Fieldpoint - How to reconfigured Field point hardware configuration

Respected Sir,
We are using labview version 5.1, operating system windows 95, FiledPoint explorer 1.6,
I would kindly request all to please help to solve how to reconfigured Field point hardware, I am new learner of labVIEW.
When i run Fieldpoint explorer 1.6, in labview 5.1 operating WINDOWS 95 version, i received one command as
A value return from the server is out of the expected range.
The FieldPoint hardware ranges need to be re configured, so they match the ranges saved in the configuration file.
Go to each device configuration dialog and select channel configuration to synchronize the saved configuration with the hardware configuration.
Thanking You
Yours faithfully
M.Viajy

That is correct. There is no way to simulate a FieldPoint device. The suggested workaround should work well for you, however. Create some simulated VIs that perform the same task as the FieldPoint writes and reads (at least in terms of what inputs they accept or outputs they have), and place them in the other case in a Case Structure as the FieldPoint VIs.
LabVIEW 8 takes these possibilities one step further with Conditional Disable Structures and Diagram Disable Structures. The difference between these two structures and a Case Structure is that code in the disabled cases doesn't even compile. This means you could even have broken wires or broken subVIs inside the disabled case, and you'd still be able to run your program. In the case of this FieldPoint application, you could use a Conditional Disable Structure that automatically polls the target OS type (Windows, Linux, Pharlap ETS, etc) and selectively compiles one case based on the target OS. This would allow you to seamlessly run VIs on your computer and FieldPoint without modifying any code. The other advantage is that the simulated FieldPoint code wouldn't get compiled when you target your real FieldPoint device, so you wouldn't increase your code size or memory usage unnecessarily for the final product.
Message Edited by Jarrod S. on 04-24-2006 03:51 PM
Jarrod S.
National Instruments

Similar Messages

  • How to see my IPAD hardware configuration ( Like Hard disk  drive , processor and camera pixels )

    How to see my IPAD hardware configuration ( Like Hard disk  drive , processor and camera pixels )

    Yeah. It is called System Status.
    Check out this application on the App Store:
    System Status - device activity monitor (battery level, disk usage, file stats, CPU load, network details, memory info, process list, work time, charge monitoring, connection overview, routing table, os data, hw report, console log, netstat information)
    Techet
    Category: Utilities
    Updated: Oct 27, 2011
                       687 Ratings
    iTunes for Mac and Windows
    Please note that you have not been added to any email lists.
    Copyright © 2012 Apple Inc. All rights reserved
    Sent from my iPad

  • How to run field point vi without the fieldpoint?

    I'm running LV 7.1.  I'm writing a vi that uses compact fieldpoint modules for DAQ and control.  The system is located in another lab.  I'd really like to be able to work on the vi at my desktop, but of course not having the cFP connected makes that a problem, at least when I try to run the program.
    Is there some sort of "dummy" mode for cFP that will let my system actually run the vi?  The cFP is on a private subnet, so I can't get to it over ethernet (although I guess I could try putting it on the public net).  I could replace all the cFP express vis, I guess, but that would be a real pain to swwitch back and forth.
    Thanks, Rob

    That is correct. There is no way to simulate a FieldPoint device. The suggested workaround should work well for you, however. Create some simulated VIs that perform the same task as the FieldPoint writes and reads (at least in terms of what inputs they accept or outputs they have), and place them in the other case in a Case Structure as the FieldPoint VIs.
    LabVIEW 8 takes these possibilities one step further with Conditional Disable Structures and Diagram Disable Structures. The difference between these two structures and a Case Structure is that code in the disabled cases doesn't even compile. This means you could even have broken wires or broken subVIs inside the disabled case, and you'd still be able to run your program. In the case of this FieldPoint application, you could use a Conditional Disable Structure that automatically polls the target OS type (Windows, Linux, Pharlap ETS, etc) and selectively compiles one case based on the target OS. This would allow you to seamlessly run VIs on your computer and FieldPoint without modifying any code. The other advantage is that the simulated FieldPoint code wouldn't get compiled when you target your real FieldPoint device, so you wouldn't increase your code size or memory usage unnecessarily for the final product.
    Message Edited by Jarrod S. on 04-24-2006 03:51 PM
    Jarrod S.
    National Instruments

  • I want to access LabView and Field Point Library through Visual Basic. Where can I find adequate information considering that I am just an starter.

    My aim is to have a ActiveX Control on a web page that can control the field point hardware as a small step towards home automation through the internet.

    The place to start is here :
    http://sine.ni.com/apps/we/nioc.vp?cid=3769〈=US
    This is labview's measurement studio homepage. This contains component works which is a toolkit for visual basic. This should give you all the info you need to get started.
    Jared

  • I purchased an iPad A 1460 which was supposed to have an A6x chip. The hardware configuration shows it as an A5x chip. Can anyone advise a solution ?

    HI. I purchased an IPad model A 1460 which was supposed to have an 1.4 ghz A6x chip. The hardware configuration however shows that my IPad has an A5x chip. How can this issue be resolved ?

    How are you getting this "hardware configuration" information?
    If you are using a third-party app, most likely the app is not up to date and does not know about the newer iPad processor to show information about it.

  • How to configure field point cFP2120

    Hi,
         I am doing a project using LabVIEW... I am using field point cFP2120  as the interface... The problem is that my PC is not detecting the field point... Can you suggest a solution???

    Hi jaks,
       From the user manual:
    Number of Flashes        Error Condition
    0 (stays lit)                     The cFP-21xx did not power on correctly. Contact
                                           National Instruments for assistance.
    1                                     The cFP-21xx is in reset mode or is unconfigured. Make
                                           sure the RESET IP switch is in the OFF position and
                                           restart the controller. Refer to the Measurement &
                                           Automation Explorer Help for FieldPoint for more
                                           information about configuration.
    2                                     The cFP-21xx has detected an error in software. This
                                           usually occurs when an attempt to upgrade the software
                                           is interrupted. Repeat the software upgrade process.
    3                                     The cFP-21xx is in safe mode. Either the controller is
                                           ready for software installation or the SAFE MODE
                                           switch is in the ON position.
    4 (or more)                    The cFP-21xx has detected an unrecoverable error.
                                          Contact National Instruments for assistance.
    In which of these condition are you?  If you never configured that module, and led flashes once, you have the  correct start-up condition, but it is strange that you cannot access module; check if Windows Fierewall is turned ON or if Antivirus' firewall is ON, they can be blocking MAX in connecting to device!
    graziano

  • The field point 4.1 software does not get installed, how to install the software and work on field point 20xx

    We want to know the basics of installation of field point s/w and where to start from after installation.
    Then we also need the details of HOW TO WORK in it. what are the other hardware and software that are necessarily to be installed along with field point in the PC. How to connect the hardware fp2000, to the PC.
                      Actually we tried installing the field point s/w, but we did not get the field point explorer icon to continue working.

    Hi.
    You can find informations in the NI Developer Zone (Distributed I/O -Fieldpoint)
    http://zone.ni.com/devzone/devzone.nsf/webcategories/67EFA8729F4A7741862567E1006EDA74
    and here for the Basics:http://zone.ni.com/devzone/conceptd.nsf/webmain/2124F6BBD29663D886256CB80054DBD7
    Configure your fieldpoint in MAX.

  • How can I get all the options of Field Point Explorer 3.0.2 in Measuremen​t and Automation Explorer 3.1?

    I am a student using LabVIEW and Compact Field Point to implement a
    senior design project in Electrical and Computer Engineering.  We
    have LabVIEW 7.1 and a cFP-2020 and additional modules.  We are
    trying to use the CTR-500 module to output a pulse train to drive a
    stepper motor.  We have found instructions online of how to do
    this, but they all use Field Point Explorer.  The instructions
    make use of options in Field Point Explorer that are not included in
    Measurement and Automation Explorer (the software included with the
    cFP).
    I have downloaded Field Point Explorer 3.0.2 and followed the
    directions.  Now, in LabVIEW, when I using the newly created .iak
    file, I get a dialogue asking to find the SubVI: 'FP Read (Float Array
    -IO).vi'.  Included with LabVIEW are subvis for FP Read, but not
    with the float array part.  So I figure I cannot use Field Point
    Explorer created .iaks with LabVIEW 7.1.  So how cannot I access
    the same options in Measurement and Automation that I was able to find
    in Field Point Explorer?
    Thanks

    Hi,
    FieldPoint Explorer is no longer used to configure FieldPoint systems. However, I do not think that the configuring your system in FieldPoint Explorer is causing the error.
    FieldPoint systems are now setup in Measurement and Automation Explorer (MAX).  Information on setting up FieldPoint systems in MAX can be found in the MAX help under: Installed Products>> FieldPoint. Also, I recommend upgrading to the latest FieldPoint driver and version of MAX.  The FieldPoint VI's will be slightly different when you upgrade, so there is a good chance that this will eliminate the error.
    Regards,
    Hal L.

  • How do i measure the frequency of a sine wave using a field point counter module

    I need to measure the frequency of the sine wave using field point. is it possible and if yes how. do i need to convert the sine wave signal to square wave. Please let me know.

    It probably would be easiest to convert the sine wave to a square wave with a simple external circuit and then use a counter module to measure the frequency. There is a shipping example in LabVIEW that shows how to measure frequency with a FieldPoint Counter module.
    JRA

  • Using field points how the dc voltage measuremen​t is done?

    i am new to labVIEW..  Using cFP-AI 100  i am trying to measure a dc voltage [5volts].. all the field point items are configured on MAX. when the example VI provided runs there is error indicating that the connection is broken or network module is not pwered on.. but i have checked both .. What may be the problem?

    Hi ELUE,
    When you say "all the FP items are configured on MAX," does that mean you can see and connect to the device? Can you take readings in MAX from the FieldPoint module I/O menu under the Data Neighborhood?
    If you're able to read from the I/O menu you are probably using the default I/O point in the example. It's usually necessary to choose the I/O point before running the example.
    Cheers.
    | Michael K | Project Manager | LabVIEW R&D | National Instruments |

  • Using field points how the dc voltage measurement is done?

    i am new to labVIEW.. Using cFP-AI 100 i am trying to measure a dc voltage [5volts].. all the field point channels are configured on MAX. when the example VI provided runs with the proper i/o point is selected] there is error indicating that the connection is broken or network module is not pwered on.. but i have checked both .. What may be the problem?

    Hi ELUE,
    Could you please let me know if the status LED (or any other LEDs are blinking) in a particular pattern on your fieldpoint controller? Also, could you please let me know what controller you are using and if you get a particular error code? Thanks!
    Best regards,
    Steven

  • How can LabView 7.0 find the field point IO?

    Please see the attachment.
    Thank you
    Attachments:
    Field Point problem.doc ‏45 KB

    Did you actually read the pop up?
    You need to set up your device in MAX by finding in the Remote Systems area, right clicking and selecting Find Devices. Then you need to save your configuration in an iak file (from the Tools>>FieldPoint menu) and then you need to load that iak file in LV as described in the pop up.
    Try to take over the world!

  • Very Urgent: how to define field symbols in class using se24 Points assured

    hi all
    I am new to abap oo programming. I am using se24 to build a class
    where some methods have code which involves working with field sybmols but i am not able to figure out way for how to define field symbols in the attributes section.
    I tried defining like : fld_sym type ref to  dbtab-fld
    but in the method implementation if i try to use it like assign fld to <fld_sym> there it says fld_sym is not defined as a field symbol.
    So can anyone please guide me how to define field symbols in se24.
    Also what should be the general steps while creating a class using se24.
    Points assured
    thanks

    Hi
    Global classes are like Global fun modules in which the Methods and code is already written and is mainly used for Reusability purpose.
    Goto SE24 tcode and see the std global classes like
    CL_ABAP_CHAR_UTILITIES
    see the links
    chk out the links below:
    General Tutorial for OOPS
    https://www.sdn.sap.com/irj/sdn/go/portal/prtroot/docs/library/uuid/e8a1d690-0201-0010-b7ad-d9719a415907
    Have a look at these links for OO ABAP.
    http://www.sapgenie.com/abap/OO/
    http://help.sap.com/saphelp_nw04/helpdata/en/c3/225b5654f411d194a60000e8353423/content.htm
    http://www.esnips.com/doc/375fff1b-5a62-444d-8ec1-55508c308b17/prefinalppt.ppt
    http://www.esnips.com/doc/2c76dc57-e74a-4539-a20e-29383317e804/OO-abap.pdf
    http://www.esnips.com/doc/5c65b0dd-eddf-4512-8e32-ecd26735f0f2/prefinalppt.ppt
    http://www.allsaplinks.com/
    http://www.sapgenie.com/abap/controls/index.htm
    http://www.esnips.com/doc/2c76dc57-e74a-4539-a20e-29383317e804/OO-abap.pdf
    http://www.esnips.com/doc/0ef39d4b-586a-4637-abbb-e4f69d2d9307/SAP-CONTROLS-WORKSHOP.pdf
    http://help.sap.com/saphelp_erp2005/helpdata/en/ce/b518b6513611d194a50000e8353423/frameset.htm
    SDN Series:
    https://www.sdn.sap.com/irj/sdn/developerareas/abap?rid=/webcontent/uuid/35eaef9c-0b01-0010-dd8b-e3b0f9ed7ccb [original link is broken]
    http://help.sap.com/printdocu/core/Print46c/en/data/pdf/BCABA/BCABA.pdf
    Basic concepts of OOPS
    https://www.sdn.sap.com/irj/sdn/go/portal/prtroot/docs/library/uuid/b6cae890-0201-0010-ef8b-f970a9c41d47
    https://www.sdn.sap.com/irj/sdn/go/portal/prtroot/docs/library/uuid/1591ec90-0201-0010-3ba8-cdcd500b17cf
    https://www.sdn.sap.com/irj/servlet/prt/portal/prtroot/com.sap.km.cm.docs/library/webas/abap/abap%20code%20samples/alv%20grid/abap%20code%20sample%20to%20display%20data%20in%20alv%20grid%20using%20object%20oriented%20programming.doc
    http://www.henrikfrank.dk/abapuk.html
    http://www.erpgenie.com/abap/OO/
    Reward oints if useful,
    Aleem.

  • How to use the FP-DO-AC120 module on Field Point?

    Hi,
    I am trying to use a FP-DO-AC120 (discrete output module) as a relay to switch of an equipment I control via Field Point 2000. This FP-DO-AC120 is connected to a FP-TB10 terminal base along with some other modules. When I try to use the “write” function on MAX (Measurement and Automation Explorer), it doesn’t allow me to do so and the “this item is read only” pops up. Checking the channel type to where the module is plugged in it shows that is a discrete input channel. I’ve tried to change it to a discrete output type, but when I do so, the status of that slot is “empty base or terminal”. I don’t understand what is going on here. Could anyone please advise?
    Thanks for the help.
    Adriana

    Adriana,
    I found a similar discussion forum thread that addresses the same issue.
    My FP-DO-AC120 module is being read as DI in FP Explorer, Why?
    This is an older post, so keep in mind that all the functionality of FieldPoint Explorer is now included in MAX.
    Otis
    Training and Certification
    Product Support Engineer
    National Instruments

  • Please tell me how you got the computer to reboot again once it was on the black screen saying "setup is inspecting your hardware configuration?"

    Please tell me how you got the computer to reboot again once it was on the black screen saying "setup is inspecting your hardware configuration?"

    Hi,
    use the power-switch on the left backside of your iMac to turn your Mac off.
    Use it again to restart your Mac and hold down the Alt/Option-button to get to the Boot Selection screen.
    Choose OSX.
    Once in OSX go to System Preferences - Startup Volume and reset it to use OSX as the default.
    Am I right assuming that you try to install Windows XP on a new (2011) iMac ?
    If so, XP is no longer supported by Apple for use/install With BootCamp.
    But there are some success stories when using a XP with SP3.
    Regards
    Stefan

Maybe you are looking for

  • Adobe Acrobat 9.0 has stopped working

    I have just downloaded and installed adobe acrobat 9.0 on a Windows Server 2008. Installl process went find. When starting the program it eventually wil give me the error "Adobe Acrobat 9.0 has stopped working". I get an option to find a solution on

  • Fax and Print

    Hi , Can we setup the fax number / printer dynamically for bursting in BI Publisher? Regards, Saurabh

  • Untrusted Forest Discovery

    Hi all, installed SCCM 2012 R2 in one domain - all seems to be functioning well. We have a second, untrusted domain which I need to deploy a DP and MP into. In order to do this I first need to use the Add Forest feature to discover the untrusted doma

  • Horizontal Scroll unavailable when Left Sidebar region present

    Hi, I have created a classic report in Apex 4.0 which has so many columns (end user requirement) that one has to horizonatal scroll to review the whole of the report content fields returned. This is fine... Up until the point that I implement a sideb

  • BT Infinity activation/connection problems

    Hello all, Please help!! As part of a house move I had the opportunity to upgrade from standard broadband to Infinity....Initially my activation date was 7th April 2014, and my TV and landline were both completed on that day.  Infinity activation was