile me and now is closed.  How can I get my webpage data back?

  • MATERIAL LEDGER  AND PRICE CONTROL V

    Hi Gurus. In a Plant I've activated material ledger and some materials have price control V. how does price control V works with material ledger? the average price is uptated at the end of the month or is updated with every receipt? Kind Regards.

  • Lightroom Photoshop and Camera Raw Converter

    Hi, I use Adobe creativ Cloud with Lightroom 5 and PS CC CS6. And I installed Topaz Adjust as a Plugin. On my Computer is Windows 8.1, 64 Bit installed, I tryd to open a Photo *.CR2 in order to develop it with the Camera Raw Converter from PS CS6, bu

  • Premiere Elements 12 - driver problems

    I just purchased PE 12 and looks like I am not the only one having 'incompatible display driver' problems.   I am using an HP Pavilion dv7t 6C00 CTO Entertainment Notebook PC.   The drivers in the Device Manager are: Intel (R) HD Graphic Family, Driv

  • Skype 6.22 stuck on Signing In screen - Can't logi...

    Hi, I am using Skype 6.22.0.107 on windows 8 computer. When I am trying to login to skype, it does stuck on "Signing In". I tried after killing skype from task manager as well  as restarting computer but it doesnt work. I am using hign speed internet