I need help resolving the issue of all channels being "clipped" by the (high and low limits) on the AI-Config sub-vi

No matter what values I put in the corresponding channel index, all channels appear to be using the 'first' index of the limit cluster. I am using a PCI-6110E 5Ms board and LabVIEW 5.0. Has anyone else encountered this problem?

If you want to have different input limits for the different channels, you need to make sure the channels are listed in separate Channel indexes as well. For example, if your channel array index 0 reads "0:7", then channels 0 through 7 will all use the input limit settings in the input limit array's index 0.
Instead, enter "0" in Channel Array index 0,
"1" in Channel Array index 1, etc.