Hello,
I need to control the position of a linear actuator based on the force feedback from a load cell (rated up to 100 ft/lbs) connected to the tip of the linear actuator.  What I want to be able to do is to set a force and have the linear actuator (driven by a stepper motor) move until it is within 0.1 ft/lb of the force setpoint.  Once within 0.1 ft/lb of the setpoint, I would like to hold and control to the setpoint based on a user configured hold time.
I have the following hardware:
PXI-1033 chassis
PXI-7340 Motion controller card
UMI-7764 Terminal Block
P7000 Drive
Omega Engineering Load Cell model number LC201-100
Omega CCT-80 Load Cell Signal Conditioner
Omega FAR-1 Power Supply
I have the + output of the CCT-80 connected to the Analog Input (AIN1) and the - output connected to the Analog Input Ground (AIGND).  This output signal is -10V to +10V (verified by DMM)
I have the ADC range set to -10 to +10
I'm reading the ADC as fast as possible (get about 700 samples/second) and this just isn't fast enough to control to the precision that I need.  Also, it seems like there is a substantial amount of noise on this line.
Does anyone have any recommendations on improving the speed of the ADC read, or how to reduce the noise on the line?
If my requirement of holding to 0.1ft/lb is too strict for this hardware (7340 motion card) is there something else that I should try?
If I'm missing any other info that is needed to help me out, let me know and I'll update this post.
Thanks!

Hello AMac,
I have a setup similar to yours with a load cell attached to a linear stage. I want to use position control of the stage to apply a set load on the load cell (position-based explicit force control). Do you have a example VI I could look at if yours was successful?
Thanks,
Kyle

Similar Messages

  • Shaker control with output from load cell

    Hi
    I am using a (analog output) shaker to generate sinusoidal forces at different frequency and of different magnitude. I am also using a load cell (analog input) to sense these forces . The max force generated by shaker decreases as I increase the frequency of vibration. Whereas, the experiment requires the force to be constant when the frequency is changing. I plan to use the max force obtained from the load cell data, as the process parameter, to modify the amplitude of input wave which excites the shaker. I seek help in this regard. I am using PCI6221 and SCC68.
    Thanks in advance.
    RSD 

    Sorry, I have been extremely busy the last couple of days (months?). I still haven't had much time to ponder the problem, but one thought comes to mind, at what frequencies are you running this and what is the load cell, and its supporting electronics, frequency response. You mention that the amplitude decreases as the frequency increases, but that you increase the gain of the driver amplifier. It (the system) is most likely non-linear in its response, so how much you increase the gain will vary. The nonlinearity of the response is one of the reasons there is so much published about control systems, PID controllers, etc.
    Putnam
    Certified LabVIEW Developer
    Senior Test Engineer
    Currently using LV 6.1-LabVIEW 2012, RT8.5
    LabVIEW Champion

  • Dynamic force control using linear servo actuator + load cell

    Hello,
    I am designing a test fixture which will allow us to test the performance of actuators we install in our products. I need to apply a constant load to the actuator while it is extending/retracting. I would like to be able to use a linear servo actuator and a load cell on the same axis as the UUT to provide and monitor the load. The actuator under test does not travel at high speeds, its max speed is approximately 1in./sec.
    I need to be able to maintain a constant load while the actuator is moving. Therefore  I'll need some kind of closed loop system to maintain a velocity such that the load being reported from the load cell is equal to the expected load as the actuator is moving.
    I am trying to figure out how to best implement this in a cost effective and time-saving way. I have not purchased any hardware at the moment so am open to suggestions. We do have LabView 2009 with all the toolkits. Would it be best to implement this using a motion controller card or would I be able to get good results using a standard DAQ?
    Message Edited by fnaeem on 02-05-2010 05:58 PM

    As you have stated correctly, you will need a deterministic closed loop system to accomplish this task. The most cost efficient while reliable solution for this purpose is a motion control board like the PCI-7352. This board provides quadrature encoder inputs for positioning tasks and analog inputs for any other type of control. Torque/force control is a very typical task for this board and it provides a simple API and useful configuration tools.
    If cost savings are a primary goal, you could also use a PCI-7342, but for your application I would recommend the PCI-7352, as the PCI-7342 provides only 12-bit ADCs, while the PCI-7352 provides 16-bit ADCs, resulting in a much better resolution of your force feedback signal.
    I hope that helps,
    Jochen Klier
    National Instruments

  • How to finetune the force control of an AC Motor Linear Actuator?

    Hello,
    I
    am hoping to find some help here with the following problem, which I am trying
    to solve for several days now....
    I
    am using the UMI-7774 and an AC servo-motor-driven linear actuator to do
    force control. Basically, I need the actuator to apply a constant force and
    react quickly to force changes. My system setup is as follows: I am using
    a PCI-7344 Motion Control Card to provide the analogue command signal
    (0-10V). This signal is supplied to the actuator controller (through a
    UMI-7774), which transforms the command signal to an amperage command signal
    (0-2.17Arms). This is the signal controlling the actuator’s torque. The actuator controller is working in torque mode. I use
    a Kistler PZT force sensor (ring type) and a Kistler amplifier as my feedback
    source. The signal from the sensor amplifier is directly connected to the ADC of the
    UMI. I am using MAX to tune my system and define a PID controller that gives
    me a good step response.
    (1)
    The results so far show that it works in principle, but I believe my system is
    not yet tuned optimally. However, the best step response results I have
    obtained and the PID parameters I used are shown in the attached files. As I am
    relatively new to this area, could you please advise me on how I could further
    improve the step response of the system? The current rise time and
    overshoot values are very good (a 3% overshoot would also be acceptable),
    but the observed undershoot is causing delayed settling. Also, the oscillation
    observed during undershoot is something I would like to remove.
    (2)
    I have tried increasing Kp and Kd values. Increased Kd does not seem to correct
    the oscillation problem. On the contrary, it destabilises the system. Increasing
    Kp causes an unwanted overshoot.  I have also tried to reduce the
    Derivative Sampling Period but that gave even worse results (System Inertia: J
    = 1.8629*10^-5 Kgm^2).
    At
    Td=2 the actuator was retracting on its own to its home position when I set Ki>=8.
    I got the most stable behaviour using Td=4. Is there any other way I could
    improve the actuator’s response?
    (3)
    I have seen that in some cases people have used a “double PID loop” one
    for the encoder feedback and one for the force feedback. Do you believe that
    this would improve system behaviour? If so, how could
    I implement two PID loops? I mean, MAX only allows me to enter
    one set of PIDs....or is there a possibility to set up a second PID-loop
    somewhere?....I have seen that the "Force Control Using Monitoring
    Force" example essentially works with two Closed-loops, but one of them is
    implemented in the application software and this would result in a
    non-deterministic and comparatively slow response of the system, right??
    Sorry for the long post and thanks
    a lot in advance for help and advice.
    Attachments:
    Force Conrtol Loop Settings Actuator-BEST.JPG ‏41 KB
    Step Responce Actuator-Force Feedback-BEST.JPG ‏58 KB

    Hello Jochen and thank you for your very nice reply.
    The past few days I have been trying to implement your advice, but unfortunately I did not have much success. Let me start by saying that explanations to my problem, the 2nd one looked more probable, as I always make sure that there is contact between my actuator and the workpiece I am pushing against. So, I unmapped my DAC by setting up the axis as a stepper axis with no feedback and I used the Load DAC to apply voltage and see when my actuator starts moving. That gave me the upper and lower limits for the Static Friction Compensation filter (please refer to attached image). I then implemented this filter and tried to retune the PID parameters, but the results I got were poor.
    I can now adjust the parameters so that there is no initial spike and undershoot, but now the force ramps up fast to a specific value and then keeps rising slowly. Vibration is observed at the point of transition from fast to slow ramp-up (ref. Step Responce Actuator-Force Feedback-WITH FILTER_v2).
    I could not eliminate the steady state error. When I tried to eliminate the steady state error by increasing Ki, or tried to create an initial overshoot by increasing Kp, I always ended up with an unstable system or a system with a response similar to the one shown in attached figure “Step Responce Actuator-Force Feedback-WITH FILTER_v1”.
      Do you perhaps have an explanation or comments for this behaviour? As for your other questions:
    Sensor Bandwidth: N/A, Charge Amplifier Bandwidth: 200 kHz, Low pass filter: No (Amplifier has the capability though)
    PID Update Period: 250 microseconds (fastest available)
    NI Motion Version 2.3
    Labview Version 8.5.1
      Thank you,
    Thomas
    Attachments:
    Step Responce Actuator-Force Feedback-Filter Settings.JPG ‏28 KB
    Step Responce Actuator-Force Feedback-WITH FILTER_v2.JPG ‏69 KB
    Step Responce Actuator-Force Feedback-Filter Settings.JPG ‏28 KB

  • Is it possible to condition a load cell signal with a 1520 SCXI and then use it as the primary analog feedback for a 735X motion control board?

    My system
    PXI 1052 chassis
    PXI 8196 RT controller
    Flexmotion 7356 motion controller
    Flexmotion 7354 motion controller
    6259 M series DAQ
    1520 SCXI
    1520 SCXI
    1314 SCXI frount mounting terminal block
    DSM strain gage load cells
    Exlar SR Brushless PM motors
    Kollmorgen servo star CD series 5 drives
    My objective:
    I want to measure the force on the load cells with the 1520 SCXI (i.e. excite the load cell then amplify and condition its output) then I want to use this analog (force) signal as the primary feedback for my motion control system (7356 and 7354 motion controller connected to my drives and motors).
    The problem:
    The motion controller boards (7356 and 7354) can be configured for force feedback control via analog feedback from a load cell.  However the boards implicitly expect the load cell signal to be amplified and conditioned with and external signal conditioner rather then using an NI SCXI module.  Currently I’m am reading the SCXI signals via the 6259 M seriers DAQ and consequentially have no way to route the signal into the 735X boards for force feedback control.  I can use softmotion to control the motors but then I loose the fast PID update rates possible with the 735X boards.
    The question:
    Is it possible to condition a load cell signal with a 1520 SCXI and then use it as the primary analog feedback for a 735X motion control board? 
    Thanks
    Patrick Aubin
    Ph.D Candidate
    University of Washington &
    VA MedicalCenter of Excellence for
    Limb Loss Prevention and Prosthetic Engineering  

    Hi GG,
    Thank you for your feedback.
    >create your own external circuitry to amplify the signal.>
    True a few op-amps could amplify and filter the signal externally but the performance of such an amateur built system will never match the accuracy and functionality of the 1520 SCXI.  That’s why we spent the $2500 for the professional version.
    >One thing that you could do is to use a UMI with your motion controller and then wire your signal from your SCXI to the UMI.>
    As I understand it the UMI is basically a break out connectivity interface for third party drives.  After conditioning and amplifying the analog force signal with the SCXI module the analog signal isn’t available to wire into a UMI.  To my knowledge the conditioned signal of the SCXI resides only in the PXI backplane (i.e. there is no physical access to the conditioned analog signal).  Can you explain how the UMI could be help here.
    Again thanks for your input GG.
    Patrick

  • Servohydra​ulic control with load cell feedback

    Hello,
    We are planning to build a tie rod fatigue test system with Labview and NI PCI-7344 4-Axis Motion Control Board. We have two linear servohydraulic actuators for applying linear force to tie rod and a servo motor for steering wheel movement. Tie rod must be vibrated by linear servo hydraulic actuators with constant force (+/- 50N , compression and tension direction) as 20 Hz while the steering turns (this is for road simulation) .
    I think we can generate the 20 hz triangle waveform with 7344 motion control board for controlling servo hydraulic. But the main problem is to apply stable force with servo hydraulic actuators while steering wheel is turned by servo motor with constant frequency. There are two load cell as load link in the system so can we solve this problem with connect load cell to 7344 as feedback ?
    Could you please share your opinions about hardware and software selection and application? What do you think about onboarb programming for this system?
    I have attached two images regarding this systems which was build by some companies.
    Best Regards
    Steward

    Steward,
    I think you should be able to use the analog feedback feature of the 7344 to accomplish your task. Please refer to this link where you can find an attachment that explains the details of using analog feedback.
    I don't think that you will need any onboard programming for the control task but depending on your security needs you might want to use it for emergency stop actions (e. g. when something goes wrong and the speed or the force become too high).
    Please note that the 7344 does provide 12 bit ADCs for analog feedback. If the accurracy of these ADCs is not enough for you you should consider to use a 7356 instead which provides 16 bit ADCs.
    Please read the document linked above. If you find that for some reason analog feedback is not the solution for your task we can talk about other options.
    Best regards,
    Jochen Klier
    National Instruments Germany

  • Pulsatile Linear Actuator Control - Help Needed

    Hi,
    I have a VI that controls the speed of a linear actuator, which is placed within a case structure. A limit switch input switches
    the case structure between forward and reverse. This allows the actuator to move in a continuous motion either forward and
    reverse. What I would like to achieve is a pulsatile movement. The linear actuator operates for a set time and completely off
    for a set time.
    I have tried various approaches with the elapsed time function, alternating wait times but just can't seem to get this, any help
    would be greatly appreciated, I have attached the VI.
    Thanks
    Ger
    Solved!
    Go to Solution.
    Attachments:
    Pulsatile Linear Actuator.vi ‏95 KB

    A few things:
    Are you using the Run Continuously button?
    If so, stop and put this into a proper loop or state machine.
    I don't think the Elapsed Time function is what you're looking for.
    I think you want to use Time Delays between changing the output on your digitals.
    Take some time with the LabVIEW tutorials. They'll help you a bunch here.

  • Linear actuator controlled with external encoder and smart motor - randomly stops

    Hi,
    This is my first experience with Labview or any sort of programming for that matter.  I am using an Animatic Smart Motor Model: SM1720M version 4.15b with an Ultra Motion Bug linear actuator: 4-2B.125-SM17-3.2-1NO-B/EC4 and a 600 series optical encoder.  I am trying to write a VI that allows me to manually control the linear actuator using the encoder.  I attached the one I have been using, but for some reason it randomly stops working, generally  when the actuator is extended about an inch and 2 1/2 inches.  It stops in the same general area, but not the exact same spot.  Any ideas?  Any help would be much appreciated!
    Attachments:
    Manual Command.vi ‏29 KB

    1. The VISA Clear and VISA Close should be outside the loop. You do not want to be re-initializing the VISA session each time through the loop.
    2. You have the port initialized to use line feed as a termination character. When using termination character, you should not use Bytes at Port. Just set the byte count input of VISA Read to a constant larger than the longest message you expect to receive.
    3. With the termination character you do not need the waits between or before the reads.
    4. The 10 ms Wait in the outer loop is rather meaningless when the start button is True. The VISA Write takes much longer than 10 ms for the string you are writing. It does make sense to have a Wait in the False case.
    5. The start button is set to Latch When Released mechanical action. With that setting it retuns to False every time it is read. The result is that the code in the True case only executes one time for each press of the button. Is that what you want?
    A state machine architecture is more flexible and more robust.
    As to why it stops in a particular place, you have not given us nearly enough information to even guess. What is the relationship between motor speed and displacement? Where do you do anything with the encoder? What is the format of the encoder output? How far does the motor move at various speed settings during one iteration of the outer loop? Where is the command to stop the motor when it gets to where you want it? 
    What error messages, if any, do you get when it stops?
    Lynn

  • Closed loop velocity control based on load cell force

    Hello,
    My application is for a drill, that drills into rocks of various densities for the purpose of collecting rock core samples.
    My setup has 2 motors which get controlled, one spins the drill bit at a constant velocity, the other moves the drill mechanism along a Z axis.
    For efficient cutting, it is desired to apply a constant force between the drill bit and the rock.  I have a load cell which measures the force being exerted by the drill bit on the rock surface, and this force can be adjusted by changing the velocity of the Z axis.  So I would like to employ closed loop control to adjust the Z axis velocity to maintain a constant force on the rock.
    Platform: cRIO 9073, with NI 9505 & 9215 Modules, Labview 2010 Full with RT and FPGA modules.
    The load cell is by Transducer Techniques, and I use their TMO-1 module to condition the signal, the output of which is attached to an input of the 9215 module, where 0-100 lbs equates to 0-8VDC.
    The motors and encoders for the Drill and Z axis are connected directly to the 9505 modules.
    Right now I am using a modified version the example found in ...\examples\CompactRIO\Module Specific\NI 9505\Velocity Control (closed loop)\Velocity Control (closed loop) - NI 9505.lvproj to accomplish velocity control of the motors.
    My questions are:
    1) Do I have the appropriate NI hardware/software for this task?
    2) With my current hardware setup, what would be an appropriate way to control my Z axis velocity rate based on Analog feedback from the load cell?
    3) Development time is a critical factor, so are there any toolkits etc that are easy to get started with that would drastically decrease my development time, or do I already have everything I need?
    Thank you for your time
    -MK Hokie

    1. Your hardware and software look appropriate assuming the motors are compatible with the 9505s.  You didn't mention the NI SoftMotion module in your software list which is something you will need.
    2.  There are a few ways of doing this.  One method would be to have a force PID loop that would attempt to maintain a force setpoint by directly outputting values to your torque loop.  In this case, the drill would essentially move as fast as it could while maintaining the force setpoint.  Another option is to have the force loop output a velocity setpoint.  You would then have a velocity PID loop that outputs torque values to the torque loop.  By adding this additional velocity loop you could have control over your maximum and minimum velocities.  There are likely other alternatives as well, but these are the first two that come to mind.
    3.  Unfortunately there are no shipping examples that close the loop on force feedback.  My advice would be to start with the NI 9505 shipping example and adapt it to your needs.  There are quite a few things you will want to change though.  Do you know if you will need to use the trajectory generator to move the drill into position before starting the force control?
    Assuming you don't need any trajectory generation, you can scrap the entire RT portion of the NI 9505 example and just create the necessary FPGA code.  On the FPGA, you won't need the Spline or Synchronization code either because this information would no longer be coming from RT.   You could take these out and replace the position loop with a force loop and possibly a velocity loop and your FPGA program would basically be finished.  In fact the only real motion IP that you will need is for the encoders (assuming you want velocity control) and PID.  Then you would need to create an RT VI that allows you to send down enable, disable, PID gains, and setpoints. 
    If you do need trajectory generation, you would want to keep most of the example code the way that it is, but then program in a 'Force Mode' that utilizes the force and velocity controly as described above.  You could think of it as having two different routines programmed side by side. 
    Regards,
    Burt S

  • Control a linear actuator

    I need to be able to control a linear actuator from labview.  Can someone show me an example of how I might do this?  Also, I have no idea how I should wire the actuall motor up so that it can go forwards and reverse.
    thanks

    Hi Eileen,
    I'm not sure how exactly the Firgelli actuator would be wired, but according to their datasheet it can be controlled by "simply applying a DC voltage to extend the actuator, and reversing the polarity to retract it."
    I would recommend starting with using the DAQ Assistant Express VI to output a DC voltage from the PCI-6024E. There is a tutorial on Getting Started with the DAQ Assistant that should be very helpful. You will want to check out the "Configuring DAQmx Express VI using the DAQ Assistant (Analog Output)" section to set up a DC voltage output. Then whatever Analog Output channel you have configured your DAQ task for can be wired to the voltage input of the actuator.
    I hope that information is helpful!
    Matt
    Product Owner - NI Community
    National Instruments

  • Simple control of a linear actuator through LabVIEW advice

    Hello all,
    Was in need of some quick guidance. I purchased a Firgelli PQ12 linear actuator along with their LAC control board. They provide a sample LabVIEW program which I was able to run properly. What I would like to do is create my own LavVIEW program for the motor, basically with two inputs; stroke length, time. I would like for the actuator's stroke to simply extend and retract for a desired time period. What is the best way to go about creating a LabVIEW program for a DC motor? Any tutorials available for this application? Advice? Any help is appreciated. 
    Thank you!
    Edit - Details on what is being used
    http://www.firgelli.com/Uploads/PQ12_datasheet.pdf
    http://www.firgelli.com/Uploads/LAC_Datasheet.pdf

    Are you looking to use just basic LabVIEW? Or do you have any toolkits or modules? Here are a few links to an example and tutorial regarding DC motor control in LabVIEW:
    -Open and Closed Loop DC Motor Control VI
    http://zone.ni.com/devzone/cda/epd/p/id/4953
    -Using the LabVIEW PID Control Toolkit with the LabVIEW Control Desgin and Simulation Module
    http://www.ni.com/white-paper/6931/en#toc1
    Daniel K | NI Applications Engineer | Certified LabVIEW Developer

  • A/C three Phase motor control using 1/4 bridge Load Cell output and a USB 9172 Daq

    NI Assistant,
    I am tasked with setting up a Motion Control using two each OMEGA LC712-100K, -50K and -10K load cells to monitor the cable tension on six A/C motor driven winches. I also need to Monitor and calculate a Moment as well as the load slope for Load verses Time.
    I have zero time to develop and I have searched your databases for existing Motor Controls to modify.
    Should I use Case Structures and then place them in a while loop?
    I setup a drawing in Word to visually define the task.
    Signed,
    Patrick Murphy
    Attachments:
    Layout for Testing Spars.docx ‏15 KB

    Hi Patrick,
    The reason why the Motion Control examples will not work for you is beacuse they are meant to be used with the NI Motion boards. Since you are using DAQ boards, the examples are probably not going to be able to help you too much. However, there is one example on the community that might be a place for you to start. 
    pmurphy wrote:  Should I use Case Structures and then place them in a while loop? 
    What exactly do you mean by this? What do you want in the case structure or while loop?

  • Linear Actuator Force Control

    How do I control the force and rate of travel of a linear actuator using Labview?

    You need to separate this into two different parts: hardware and software. You first need to determine what kind of hardware you need. You said you "believe that this can be controlled by the voltage". Are you sure? What does the documentation say? If it's controlled by a voltage level, what are the specs? This will help to determine what kind of hardware you need to buy and/or make. 
    The software part is the other half. This really isn't all that difficult, but the exact implementation depends on a lot of factors. One of these is whether you get a DAQ device from NI, or you get one from another vendor, or you build your own. I think you should spec out your hardware first. If you need help with this part of it you can provide more information and we can suggest a couple of items, or you can look over the products that NI sells, or you can call your local NI sales rep.

  • Boot Camp control panel does not load: Windows XP via VMWare Fusion

    whenever i try to access the boot camp control panel--either via the diamond-shaped boot camp icon running in the task bar, or through the windows control panel itself--i get the following error message related to administrative privileges:
    "An error occurred while trying to access the startup disk settings. You may not have privileges to change the startup disk. Make sure you have administrator privileges and try again."
    is this because i am running windows as a virtual machine within fusion? obviously i'm not interested in the control panel for its startup options, but rather for its other adjustments such as brightness, trackpad, etc.
    i am logged in as administrator--that is the only account i have--and i am running boot camp 2.1 on windows xp sp3.
    boring possibly-related background info:
    - i installed sp3 before ever putting boot camp on my windows virtual machine. i started, of course, with boot camp 2.0 via the OEM leopard install disk, but even after that installed successfully, i could not access the boot camp control panel. so i plowed forward and installed the 2.1 update, but to no avail.
    - i even un-installed sp3 and rolled back to sp2, then removed all traces of boot camp, then re-installed starting from 2.0, but to no avail.
    google reveals that a few others have gotten this error message, but i've seen no definitive answer for any of them.

    Check your XP Task Manager to see if the processes are running or not. I found that I had issues with my Boot Camp Control Panel if I let it auto-launch. It would hang and not start properly most of the time (but it would sometimes). I removed the process from the auto-start list and put an icon on my desktop to manually start it, and it works right every time now. As for the special keys, etc many of those only work right once the control panel app running.

  • Controlling the displacement of 2 linear actuator

    im using arduino to work the linear actuator 
    1) im not able to sync the 2 linear actuators togethers 
    2) stop at same distance with each other
    3) im using dual channel 10A driver for DC motor board 
    4) using labview to simulate this movment 
    pls check the file below and offer any suggestion in doing so.
    Attachments:
    woirking linear actuator.vi ‏26 KB

    Equal Height CSS Columns ~
    http://alt-web.com/Articles/Equal-Height-CSS-Columns.shtml
    Nancy O.
    Alt-Web Design & Publishing
    Web | Graphics | Print | Media  Specialists 
    http://alt-web.com/
    http://twitter.com/altweb

Maybe you are looking for

  • Multiple iTunes open in multiple 'user accounts'- at the same time

    We have three people in our family, each with their own iPod/iphone, we sync our iPod/iphone on the same computer but in different 'user accounts' in xp. Now the problem is ; only one iTunes program can run at a time, so if one person is downloading

  • ICal more than a day event

    Due to my work I have events that start in the evening and finish next day. When I saw them in iCal (month view) they show as finishing the first (starting) day. How can I see next day as busy too?

  • Payment Terms, Invoice Due Date

    Hi, I've got to set up a new payment term in our system. The requirement for this payment term is: A)     The invoice due date is either, whichever is the later of: i)     The 12th day after the day on which the invoice document was deemed to be rece

  • Should I use EJB?

    Hi- I was wondering if anyone could offer some architectural advice. I need to create a service that does the following: 1.take a plain text file provided by a client 2.run some non-java executables on that file 3.return the binary output file to the

  • Message: This application does not support this browser

    After pressing 'New Analysis' in the Web Analyzer I am getting the message: This application does not support this browser: Microsoft Internet Explorer 4.0 (compatible; MSIE 7.0; Windows NT 5.1; .NET CLR 1.1.4322; .NET CLR 2.0.50727) This is for a ne