Modbus Object Bug?

Another problem with modbus object?  Maybe so.
PLCs are Koyo DL06, same program, exactly just different modbus addresses.  Sites poll every 60 seconds. I have the modbus objects copied exactly the same settings (except station address of course). 
PLC1:  Connection on 40889 sets a 1 on every other poll. Polls. Updates. Done.  All good.
PLC2:  Connection on 40889 sets a 1 on every other poll. Polls. Updates. Polls. Updates. Polls. Updates....  It doesnt stop.
Heres the funny thing.  If i make a new modbus object:
PLC2TEMP:  Connection on 40889 sets a 1 on every other poll. Polls. Updates.  Done.
My modbus.ini settings:
[all]
UpdateOutputs=2
RefreshOutputs=1
Thanks for the help
Mike
Mike Crabtree - Lead Developer
Destek of Nevada, Inc. / Digital Telemetry Systems, Inc.
(866) 964-6948 / (760) 247-9512

I do the same configuration and test on my computer.  It polls every 15 sec. UpdateOutputs=2 RefreshOutputs=1, "immediately write" checked.
The below is the log file on serial port.
[01][01][00][00][00][01][FD][CA] is the read on every poll. See, if the write output is not changed, there is no write function sent out. On every poll, it just reads the value back, no write.
After I change the switch to ON, it sends out [01][05][00][00][FF][00][8C][3A] immediately. [05] is write single coil.
So, when immediately write is checked, UpdateOutputs is almost meaningless, because the output will be updated immediately.
What do you mean by "Updates. Done.  All good." I think if you set polls=60 sec, it should poll every 60sec, it should not stop polling.
So could you also make the log file on serial port? With the log file, we may find something.
15:23:37.2 - Modbus1 ->
[01][01][00][00][00][01][FD][CA]
15:23:37.3 - Modbus1 <-
[01][01][01][00][51][88]
15:23:52.2 - Modbus1 ->
[01][01][00][00][00][01][FD][CA]
15:23:52.3 - Modbus1 <-
[01][01][01][00][51][88]
15:23:52.6 - Modbus1 ->
[01][01][00][00][00][01][FD][CA]
15:23:52.6 - Modbus1 <-
[01][01][01][00][51][88]
15:23:52.6 - Modbus1 ->
[01][05][00][00][FF][00][8C][3A]
15:23:52.7 - Modbus1 <-
[01][05][00][00][FF][00][8C][3A]
15:24:07.3 - Modbus1 ->
[01][01][00][00][00][01][FD][CA]
15:24:07.3 - Modbus1 <-
[01][01][01][01][90][48]
15:24:22.3 - Modbus1 ->
[01][01][00][00][00][01][FD][CA]
15:24:22.3 - Modbus1 <-
Ryan Shi
National Instruments

Similar Messages

  • Communication problem with Modbus object in Lookout 3.8

    What means the error code 06 besides the following alarm message NO COMMUNICATION RESPONSE FROM MODBUS SECONDARY ? Lookout runtime-express version 3.8 build 7

    Greetings,
    The alarm message "No Communication response from modbus secondary" means that communication cannot be established between the modbus object and your external device. Verify that you have set up the serial port settings properly and that you have configured the modbus object. Verify that your external device is functioning properly and connected to the PC. If all of these things are ok, you may need to increase the receive gap of the serial port settings and the receive timeout of the modbus object. There is a tutorial on the web which outlines the troubleshooting steps for communication in Lookout.
    http://zone.ni.com/devzone/conceptd.nsf/webmain/033CD84BAC7E1E7586256A3300756284?opendocument
    I hope this information is helpful. Have a good day!
    Patrick R.

  • Inhibiting a Modbus object's Commfail alarms from inidicating on the alarm panel

    I have an Lookout v5.0 application that runs under W2K, SP2. This application has 65 modbus objects that have individual pots that are tied to the poll rate for their respective modbus object. When there is a failure of a modbus object, usually vandalism at the remote RTU site bring down the PLC, I would like to inhibit the modbus object from indicating commfail in the alarm window. I know about setting the poll rate to zero or some large number, but this still does not remove the alarm. Even blanking the poll rate field does nothing to remove the alarm. I would like to remove the existing alarm and prevent any further alarms from indicating on the alarm window. Visualize like a modbus alarm enab
    le/disable switch. Any suggestions?

    Hello,
    Thank you for contacting National Instruments.
    I looked into your questions about disabling the Modbus Comm alarms. The easiest way I�ve found to disable these alarms is to set the Alarm Priority for the Modbus objects to �0�. This should make the alarms not ever appear in the Alarms Window. The only downside to this is that the Alarm Priority cannot be set programmatically so once you set it to 0 you will never see the alarm until you set it to a value grater than 0.
    A second option that may or may not work for you is to use a Pulse object to continually acknowledge the alarm area where the Modbus Comm Alarms appear (this defaults to the �comm� area). To do this just create a Pulse object and then create a connection from the $Alarm.comm.ack to the Pu
    lse object�s output (the expression might look like �$Alarm.comm.ack=Timer1�). The downside to this approach is that this will only acknowledge the alarms from that area, so if the alarm is still active (for instance if the communications to the RTU is still failing) then the alarm will still appear in the Alarms window in an acknowledged state. The alarm won�t disappear until the fault condition goes away.
    I hope this helps. Let me know if there is anything I can help with or clarify.
    Ken S.
    Applications Engineering
    National Instruments

  • AS3 Masking with multiple objects bug

    Hi again.
    I have simplified my script to tell more about the problem.
    I'm creating Sprite which holds other Sprites with graphics. The whole Sprite is used to mask MovieClip.
    When I don't apply it as a mask, it shows, that objects are rendered correctly. But when I add it as a mask, flash fails to draw a mask where those Sprite objects overlap each other. You can see an example here:
    With no masking applied: http://imageshack.us/photo/my-images/29/screenshot20110914at432.png/
    With masking applied: http://imageshack.us/photo/my-images/233/screenshot20110914at433.png/
    As i've seen, this bug doesn't occur everytime mask overlaps.
    What could be the problem?

    bump...

  • Photoshop CC 14.2 Smart Objects Bug

    Hey,
    While updating to the latest Photoshop CC 14.2 (today, 17.01.2014) I've found a huge bug with the traditional smart objects behavior.
    I recorded a video. Please, take a look on it.

    SG... wrote:
    Hi Herbert2001,
    What do you mean by 'smart objects do not update in realtime'? Can you outline steps to exhibit the behavior?
    regards,
    steve
    Suppose you wanted to create a mirrored setup with two or more smart objects, or your project consists of multiple smart objects that are used throughout the design as repeatable patterns (let's say jewels, or textures).
    So you open the contents of the smart object in a new window, and arrange both windows horizontally. Now draw in or change the smart object's contents - nothing happens in the main project. The user is forced to save the smart object first before the changes are applied. In effect a new separate file is generated.
    Very cumbersome. Even more counter-productive is that the user cannot edit a smart object's content in place in the original file, and that Photoshop opens a new window instead. (I understand that external files like Illustrator cannot be edited in place, but Photoshop elements should really have that option.)
    All of this severely breaks the workflow. An alternative workflow is presented in Photoline: the user is able to create virtual clones/instances of any type of layer, layer groups, and layer masks, and when the source layer is edited in some way those changes update in real time cascading throughout the project. No need for the content to be opened in a separate window. Also worthy of note is that the changes are applied while the user draws or changes the vector shape(s) - which makes it incredibly useful for mirrored painting, to cite just one example.
    Flash also offers this type of functionality: double-click a symbol, and the user can edit it in place. Changing the object automatically updates the other instances. Unfortunately even Flash does not update in "real time", only after you made the changes does it update the instances.
    All in all, dealing with smart objects in Photoshop is a bit of a pain compared. Just not a very well thought out feature, in my opinion, and in dire need for an update - the externally linked content is a step in the good direction, but the actual implementation of "smart objects" is rather "dumb". ;-)

  • PS 14.2 Smart Object Bug

    A quick screencast demonstrating a bug in Photoshop where it gets confused between two instances of the same Smart Object, in two different documents.

    Hi,
    This has been reported and we're investigating a fix. As you've noted, this bug happens with copied Smart Object layers (even in the same document).
    Sorry for the introduction of this bug.
    regards,
    steve

  • Smart Object Bug?

    When I edit Smart Objects in CS5.5 they open in their own window; meaning I only see the smart object in my new window when I chose to edit. In CS6 I am seeing the actual document I made the Smart Object from, as well as the Smart Object when I edit the Smart Object, AND it has its own rounded border that when saved out, does not appear - it is taking that from the original for no reason.
    Windows 7 Pro 64 Bit only. I did not install 32 bit.

    Hi Zeno,
    Thanks for the suggestion. Resetting the temp directory to another location is a good workaround. I was having the same problem with another program, CuteFTP, and changing the temp dir fixed its problem too. I had previously tried running in Compatibility mode, Administrator mode and both together but none of those modes helped.
    It would still be nice to know why Windows 7 denies access to its own temp directory but at least now, I can get back to work.
    Thanks,
    David Salahi

  • Unwanted drop shadow showing up on shape objects - BUG?

    Hi all,
    I am currently using photoshop cc 2014 and pasting vector objects in as a "Shape Layer" - for some reason a shadow is showing up around every object i create since i upgraded to cc 2014 but it is NOT a layer style. How do i remove this? is it a graphics issue or processor issue? Does anyone know the settings to allow me to create shapes with sharp edges?
    Any help would be greatly appreciated

    I'm running into a similar problem. I've pasted a shape from illustrator as a vector smart object. When I have a green rectangle below it, there is no drop shadow. But when I hide that layer, the drop shadow clearly shows above the white background.
    It appears to be controlled by the global light under layer styles, but I can't turn it off even when "Drop Shadow" is unclicked.
    Drop shadow clearly showing, even when it's unclicked in Layer Style.
    No Drop Shadow showing when there is a green rectangle underneath.
    Drop Shadow appears over white Background when the green rectangle is turned off.
    Drop Shadow appears to be controlled by Global Light, but there seems to be no way of turning it off.
    What am I missing here? Any help would be awesome. Thanks!

  • LoadVars & XML object bug?

    hi all
    me try the code below and found that onLoad() never fire when
    the file are zero byte(empty)
    is it the bug in Flash?
    //where the "test.txt" are the file which with zero
    byte(empty)

    Flash is probably waiting for some bytes coming in...
    But what real-life application do zero-byte text files
    have?

  • Counter-Strike Source white objects bug? :(

    Hey!
    Long-time lurker, first-time poster here ... first of all - I LOVE Arch! ^_^.
    But it makes my CS:S sad. These are my launcher settings:
    -game cstrike -nojoy -dxlevel 80 -w 1152 -h 864 -windowed
    And my userconfig:
    rate 30000
    cl_updaterate 75
    cl_cmdrate 101
    cl_interp "0,013333333333333333333333333333333"
    cl_crosshairusealpha 1
    cl_crosshairalpha 800
    cl_dynamiccrosshair 0
    violence_hblood 1
    violence_ablood 1
    violence_agibs 1
    violence_hgibs 1
    hud_fastswitch 1
    fps_max 300
    jpeg_quality 100
    mat_picmip 1
    r_lod 1
    cl_forcepreload 1
    r_drawmodeldecals 0
    r_dynamic 0
    r_3dsky 0
    r_teeth 0
    gl_clear 0
    mat_bumpmap 0
    However, I keep getting results like these:
    I've already tried:
    * Enabling/Disabling GLSL
    * dxlevel 90, 81, 80 and 70
    * Enabling/Disabling pixel shaders under WINE
    My config specs are as follows:
    * P4 3.2Ghz
    * GeForce4 Ti 4200 AGP8X 128Mb
    * 1,5Gb RAM
    * nvidia-96xx drivers
    * WINE 1.1.5 from pacman, not AUR.
    Any help?
    Last edited by DARKGuy (2008-09-28 20:46:50)

    Nope, but I got smoother shading with -dxlevel 95 and some config lines:
    cl_phys_props_enable 0
    cl_phys_props_max 0
    cl_ragdoll_physics_enable 1
    cl_show_splashes 0
    cl_smooth 0
    fog_enable 0
    fog_enable_water_fog 0
    mat_bloom 0
    mat_bumpmap 0
    mat_clipz 0
    mat_fastnobump 1
    mat_fastspecular 1
    mat_specular 0
    mat_picmip 0
    r_avglight 0
    r_eyeglintlodpixels 0
    Still, the same overbright error happens. It also happens with the windows on the walls, props, barrels, and so on.

  • I get error, "can not load NETLIB.dll" on a MODBUS Plus Object.

    I have 18 Modicon PLCs in my network, using LOOKOUT for my HMI. Only one PLC gives this error.
    Can you help me?
    J. Bubba

    thank you !
    i have tried to make new installation of lookout in eveluation mode, with only one point in ModBusPlus
    the problem is the same but after i have added manualy the dll and apparently this is a good solution
    another problem is the selection of serial port, in modbus object thi is possible only in serial ModBus option but non in ModBusPlus option
    i think to modify the port in .lks files and recompiling this, is correct ?
    the next week i tried with the scada the same procedure
    because in my (two different) computer the installer work [apparently] fine but not install netlib.dll  ?
    intel processor, winXP.p SP2 without any firewall, one without antivirus (the scada) and one with avast professional (the tried machine)
    is a problem in modplus plus driver in this version (see precedent post) ?
    is made specific patch or document by NI ?
                   B_N_

  • Immediately write outputs - more on modbus plus performance

    more on modbus plus performance
    I have more dilemmas considering modbus plus. I'm trying to reduce the unnecessary traffic as much as possible, so I've unchecked "immediately write outputs" in advanced settings for modbus plus hoping that lookout will write to plc only when modbus object is polled. However, it seems that it doesn't happen that way, looks to me like lookout is writing to plc poll or no poll. I need to cut down the traffic because I have delay in system response and I'm considering lookout's share in it.
    I have a feeling that making a system with deterministic response (which should be one of mb+ highlights) is quite cumbersome and sometimes impossible.
    Can anyone comment on this issue and maybe share ideas for improving modbus response time? Is there anything about modbus plus and lookout on ni.com that I'm not aware of?
    Darko

    By default, Lookout writes Outputs immediately (without waiting for the poll).  BUT, if you uncheck the "immediately write outputs" setting, it should write only when polled.  If it's not doing this, it's a bug -- can someone at NI verify this? 
    Couple of things you can try for improving communication performance:
    1. Make sure you're not writing outputs every-so-many polls (unless you really have to).  By default, Modbus Object writes the Outputs every 100th poll -- even if none of them have changed.  Use the Modbus INI settings to change this behaviour:
    http://digital.ni.com/public.nsf/allkb/2E64D5CF87CA6A1086256BB30070DC1A
    2. If you have some IO points which don't need to be read as fast as others, use a second Modbus object for these with a slower poll rate (but on the same address, etc.). 
    3. Use an appropriate update deadband for your analog reads -- you can filter out "noise" from data this way.  Note that the IO are still read every poll, but aren't propagated to the rest of the system unless the deadband is surpassed.
    Hope this helps,
    -Khalid

  • Lookout's Modbus Slave Address

    Hi,
    It appears that the Modbus Slave (Ethernet) Object in Lookout (6.0.1) doesn't work with an Address (or "Identifier") greater than 127. 
    I tried a simple test with the Modbus Object in one process with an address of 128.  And a ModbusSlave Object in another process with its address as 128.  There's no communication.  However, when I make the addresses 127 (or lower), they yak like nobody's business! 
    I haven't tested the Serial version though. 
    Est-ce un bug?
    -Khalid

    Hi Khalid,
    I think I was overlooking the Lookout 6.01 version that you mentioned earlier in your post  ! I was able to recreate the issue that you are facing if I create a modbus slave object in Lookout 6.01 version. Thats a bug! And version 6.02 has a fix for it!
    Have a great day!
    Regards,
    Prashanth

  • Lookout modbus plus performanc​e

    I'm running 9 Schneider Electric PLCs Compact 265 connected to Lookout v5 PC via modbus plus. I have cyclic stalls of transport, each 50 secs or so, which last for 3 or even more seconds. I've tried all the settings there are on modbus object in Lookout, but with no success, only different graph shapes in performance monitor (you can have a look at graphs at the end of mail). Even single PLC on network (with others shut down) freezes the communication for more then second, which is unacceptable since I need to refresh my data at least each 350ms.
    I've considered 3 things:
    1. PLC underperforms
    I've checked scan time in PLCs, they're all running smooth with scan time under 90ms. This time doesn't increase even during modbus peaks, I've reduced watchdog to 100ms and it never triggered. Looks to me like plc has more than enough time for modbus, so plc should not be the problem.
    2. PC underperforms
    Hardly a problem, PC running under 5% most of the time, never goes over 50% no matter what I do.
    3. modbus underperforms
    Statistics show no garbled or timed out frames on any plc, so wiring should be fine.
    PLC uses 130 registers of memory (type 4 – holding register). With all registers back to back (no slack between registers), this should mean that all the memory can be transferred in 2 frames. This also means total data load per sec should be
    9 plcs * 3 refreshes * 130 reg * 2 bytes = 7030 bytes.
    Even with overhead included, this is so little compared to theoretical 120 kbytes modbus plus should be able to perform, so nothing else for me to do but scratch my head.
    I've checked Lookout source for any loops which could initiate some read or write at 50sec cycle, but there's nothing even close anywhere in program.
    Am I missing something? Can anyone tell me why modbus freezes my system?
    Bye everyone,
    Darko
    SVETLOST TEATAR

    Hello,
    It’s been a while since I last checked the forum, but in the meanwhile I’ve resolve the problem.
    The solution lies in modbus.ini and the way modbus object communicates with modbus secondary, an issue not properly covered by help and ni.com. Unless defined otherwise in modbus.ini, modbus object will refresh all of the configured memory points in your plc each 50 or so polls (I can’t remember which is the default value). This can be a problem if the number of memory points is large, because it congests modbus and creates performance stalls.
    You can read more about this here: Lookout Driver Objects - Custom INI File Settings (http://zone.ni.com/devzone/conceptd.nsf/webmain/E​54F75254BBE772786256CFC00700B5F).
    Thanks everybody for joining in.
    Bye,
    Darko

  • [Patch 정보] TRACKING BUG FOR CUMULATIVE MLR#6 ON TOP OF BPEL PM 10.1.3.3.1

    최근에 출시된 BPEL PM 10.1.3.3.1의 통합패치입니다.
    아래는 readme.txt에 포함된 patch list입니다.
    # WARNING: Failure to carefully read and understand these requirements may
    # result in your applying a patch that can cause your Oracle Server to
    # malfunction, including interruption of service and/or loss of data.
    # If you do not meet all of the following requirements, please log an
    # iTAR, so that an Oracle Support Analyst may review your situation. The
    # Oracle analyst will help you determine if this patch is suitable for you
    # to apply to your system. We recommend that you avoid applying any
    # temporary patch unless directed by an Oracle Support Analyst who has
    # reviewed your system and determined that it is applicable.
    # Requirements:
    # - You must have located this patch via a Bug Database entry
    # and have the exact symptoms described in the bug entry.
    # - Your system configuration (Oracle Server version and patch
    # level, OS Version) must exactly match those in the bug
    # database entry - You must have NO OTHER PATCHES installed on
    # your Oracle Server since the latest patch set (or base release
    # x.y.z if you have no patch sets installed).
    # - [Oracle 9.0.4.1 & above] You must have Perl 5.00503 (or later)
    # installed under the ORACLE_HOME, or elsewhere within the host
    # environment.
    # Refer to the following link for details on Perl and OPatch:
    # http://metalink.oracle.com/metalink/plsql/ml2_documents.showDocument?p_database_id=NOT&p_id=189489.1
    # If you do NOT meet these requirements, or are not certain that you meet
    # these requirements, please log an iTAR requesting assistance with this
    # patch and Support will make a determination about whether you should
    # apply this patch.
    # 10.1.3.3.1 Bundle Patch 6823628
    # DATE: March 14, 2008
    # Platform Patch for : Generic
    # Product Version # : 10.1.3.3.1
    # Product Patched : Oracle(R) SOA
    # Bugs Fixed by 10.1.3.3.1 Initial patch 6492514 :
    # Bug 5473225 - PATCH01GENESIS HOT UNABLE TO CATCH AN EXCEPTION DURING A
    # TRANSFORM
    # Bug 5699423 - PARTNERLINK PROPERTY THAT SET BPELXPROPERTY FUNCTION DOESN'T
    # WORK
    # Bug 5848272 - STATEFUL WEBSERVICES DEMO ON OTN DOES NOT WORK 10.1.3.1
    # Bug 5872799 - ANT DEPLOY BPEL TEST FAILS/RUNS ON DEFAULT DOMAIN NOT
    # SPECIFIED TARGET DOMAIN
    # Bug 5883401 - ALLOW A WAY TO CREATE EMPTY NODES - AND USE FOR REQUIRED
    # NODES
    # Bug 5919412 - SAMPLE DEMO BPEL PROCESSES MIMESERVICE MIMEREQUESTER AXIS
    # JAVA EXAMPLE ERROR
    # Bug 5924483 - ESB SHOULD SUPPORT SOAP EDNPOINT LOCATION DYNAMIC UDDI LOOKUP
    # Bug 5926809 - ORAPARSEESCAPEDXML XPATH EXPRESSION FAILED TO EXECUTE
    # FOTY0001 TYPE ERROR
    # Bug 5937320 - STRANGE BEHAVIOUR CALLING FROM BPEL TO BPEL GETTING
    # NULLPOINTEREXCEPTION.
    # Bug 5944641 - BPA BLUEPRINT NOT AVAIALBLE IN JDEVELOPER
    # Bug 5945059 - JAVA.LANG.NULLPOINTEREXCEPTION SENDING EMAILS WITH PAYLOADS
    # LARGER THAT 1MB
    # Bug 5962677 - WS RESPONSE IS EMPTY SOAP BODY IN ONE-WAY CALL
    # Bug 5963425 - WHEN THE OUTCOMES FOR A HT CHANGED & IMPORTED - UPDATE
    # CONNECTION ROLES IN BPEL
    # Bug 5964097 - AQ ADAPTER DEPLOYMENT CAUSES OPMN TO PERFORM A FORCEFUL
    # SHUTDOWN IN SOA
    # Bug 5971534 - CANNOT GRANT USER TASK VIEWS TO GROUPS, ONLY TO USERS.
    # Bug 5989367 - REFER TO SR 6252219.993 BPEL 10.1.3 ONLY COPIES IN ASSIGN,
    # IN 10.1.2 IT CREATES
    # Bug 5989527 - ENHANCEMENT WARNING SHOULD BE GIVEN UPON UPLOAD IF BPEL
    # PROCESS IS OPEN IN ARIS
    # Bug 5997936 - ESB FAULT DOES NOT GET PROPAGATED TO BPEL
    # Bug 6000575 - PERF NEED ESB PURGE SCRIPT TO PURGE BY DATE AND PROCESS
    # Bug 6001796 - POSTING OF DATE RECEIVED FROM XML GATEWAY TO BPEL FAILED IN
    # ESB
    # Bug 6005407 - BPEL PROCESS DOESN'T PROPOGATE FAULT THROWN BY BPEL
    # SUB-PROCESS
    # Bug 6017846 - MIMETYPE OF EMAIL NOTIFICATION IS NOT SET THROUGH HUMAN TASK
    # Bug 6027734 - DECISION SERVICE IMPORT - LOCATING DECISION SERVICE IN .DECS
    # FILE IMPROPER
    # Bug 6028985 - EXCEEDED MAXIMUM NUMBER OF SUBSCRIBERS FOR QUEUE
    # ORAESB.ESB_CONTROL
    # Bug 6041508 - CREATING/UPDATING DVM CAUSE EXCEPTION
    # Bug 6053708 - FTP ADAPTER DOES NOT SUPPORT ENCRYPTED PASSWORD IN
    # OC4J-RA.XML
    # Bug 6054034 - INDEX4,INDEX5 AND INDEX6 CANNOT BE USED IN BPEL CONSOLE
    # Bug 6068801 - BACKPORT OF BPEL ON WEBLOGIC - VERSION 10.1.3.3
    # Bug 6070991 - HT EXPORT DOES NOT EXPORT PARAMETERS, ALLOW PARTICIPANTS TO
    # INVITE OTHERS
    # Bug 6071001 - WSIF HTTP BINDING NOT WORKING FROM ESB
    # Bug 6073311 - STRESS SCOPE NOT FOUND ON CALLBACK - WRONG (DUPE)
    # SUBSCRIPTION IN TABLE
    # Bug 6081070 - JMS ADAPTER REJECTION HANDLER CREATE 0 BYTE FILES
    # Bug 6083419 - DECISION SERVICE SCOPE NEED TO HAVE A SPECIAL INDICATOR
    # Bug 6085799 - HUMAN TASK ADDED IN SCOPE IN JDEV IS NOT UPDATED TO BPA
    # SERVER
    # Bug 6085933 - EXPORT AND EXPLORE SHOULD USE USER LANGUAGE AND NOT ENGLISH
    # ALWAYS
    # Bug 6086281 - STRING INDEX OUT OF RANGE ERROR FOR COBOL COPYBOOK WITH PIC
    # CLAUSE HAVING S
    # Bug 6086453 - DOMAINS CREATED IN A CLUSTER GETS NOT PROPAGATED TO NEW OR
    # EXISTING NODES
    # Bug 6087484 - MULTIPLE HEADER SETTING CAUSES ESB EXCEPTION
    # Bug 6087645 - ESB SHOULD ALLOW USER PICK RUNTIME PROTOCOL (HTTP/HTTPS)
    # Bug 6110231 - TRANSLATION NOT BASED ON MQ CCSID CHARSET
    # Bug 6120226 - BPEL IS NOT SETTING THE APPS CONTEXT CORRECTLY
    # Bug 6120323 - COMPLETIONPERSISTPOLICY ON DOMAIN LEVEL HAS DISAPPEARED
    # Bug 6125184 - ESB JMS SESSION ROLLBACK ORACLE.JMS.AQJMSEXCEPTION
    # Bug 6127824 - [AIA2.0] CURRENT XREF IMPLEMENTATION IS MISSING REQUIRED
    # INDEXES ON XREF SCHEMA
    # Bug 6128247 - HTTPCONNECTOR POST() METHOD SHOULD RAISE EXCEPTION FOR ALL
    # STATUS CODES EXCEPT 2
    # Bug 6131159 - ENABLE USERS TO CHOOSE XSD WHEN CREATING A BPEL PROCESS FROM
    # BLUE PRINT
    # Bug 6132141 - PROCESS_DEFAULT TABLE STILL CONTAINS INFORMATION FROM
    # UNDEPLOYED PROCESSES
    # Bug 6133190 - ENABLING ESB CONSOLE HTTP/S IS MAKING THE CONSOLE TO COME UP
    # BLANK.
    # Bug 6139681 - BPEL WSDL LINK IN CLUSTERED RUNTIME POINTS TO A SINGLE NODE
    # Bug 6141259 - BASICHEADERS NOT PUTTING WWW-AUTHENTICATE HEADERS FOR HTTP
    # BINDING IN BPEL
    # Bug 6148021 - BPEL NATIVE SCHEMA FOR COBOL COPYBOOK WITH IMPLIED DECIMAL
    # LOSES DIGIT IN OUTPUT
    # Bug 6149672 - XOR DATA - CONDITION EXPRESSION SPECIFICATION IS NOT
    # INTUITIVE IN BPMN MODELS
    # Bug 6152830 - LOSING CONDITIONAL EXPRESSIONS CREATED IN JDEV UPON MERGE
    # Bug 6158128 - BASICHEADERS NOT PUTTING WWW-AUTHENTICATE HEADERS FOR HTTP
    # BINDING
    # Bug 6166991 - WHEN STARTING SOA SUITE,, PROCESSES FAIL DUE TO UNDEFINED
    # WSDL
    # Bug 6168226 - LOCATION-RESOLVER EXCEPTION THROWN IN OPMN LOGS
    # Bug 6187883 - CHANGES FOR BPEL RELEASE ON JBOSS- VERSION 10.1.3.3
    # Bug 6206148 - [AIA2.0] NEW FUNCTION REQUEST, XREFLOOKUPPOPULATEDCOLUMNS()
    # Bug 6210481 - BPEL PROCESS WORKS INCORRECTLY WHEN AN ACTIVITY HAS MULTIPLE
    # TRANSITIONCONDITION
    # Bug 6240028 - WEBSERVICE THAT DOES NOT CHALLENGE FOR BASIC CREDENTIALS
    # CANNOT BE INVOKED
    # Bug 6257116 - MULTIPLE HEADER SETTING CAUSES ESB EXCEPTION
    # Bug 6258925 - MESSAGE RECEIVED BY THE TARGET ENDPOINT VIA HTTP POST IS
    # MISSING THE XML HEADER
    # Bug 6259686 - TOO MANY UNNECESSARY WORKFLOW E-MAIL NOTIFICATIONS GENERATED
    # Bug 6267726 - 10.1.3.3 ORACLE APPLICATIONS ADAPTER - NOT ABLE TO CAPTURE
    # BUSINESS EVENT
    # Bug 6272427 - WEBSPHERE BPEL FAILS FOR DATA RETRIEVAL OF SIZE 500+ KB
    # Bug 6276995 - MERGE SCOPE NAME IS NOT UPDATED WHEN CHANGED IN THE SERVER
    # Bug 6280570 - XPATH EXPRESSION ERROR IN MEDIATOR FOR ASSIGNING USER-DEFINED
    # CONTEXT VALUES
    # Bug 6282339 - RETRYCOUNT DOES NOT WORK PROPERLY
    # Bug 6311039 - ONE RECORD IS INSERTED TO SYNC_STORE IF
    # COMPLETIONPERSISTPOLICY SET TO FAULTED
    # Bug 6311809 - [AIA2.0] NON-RETRYABLE ERRORS ARE NOT POSTED ON ESB_ERROR
    # TOPIC
    # Bug 6314784 - THE PRIORITY DEFINED IN THE BPA SUITE IS NOT TRANSFERRED TO
    # THE JDEV CORRECTLY
    # Bug 6314982 - THREADPOOL RACE CONDITION IN ADAPTER INITIALIZATION MESSAGES
    # NOT PROCESSED
    # Bug 6315104 - (SET)CLASSNAME MISSING IN TSENSOR JAXB OBJECTS
    # Bug 6316554 - CONSUME FUNCTIONALITY OF JMS ADAPTER FOR BEA WEBLOGIC DOES
    # NOT WORK
    # Bug 6316950 - FILEADAPTER HARPER ENHANCEMENTS SYNC WRITE AND CHUNKED
    # INTERACTION SPEC
    # Bug 6317398 - THE ICON FOR COMPUTING DIFFERENCE IS MISSING IN JDEV REFRESH
    # FROM SERVER DIALOG
    # Bug 6320506 - IMPORT FAILS WHEN THERE IS AN UNNAMED CASE
    # Bug 6321011 - CANNOT PROCESS 0 BYTE FILE USING FTP ADAPTER
    # Bug 6325749 - TRACKING BUG FOR TRACKING ADDITIONAL CHANGES TO BUG #6032044
    # Bug 6328584 - NEED A NEW XPATH EXPRESSION TO GET ATTACHMENT CONTENT VIA
    # SOAP INVOKATION
    # Bug 6333788 - COLLAPSING OF CONSECUTIVE ASSIGN TASKS BREAKS BAM SENSOR
    # Bug 6335773 - BUILD.XML CONTAINS DO NOT EDIT .. - WHILE <CUSTOMIZE> TASK
    # MUST BE IN <BPELC>
    # Bug 6335805 - AQ ADAPTER OUTBOUND DOESN'T RECONNECT AFTER FAILURE
    # Bug 6335822 - [AIA2.0] PSRPERFESB - RUNTIME DVM PERFORMANCE OVERHEAD IN ABS
    # USE CASE
    # Bug 6339126 - CHECKPOINT BPEL JAVA METHOD DOESN'T WORK IN BPEL 10.1.3.3
    # Bug 6342899 - OUTLINECHANGE.XML NOT UPDATE WITH ACTIVITY FROM NEW BRANCH
    # Bug 6343299 - ESB CONCRETE WSDL NAMESPACE SHOULD BE DIFFERENT FROM IMPORTED
    # WSDL NAMESPACE
    # Bug 6372741 - DEHYDRATION DATABASE KEEPS GROWING IN 10.1.3.3
    # Bug 6401295 - NXSD SHOULD SUPPORT ESCAPING THE TERMINATED/QUOTED/SURROUNDED
    # DELIMITERS
    # Bug 6458691 - DIST DIRECTORY FOR 10.1.3.3.1 NEEDS UPDATE
    # Bug 6461516 - BPEL CONSOLE CHANGES FOR DISPLAYING RELEASE 10.1.3.3.1
    # Bug 6470742 - CHANGE THE VERSION NUMBER AND BUILD INFO IN ABOUT DIALOG IN
    # ESB
    # BUG ADDED IN MLR#1, 6671813 :
    # Bug 6494921 - ORABPEL-02154 IF LONG DOMAIN AND SUITECASE NAMES IN USE
    # BUGS ADDED IN MLR#2, 6671831 :
    # Bug 6456519 - ERROR IN BPEL CONSOLE THREADS TAB:SERVLETEXCEPTION CANNOT GET
    # DISPATCHER TRACE
    # Bug 6354719 - WHICH JGROUP CONFIGURATION PARAMETER IMPACTS BPEL CLUSTER
    # ACTIVITY
    # Bug 6216169 - SCOPE NOT FOUND ERROR WHILE DELIVERING EXPIRATION MESSAGE OF
    # ONALARM
    # Bug 6395060 - ORA-01704 ON INSERTING A FAULTED INVOKE ACTIVITY_SENSOR
    # Bug 6501312 - DEHYDRATION DATABASE KEEPS GROWING IN 10.1.3.3 #2
    # Bug 6601020 - SEARCHBASE WHICH INCLUDES PARENTHESIS IN THE NAMES DOES NOT
    # WORK
    # Bug 6182023 - WAIT ACTIVITY FAILS TO CONTINUE IN CLUSTER WHEN PROCESSING
    # NODE GOES DOWN
    # BUGS ADDED IN MLR#3, 6723162 :
    # Bug 6725374 - INSTANCE NOT FOUND IN DATASOURCE
    # Bug 4964824 - TIMED OUT IF SET CORRELATIONSET INITIATE YES IN REPLY
    # ACTIVITY
    # Bug 6443218 - [AIA2.0]BPEL PROCESS THAT REPLIES A CAUGHT FAULT AND THEN
    # RETHROWS IT IS STUCK
    # Bug 6235180 - BPPEL XPATH FUNCTION XP20 CURRENT-DATETIME() IS RETURNING AN
    # INCORRET TIME
    # Bug 6011665 - BPEL RESTART CAUSES ORABPEL-08003 FAILED TO READ WSDL
    # Bug 6731179 - INCREASED REQUESTS CAUSE OUTOFMEMORY ERRORS IN OC4J_SOA WHICH
    # REQUIRES A RESTART
    # Bug 6745591 - SYNC PROCESS <REPLY> FOLLOWED BY <THROW> CASE CAUSING
    # OUTOFMEMORY ERRORS
    # Bug 6396308 - UNABLE TO SEARCH FOR HUMAN TASK THAT INCLUDES TASK HISTORY
    # FROM PREVIOUS TASK
    # Bug 6455812 - DIRECT INVOCATION FROM ESB ROUTING SERVICE FAILS WHEN CALLED
    # BPEL PROCESS
    # Bug 6273370 - ESBLISTENERIMPL.ONFATALERROR GENERATING NPE ON CUSTOM ADAPTER
    # Bug 6030243 - WORKFLOW NOTIFICATIONS FAILING WITHOUT BPELADMIN USER
    # Bug 6473280 - INVOKING A .NET 3.0 SOAP SERVICE EXPOSED BY A ESB ENDPOINT
    # GIVES A NPE
    # BUGS ADDED IN MLR#4, 6748706 :
    # Bug 6336442 - RESETTING ESB REPOSITORY DOES NOT CLEAR DB SLIDE REPOSITORY
    # Bug 6316613 - MIDPROCESS ACTIVATION AGENT DOES NOT ACTIVATED FOR RETIRED
    # BPEL PROCESS
    # Bug 6368420 - SYSTEM IS NOT ASSIGNING TASK FOR REAPPROVAL AFTER REQUEST
    # MORE INFO SUBMITTED
    # Bug 6133670 - JDEV: UNABLE TO CREATE AN INTEGRATION SERVER CONNETION WHEN
    # ESB IS ON HTTPS
    # Bug 6681055 - TEXT ATTACHMENT CONTENT IS CORRUPTED
    # Bug 6638648 - REQUEST HEADERS ARE NOT PASSED THROUGH TO THE OUTBOUND HEADER
    # Bug 5521385 - [HA]PATCH01:ESB WILL LOSE TRACKING DATA WHEN JMS PROVIDER IS
    # DOWN
    # Bug 6759068 - WORKLIST APPLICATION PERFORMANCE DEGRADATION W/ SSL ENABLED
    # FOR BPEL TO OVD
    # BUGS ADDED IN MLR#5, 6782254 :
    # Bug 6502310 - AUTOMATED RETRY ON FAILED INVOKE WITH CORRELATIONSET INIT
    # FAILS
    # Bug 6454795 - FAULT POLICY CHANGE NEEDS RESTART OF BPEL SERVER
    # Bug 6732064 - FAILED TO READ WSDL ERROR ON THE CALLBACK ON RESTARTING BPEL
    # OC4J CONTAINER
    # Bug 6694313 - ZERO BYTE FILE WHEN REJECTEDMESSAGEHANDLERS FAILS
    # Bug 6686528 - LINK IN APPLICATION.XML FILES CHANGED TO HARD LINKS WHEN MORE
    # THAN 1 HT PRESENT
    # Bug 6083024 - TEXT AND HTML DOC THAT RECEIVED AS ATTACHMENTS WERE EITHER
    # BLANK OR GARBLED
    # Bug 6638648 - REQUEST HEADERS ARE NOT PASSED THROUGH TO THE OUTBOUND HEADER
    # Bug 6267726 - 10.1.3.3 ORACLE APPLICATIONS ADAPTER - NOT ABLE TO CAPTURE
    # BUSINESS EVENT
    # Bug 6774981 - NON-RETRYABLE ERRORS ARE NOT POSTED ON ESB_ERROR TOPIC
    # Bug 6789177 - SFTP ADAPTER DOES NOT SUPPORT RENAMING FILES
    # Bug 6809593 - BPEL UPGRADE TO 10.1.3.3.1 WITH ESB CALLS FAILS DUE TO
    # CACHING OF PLNK - SERVICE
    # BUGS ADDED IN MLR#6, 6823628 :
    # Bug 6412909 - <BPELX:RENAME> DOES NOT ADD XMLNS DECLARATION AUTOMATICALLY
    # Bug 6753116 - OUTPUT FROM HUMAN TASK IS NOT IS NOT CONSISTENT WITH
    # SCHEMA
    # ORDERING
    # Bug 6832205 - BAD VERIFICATIONSERVICE PERFORMANCE IF LDAP SERVICE HAS HUGE
    # DATA
    # Bug 6189268 - CALLING BPEL PROCESS VIA SOAP FROM ESB FAILS WITH
    # NAMENOTFOUNDEXCEPTION
    # Bug 6834402 - JMS ADAPTER IMPROPERLY CASTS XAQUEUESESSION TO QUEUESESSION
    # Bug 6073117 - TASK SERVICE DOESN'T RENDER THE TASK ACTIONS
    # Bug 6054263 - REUSING SOAP WSDL IN RS CAUSES SOAP ACTION'S NS TO BE
    # STRIPPED
    # AWAY
    # Bug 6489703 - ESB: NUMBER OF LISTENERS > 1 GIVES JMS EXCEPTION UNDER STRESS
    # Bug 5679542 - FTP ADAPTER: COULD NOT PARSE TIME:
    # JAVA.LANG.STRINGINDEXOUTOFBOUNDSEXCEPTION
    # Bug 6770198 - AQ ACTIVATIONINSTANCES >1 DOESN'T WORK IN ESB
    # Bug 6798779 - ESB ROUTING RULES CORRUPTED ON RE-REGISTERING WITH ROUTING
    # ORDER
    # IN WSDL CHANGED
    # Bug 6617974 - BACKPORT REQUEST FOR MOVING FILES FUNCTION OF FTP ADAPTER
    # Bug 6705707 - VALIDATION ON ESB CAN'T HANDLE NESTED SCHEMAS
    # Bug 6414848 - FTP ADAPTER ARCHIVE FILENAME FOR BPEL IS BEING SCRAMBLED
    # AFTER
    # THE 10.1.3.3 UPGR
    # Bug 5990764 - INFORMATION ARE LOST WHEN BPEL PROCESS IS POLLING FOR MAILS
    # WITH
    # ATTACHEMENTS
    # Bug 6802070 - ORA-12899 SUBSCRIBER_ID/RES_SUBSCRIBER COLUMN SMALL FOR LONG
    # DOMAIN AND PROCESS
    # Bug 6753524 - WRONG SERVICE ENDPOINT OPEN WHEN TEST WEB SERVICE OF ESB
    # Bug 6086434 - PROBLEM IN BPEL FILE ADAPTER WHILE READING A FIXED LENGTH
    # FILE
    # Bug 6823374 - BPEL 10.1.3.3.1 BAM SENSOR ACTION FAILS WITH BAM 11
    # Bug 6819677 - HTTS STATUS 202 RETURNED INSTEAD OF SOAP FAULT
    # Bug 6853301 - MQ ADAPTER REJECTED MESSAGES IS NOT REMOVED FROM THE RECOVERY
    # QUEUE
    # Bug 6847200 - 10.1.3.3.1 PATCH (#6748706) HAS STOPPED FTP ADAPTER POLLING
    # IN
    # SFTP MODE
    # Bug 6895795 - AQ OUTBOUND DOESN'T WORK WITH MLR#6
    업무에 참고하시기 바랍니다.

    David,
    You are right, theer are some changes incorporated in the latest MLR # 16 on the configurations files and on the dehydration store metrics(such as performance, fields,..).
    However, I would not suggest to continue working on olite, even for Development/Test purposes as you might get stuck with strange errors...and the only solution would be to re-install SOA Suite if your olite gets corrupted. There might be ways to gets your olite back to position, but trust me..its not so simple.
    Also, when you develop and stress test all your testcase scenarios in an TEST Adv installation, its simple to mimic the same in actual production box, as you exactly know its behavior.
    So, go for a brand new SOA 10.1.3.4 MLR # 5 (or) 10.1.3.3.1 MLR # 16 SOA Suite Advanced installation with Oracle DB 10.2.0.3 as its dehydration store.
    Hope this helps!
    Cheers
    Anirudh Pucha

Maybe you are looking for