Performanc​e of Modbus using DSC Shared Variables

   I'm fairly new at using Modbus with LabVIEW.  Out of the roughly dozen tools and API's that can be used, for one project I'm working on I decided to try using Shared Variables aliased to Modbus registers in the project, which is a DSC tool.  It seemed like a clever way to go.  I've used Shared Variables in the past, though, and am aware of some of the issues surrounding them, especially when the number of them begins to increase.  I'll only have about 120 variables, so I don't think it will be too bad, but I'm beginning to be a bit concerned...
   The way I started doing this was to create a new shared variable for every data point.  What I've noticed since then is that there is a mechanism for addressing multiple registers at once using an array of values.  (Unfortunately, even if I wanted to use the array method, I probably couldn't.  The Modbus points I am interfacing to are for a custom device, and the programmer didn't bother using consecutive registers...)  But in any case, I was wondering what the performance issues might be surrounding this API.
    I'm guessing that:
1) All the caveates of shared variables apply.  These really are shared variables, it's only that DSC taught the SV Engine how to go read them.  Is that right?
   And I'm wondering:
2) Is there any performance improvement for reading an array of consecutive variables rather than reading each variable individually?
3) Are there any performance issues above what shared variables normally have, when using Modbus specifically?  (E.g. how often can you read a few hundred Modbus points from the same device?)
Thanks,
    DaveT
David Thomson Original Code Consulting
www.originalcode.com
National Instruments Alliance Program Member
Certified LabVIEW Architect
There are 10 kinds of people: those who understand binary, and those who don't.
Solved!
Go to Solution.

Anna,
    Thanks so much for the reply.  That helps a lot.
    I am still wondering about one thing, though.  According to the documentation, the "A" prefix in a Modbus DSC address means that it will return an array of data, whereas something like the F prefix is for a single precision float.  When I create a channel, I pick the F300001 option, and the address that is returned is a range:  F300001 - F365534.  The range would imply that a series of values will be returned, e.g. an array.  I always just delete the range and enter a single address.  Is that the intention?  Does it return the range just so you know the range of allowed addresses?
   OK, I'm actually wondering two things.  Is there a reason why the DSC addresses start with 1, e.g. F300001, instead of 0, like F300000?  For the old Modbus API from LV7, one of the devices we have that uses that API has a register at 0.  How would that be handled in DSC?
Thanks,
    Dave
David Thomson Original Code Consulting
www.originalcode.com
National Instruments Alliance Program Member
Certified LabVIEW Architect
There are 10 kinds of people: those who understand binary, and those who don't.

Similar Messages

  • Using Modbus TCP I/O Server with new DSC Shared Variables in LabVIEW 8.6

    Hello,
    I'm using LabVIEW 8.6 and want to communicate with a Beckhoff BK9000 Ethernet TCP/IP Bus Coupler via Modbus TCP. Instead of using the NI Modbus Library, I've tried the new LabVIEW 8.6 feature "DSC Shared Variables" as described at the bottom of this page: Latest NI LabVIEW DSC Module Features and Demos. Reading of analog input bus terminals works fine. However, I haven't figured out yet how to write on an anolog output bus terminal with these shared variables.
    It's about a 16 bit analog output and I need to write to the registers 0x1121 and 0x0801. It works with the NI Modbus Library (just using function code 6 and choosing the registers), but on the other hand I don't know which shared variables I have to choose for these registers. I've tried several data items (e.g. 400001 upwards as well as 402049 for 0x0801) but none of them worked. I would be glad for a short explanation - thanks in advance for your support!
    Regards
    utechle

    The Beckhoff documentation says, that holding registers start with 0x0800. I've checked this by using the NI Modbus Library. I used the "MB Ethernet Master Query.vi" togehter with the function code 6 for "Write Single Registers", changed the settings of the starting address to hexadecimal view and entered 801 (since it starts with a control byte in 0x0800 and the data out word follows in 0x0801). Furthermore, I had to address register 0x1121 in the same way for resetting the watchdog. As I've mentioned in my first post, this method works fine. However, I haven't found out yet which shared variables i have to use for accessing these registers.
    On the other hand, it's no problem to read data from analog input bus terminals using shared variables. They start with 0x0000 (status byte) and 0x0001 (data in word) and I can read data with the shared variable and data item 300001, respectively.
    Message Edited by utechle on 01-27-2009 11:12 PM

  • Issue with use of shared variables in Crystal Reports 2008 Offline Viewer

    Hi,
    I have a report that contains a number of sub-reports which include drill-down functionality. The report returns data relating to an individual team with the user being able to view top level summary information in each area from the parent report and then drill into the sub-reports to view see more detail. The data returned by the sub-reports is filtered, using sub-report links, based on the team code parameter value given by the user. This parameter field resides in the main report.
    One of the values returned by the main report is the team name. This is passed to each sub-report using a shared variable and each sub-report displays this team name as part of a heading.
    This all works fine in Crystal Reports 2008, but when a report, containing data, is opened using Crystal 2008 Offline Viewer there is a problem with the shared variable. The value is displayed correctly when the user initially drills into the sub-report. However, when the user begins to drill into grouped data within the sub-report the value passed to the sub-report using the shared variable disappears. 
    How can I ensure that, when a report is viewed using Crystal Offline Viewer 2008, the value within the shared variable is not lost when users drill into grouped data within sub-reports
    Thanks
    Stuart

    Please re-post if this is still an issue or purchase a case and have a dedicated support engineer work with you directly:
    http://store.businessobjects.com/store/bobjamer/DisplayProductByTypePage&parentCategoryID=&categoryID=11522300?resid=-Z5tUwoHAiwAAA8@NLgAAAAS&rests=1254701640551

  • Using network shared variables in two computers connected via a network switch

    let me start by saying im a rookie to the programming environment but i have used Labview a couple of times to understand the basics,  i have a computer and a laptop (both using vista), both of them with Labview Full development System (Student ed. with Mathscript) installed, so what im tryin to do is to use the built in microphone located in the laptop to aquire sound and then use a Shared Variable to transfere the sound signal from the laptop to the computer, the laptop and the computer are connected to a network via a network switch and ethernet cables,  so far i nothing worked, i can manage to create the shared variable in the laptop and use it there but it doesnt appear in the computer, im not sure whats the problem i have even disabled firewalls in both systems, help from anyone wil be appreciated.....

    Hi Lukie,
    This KB should be of some assistance to you.
    Trouble shooting network published shared variables
    Also the following link gives some instructions on the use of shared variables.
    http://zone.ni.com/reference/en-XX/help/371361B-01/lvhowto/bind_to_source/
    I hope this is of some assistance, let me know if you have any more problems.
    All the best,
    Message Edited by mickeyw on 08-05-2008 12:29 PM
    Mike W
    Applications Engineer
    National Instruments UK&Ireland

  • Use of Shared Variables for data transfer from a RT traget to a desktop application

    Hi,
    I want to adopt the shared variables to share data in an existing distributed application comparable with the T3 Benchmark configuration in this document:
    [1] http://zone.ni.com/devzone/conceptd.nsf/webmain/5B4C3CC1B2AD10BA862570F2007569EF
    The current implementation uses a well tuned solution with RT FIFOs and TCP/IP communication with a desktop-PC which monitors and stores the data.
    The desktop application runs with a much slower execution rate than the TCL. So the TCP/IP packets are used to buffer the data with a package size dependent on the data send rate.
    To use the shared variables instead of this RT FIFO + TCP/IP implementation I need to read the shared vairable buffer at once each time the desktop application reads the shared variable.
    But according to this quotation from [1]:
    "With buffering, you can account for temporary fluctuations between read/write rates of a variable. Readers that occasionally read a variable slower than the writer can miss some updates."
    this seems to be impossible. Am I right?
    Are there any suggestions to circumvent this problem? Or are shared variables not made to share data between unsynchronized processes without data loss?
    Regards Till

    You can use the error-cluster to detect the end of your queue. The erroroutput of the shared variable will return a -2220 Warning, if it reads a value it has read already before. I attached a modified example and saved it for 8.2 I hope you can open it.
    Attachments:
    readbuffered82.zip ‏51 KB

  • Is it possible to use a Shared Variable within a Chart?

    I have a shared variable between a container report and a subreport called {@ResponseCount}:
    whileprintingrecords;
    shared numbervar Responses:= DistinctCount ({Survey_Response.RecipID})
    I placed the variable in the report footer and the value is passing correctly.  I would like to use this shared value in a chart; however, it is not even listed in the Chart Expert as an available field.  I was placing the chart in Report Footer b.
    I have also tried moving the variable value to the Report Header and placing the chart in the Report Footer, with the same result.
    I tried changing the variable to a global variable, thinking that I was using the incorrect scope, but that passed a zero value instead.
    Any suggestions would be welcome.  Thank you.

    Thank you for the response.  Though I almost gave up on this, I did find a way to access the shared variable after all.  I created a formula that simply called the variable formula.  For this example, I was using a shared variable to pull a value from my container report into my sub report for use in a chart.
    In my container report I created the shared variable {@Get_Responses}:
    whileprintingrecords;
    shared numbervar Responses:= DistinctCount ({Survey_Response.RecipID})
    In my sub report I created the formula to call the above variable {@Fetch_Responses}
    whileprintingrecords;
    shared numbervar Responses;
    Then, again in my sub report, I created a second formula to call the above formula {@ResponsesForChart}
    {@Fetch_Responses}
    This last formula was then available for use in the chart I needed to create.

  • LV7.1 DSC tag engine VS LV8.6 DSC shared variables

    I'm currently running LV7.1 with DSC and RT. To handle communications and logging RT variables I'm using the init / read / write publish.vi's on the RT side and datasockets on the HMI side (Windows XP). This has worked out great - new tags can be programmatically created in real time with the publsih vi's and then I go to the the .scf file and use the tag configuration wizard to add them to my scf file and handle data logging. This worked very well - the wizard would organize all of the memory tags into folders by block name used by the init publish vi. I could also select entire groups of tags and add hundreds at a time to the .scf file. Hardware Tag also worked in a similar fashion, organizing tags by controller and module folders. Now - looking at LV8.6.I found I can still use the init / read / publish vi's on the RT side - great. However there is not tag configuration editor as in LV7.1 to let me add large numbers of tags through a wizard. The closest thing I've found is to create a library to represent each block name from the RT init publish.vi then use "create bound variables" option under the library to bind the new shared variables to the RT memory tags. I can browse to the tags on the controller by network items, but when I add them it doesn't bring the block name of the tag as it did in 7.1, only the item name. I use a lot of PID loops that share the same tag names (i.e.: P,I,D, mode, output), so not including the block name represents an organizational problem. The problem with this is, it's very labor intensive compared to the wizard in LV7.1 DSC, especially talking about creating systems with thousands of RT memory tags. Also, there is a similar problem with hardware channels (I'm using compact FieldPoint). To log channels via DSC do I have to create a shared variable for each channel to access the DSC logging capabilities? Again how do I add all of the hardware channels in some organized fashion? I hope I'm missing some tool that is an analog to the tag configuration wizard to bring in these channels and organize them. Any help or suggestions would be appreciated. Thanks,Brad

    Hi lb,
    We're glad to hear you're upgrading, but because there was a fundamental change in architecture since version 7.1, there will likely be some portions that require a rewrite. 
    The RTE needs to match the version of DSC your using.  Also, the tag architecture used in 7.1 is not compatible with the shared variable approach used in 2012.  Please see the KnowledgeBase article Do I Need to Upgrade My DSC Runtime Version After Upgrading the LabVIEW DSC Module?
    You will also need to convert from tags to shared variables.  The change from tags to shared variables took place in the transition to LabVIEW 8.  The KnowledgeBase Migrating from LabVIEW DSC 7.1 to 8.0 gives the process for changing from tags to shared variables. 
    Hope this gets you headed in the right direction.  Let us know if you have more questions.
    Thanks,
    Dave C.
    Applications Engineer
    National Instruments

  • Modbus Communication, Adding shared variables, Licenses

    Hello,  I am having trouble communicating with a third party DAQ.  I am receiving data from a thermocouple input module through a modbus library address but I recently purchased a digital I/O module which is giving me trouble.  As soon as I add the shared variables which correspond to the modbus addresses of the digital I/O module channels I am using I get a few different errors.  If I turn off aliasing for one of the thermocouple channels I get Error 1550 "the license for the I/O server type is invalid"....If I turn it back on I get errors for every modbus location saying "invalid value for enable aliasing option"  I am using the student edition and on the opening screen it says the data logging license is expired.  Is that the problem?  I don't think so because I am successfully communicating with the thermocouple module of the same DAQ device.  Is there a simple way to write a new VI that I can try to communicate with just a switch on the digital I/O module and see if it is reading on or off (0 or 1).  Thank you very much for your time

    Hi brade, 
    To clarify where we are at. the behavior you are seeing isn't expected. It is a minor bug that we have seen in R&D but haven't been able to reproduce and fix yet. 
    People have gotten around it by
    1) re-making their projects 
    2) Enabling descriptions, as the engineer in other post.  The problem went away for him on this post: "Aliasing is no longer an error.  (As long as NI Variables (task description) is enabled)."
    We were talking about the aliasing tab you can see on the modbus variables in hte labview project by right-clicking and going to properties; 
    I assume he checked the box on this tab: 
    Can you also post your project? 
    Jesse Dennis
    Design Engineer
    Erdos Miller

  • Dsc shared variable property are saved to library?

    Hi,
    I would like to be sure to know if the shared variable properties like "alarm level" and "description" are saved to the library directly?
    If not, where? database?
    Also can we not add table to the dsc ms sql express database? (the one for alarms and events)
    Thanks
    Patrick
    Message Edited by paubine on 09-04-2009 08:23 AM

    The properties of the shared variables like alarm and description do get saved to the library. As for your second questions about a table in ms sql, can you tell me more about this? Are you using the LabVIEW DSC VIs to do this, if so provide a screen shot or your code or a good description. Tell me exactly what is going wrong, what behavior you expect and what you are seeing.
    Thanks,
    Anna K.
    National Instruments

  • Migrating large project from DSC 7.1 to LabView 2009 Shared Variables ... What's the next step after recreating my variables?

    I am in the process of migrating a large distributed (multi-workstation) automation system from the LabVIEW 7.11 DSCEngine on Windows XP to the LabVIEW 2009 Shared Variable Engine on Windows 7.
    I have about 600 tags which represent data or IO states in a series of Opto22 instruments, accessible via their OptoOPCServer. There are another 150 memory tags which are used so the multiple workstations can trade requests and status information to coordinate motion and process sequencing.  Only one workstation may be allowed to run the Opto22 server, because otherwise the Opto22 instruments are overwhelmed by the multiple communications requests; for simplicity, I'll refer to that workstation as the Opto22 gateway.
    The LabVIEW 2009 migration tool was unable to properly migrate the Opto22 tags, but with some help from NI support (thank you, Jared!) and many days of pointing and clicking, I have successfully created a bound shared-variable library connecting to all the necessary data and IO.  I've also created shared variables corresponding to the memory tags. All the variables have been deployed.
    So far, so good. After much fighting with Windows 7 network location settings,  I can open the Distributed System Manager on a second W7/LV2009 machine (I'll refer to it as the "remote" machine henceforth) and see the processes and all those variables on the Opto22 gateway workstation. I've also created a few variables on the remote workstation and confirmed that I can see them from the gateway workstation.
    Now I need to be able to use (both read and write) the variables in VIs running on the remote workstation machine. (And by extension, on more remote workstations as I do the upgrade/migration).
    I have succeeded in reading and writing them by creating a tag reader pointed at the URL for the process on the Opto22 gateway. I can see a way I could replace the old DSC tag reads and writes in my applications using this technique, but is this the right way to do this? Is this actually using the Shared Variable Engine, or is it actually using the DataSocket? I know for a fact that attempting to manipulate ~800 items via Datasocket will bog down the systems.
    I had the impression that I should be able to create shared variables in my project on the remote workstation that link to those on the Opto22 gateway workstation. When, however, I try to browse to find the processes on that workstation, I get an error saying that isn't possible.
    Am I on the right track with the tag reader? If not, is there some basic step I'm missing in trying to access the shared variables I created on the gateway workstation?
    Any advice will be greatly appreciated.
    Kevin
    Kevin Roche
    Advisory Engineer/Scientist
    Spintronics and Magnetoelectronics group
    IBM Research Almaden

    I have found the answer to part of my question -- an relatively easy way to create a "remote" library of shared variables that connect to the master library on my gateway workstation.
    Export the variables from the master library as a csv file and copy that to the remote machine.
    Open the file on the remote machine (in excel or the spreadsheet app of your choice) and (for safety's sake) immediately save it with a name marking it as the remote version.
    Find the network path column (it was "U" in my file).
    replace the path for each variable (which will be either a long file path or a blank, depending on the kind of variable) with \\machine\'process name'\variable name
    where machine is the name or ip address of the master (gateway) workstation (I used the ip address to make sure it uses my dedicated automation ethernet network rather than our building-wide network)
    and process name is the name of the process with the deployed variables visible in the Distributed System Manager on the gateway machine.
    NOTE the single quotes around the process name; they are required.
    The variable name is in the first ("A") column, so in Excel, I could do this for line 2 with the formula =CONCATENATE("\\machine\'process name'\",A2)
    Once the formula worked on line 2, I could copy it into all the other lines.
    Save the CSV file.
    Import the CSV into the remote library to create the variables.
    Note: at this point, if you attempt to deploy the variables, it will fail. The aliases are not quite set properly yet.
    Open the properties for the first imported variable.
    There is probably an error message at the bottom saying the alias is invalid.
    In the alias section, you'll see it is set to "Project Variable" with the network path from step 4.
    Change the setting to "PSP URL" with the same path and the error message should disappear.
    Close the properties box, save the library, and then export the variables to a new CSV file.
    Open the new CSV file in Excel, and scroll sideways to the NetworkrojectBound field.
    You'll notice it is False for the first variable, and true for the rest. Set the field FALSE for all lines in the spreadsheet.
    Scroll sideways... you'll notice there are two new columns between NetworkrojectPath and Network:UseBinding
    The first one is NetworkingleWriter; it should already be FALSE for all lines.
    The second one is Network:URL. That needs to be set equal to the value for each line of NetworkrojectPath.
    You can accomplish this with a formula like in step 4. In Excel it was =U2 for line 2, and then cut and paste into all lines below it.
    There is a third new field, Path, which should already be set to the location of the variable library. You don't need to do anything with it.
    Save the edited CSV file.
    Go back to the remote library, and import variables from the just-edited remote library CSV file.
    Once you have imported them and the Multiple Variable Editor opens, click on done.
    You should now be able to deploy the remote variable library without error. (Make sure to open the Distributed System Manager and start the local variable engine. It took me a few failures before I realized I had to do that before attempting a deployment).
    Voila! You now have a "remote" library of shared variables that references all the shared variables on the master machine, and which should be deployable on other machines with very little difficulty.
    It actually took longer to write out the process here than to perform these steps once I figured it out.
    Kevin Roche
    Advisory Engineer/Scientist
    Spintronics and Magnetoelectronics group
    IBM Research Almaden

  • About the performance of using shared variables

    Hi
     My system has almost 200 I/O points,I want to the host communicates with PLC using OPC(I had create a OPC I/O Server).
    If I use shared variables bind to OPC data items, there must be almost 200 shared variables.
    And my puzzle is that what's the performance of using these shared variables,will they eat up memory and processor?
    Another question is that if an shared variable will be time-lapse(i.e.,if an OPC data item value change feedback to  program block with 0 delay or not),if so ,then how many millseconds it will delaies? 

    here is a paper about the performance of shared variables.
    Steve Bird
    Culverson Software - Elegant software that is a pleasure to use.
    Culverson.com
    Blog for (mostly LabVIEW) programmers: Tips And Tricks

  • Using shared variables in windows 7 64 bit

    Hi !
    I am trying to use network published shared variables (with Labview 8.6.1) in windows 7 64 bit. I have three PCs on the network. All PC's are visible to each other. I am able to remotely log on to other PCs.
    But when i run my program, the shared variables are not able to read the value over the network. The same program was working with windows XP.
    I am not sure whether it is windows issue or labview issue.
    Please help ASAP.
    Mandar Joshi

    I am having the same problem with Shared Variables with LV8.6.1 and Win7 64 in a program that uses a shared variables to share in seperate loops. I was able to use a local variable instead, but would love to know if it possible to use shared variables with 8.6.1 and win7.

  • Time Difference Calculation Using Shared Variables

    I have a subreport that is passing times(HH:MM:SS AM) through shared TIMEVAR variables to a main report.  I am trying to use these shared variables to calculate a time difference between the shared variable and one in the main report.  The shared variable passes without problems and I end up with a numeric value when trying to subract the two time fields.  What am I doing wrong?

    Here is an example for converting seconds to hh:mm:ss  ( Hopefully the message will not lose the (Parens))
    WhilePrintingRecords;
    StringVar Hours1;
    StringVar Minutes1;
    StringVar Seconds1;
    NumberVar MY_SECONDS_1:=0;
    MY_SECONDS_1:= ;
    If MY_SECONDS_1 < 0 Then
      "Cannot have a time less than zero"
    Else
      (Hours1:=ToText(Truncate(MY_SECONDS_1/3600),0);
      Minutes1:=ToText(Truncate(Remainder(MY_SECONDS_1,3600)/60),0);
      Seconds1:=ToText(Remainder(Remainder(MY_SECONDS_1,3600),60),0));
    Display the time formated.
      (if length(Hours1) < 2 then '0') + Hours1 + ":" +
      ["0",""][length(Minutes1)] + Minutes1 + ":" +
      ["0",""][length(Seconds1)] + Seconds1;

  • Shared variable engine OPC delay

    Hello All,
    I've got a bit of a problem with the delay time of updates between a non NI OPC server and a shared variable engine OPC client. I am using the redion OPC software OPCWorx with a database of around 120 tags to monitor and log data from a small pilot plant. The OPCWorx server has been configured with a 500ms update rate and the NI OPC client as the same. So here is my problem; logged updates occur no faster that 2.5s which is fine as we are exporting in 3 sec intervals (would still like to increase the performance of this to around 1 sec) but the main nuisance is the delay in changing control registers in the PLCs. The controls and indicators are directly bound to the shared variable items where by a change in a boolean control on the front panel to the indicated response can range from 5 to sometimes 15 seconds delay. If I bind the same control and indicator directly to the OPC item through the data socket the delay in response is almost unnoticeable at around 1 sec. I have increased the update/logging dead bands of the shared variables which seemed to help but only by a second or so.
    Im wondering what the limitations of using an OPC shared variable engine is and if this is expected or have I gone wrong somewhere. All the variables are configured as non buffered and to have single writers.
    A few changes have been suggested;
    - Upgrading the PC. The current hardware is AMD Phenom 2 3.21GHz processor, 4GB of ram running windows XP.
    - Using Modbus over ethernet instead of OPC.
    This is the first major use of the DSC module and using the shared variable engine as an OPC client so any information or insight to help with this would be much appreciated. 

    Hi Kallen,
    The Shared Variable Engine can become bogged down when there are more than 100 shared variables.  This may be what you are experiencing.  We can check buffering for the variables and disable it, and that should improve performance slightly.  As it is, using datasockets may be the best method for over 100 shared variables.  I apologize for the inconvenience.
    Here are some KnowledgeBase articles that can be of use with regards to this issue:
    How Does Buffering Work for Shared Variables?
    http://digital.ni.com/public.nsf/allkb/5A2EB0E0BC56219C8625730C00232C09?OpenDocument
    Why Is Accessing IO Variables Through The Shared Variable Interface So Slow?
    http://digital.ni.com/public.nsf/allkb/F18AEE4BE7C9496B86257614000C43DF?OpenDocument
    Matt S.
    Industrial Communications Product Support Engineer
    National Instruments

  • CFP-1808 shared variables timestamp

    Hi,
    I need to control and acquire data from a cFP Ethernet module (cFP-1808) to a PXI RT system. I have tested two ways of doing it:
    1. Bind shared variables to the Fieldpoint channels. Works great except for the fact that I have to record the timestamp of every single channel in all Fieldpoint modules. I have to avoid this. The reason I have to record all timestamps is that sometimes two consecutive reads are the same in value and in timestamp; so even if I make sure I get a value every 100ms in my real time application I cannot trust  that  the shared variable engine will give a real new value every 100ms, because sometimes one read is the same as the previous one. My
    understanding of the technology is that the cFP network interface checks for an
    updated value of the channels of each module at the Advise Rate. If there’s a
    new value the cFP transmits it to the Shared Variable Engine running in the PXI
    controller, but if the value has not changed it doesn’t transmit anything, so
    more efficiency is achieved in the network communication. This would explain the
    timestamp behavior of the shared variables bound directly to Fieldpoint
    channels; since there is no new value the shared variable is not updated so the
    timestamp of two consecutive reads is the same.
    2.  Create a Modbus server and then create shared variables bound to the Modbus server channels. With this method any time my RT application asks for a new value the shared variable engine provides a real new value with an updated timestamp, and all timestamps in the same module are equivalent (in 1usec range).  Therefore, it looks like using the Modbus solution I  only have to record one timestamp per module.
    So option 2 probably fixes my problem, but I'd like to understand why. Both methods use the shared variable engine, shouldn't they behave the same way? There's one downside in option 2, which is having to deal with Modbus addresses and not having the ease of use of option 1 that just browses to find the Fieldpoint channel.
    Any comments?
    A final note, it'd be great to be able to use the Fieldpoint VIs in LV Real-Time! Can this be achieved?
    Raimon

    Hi Raimon,
    How are you binding to your shared variables?  This KB reviews three methods:
    http://digital.ni.com/public.nsf/allkb/FA610367EC62574186257118005089F2?OpenDocument
    I don't believe using FieldPoint VIs on a PXI RT target is possible because FieldPoint is not a driver that you are able to install on the PXI RT target.  We do have the cFP-2xxx line of RT controllers for FieldPoint, which can communicate directly to the FieldPoint modules, ensuring determinism.
    Trey B
    Applications Engineering
    National Instruments