Disparity in process range and control system range

I am in the process of ordering a hydrostatic level measurement sensor. This sensor is to be used to measure water level in a sump 4m high. The sensor however can only measure from 10cm from the bottom of the sump because it cannot get right to the bottom. This means an offset of 10cm. The technology is 4-20mA and the system specification allows an uncertainty of 1% in measurement.
The I&C system was programmed with a range of 0.1 -4m (0.1 to take care of the offset mentioned earlier) but then the upper limit should have been 4.1 to cater for a sensor with a range of 4m. Because we do not want to incure additional costs in having to update the I&C system (from 4 to 4.1m) we are planning on living with this disparity.
My question is how do I account for the disparity, knowing that the sensor has a range of 0-4m,  but the I&C system is 0.1 - 4m?
In terms of thresholds, the max water level that triggers the sump pumps is 3.5m. Am I correct in saying that with the I&C, we are okay up till 3.9m (ie 0.1 - 4m)? Or is there some calculation I have to take into account '4-20mA' wise?
Thanks a lot.

How about some basic math?
You sensor will give you out the value it sense, that could or couldn't be the value of interest
What you wanted:
 Actual_water_level_in_meter = 4m/16mA*($measured_current-4mA) +0.1m
What you get:
System_output_waterlevel= 3.9m/16mA*($measured_current-4mA)+0.1m
So all you need is a correction factor of 4/3.9 to get the actual level or the factor 3.9/4 for new limits ...
At least: Do a field calibration: all you need is a 4m tube surrounding the sensor ....
Greetings from Germany
Henrik
LV since v3.1
“ground” is a convenient fantasy
'˙˙˙˙uıɐƃɐ lɐıp puɐ °06 ǝuoɥd ɹnoʎ uɹnʇ ǝsɐǝld 'ʎɹɐuıƃɐɯı sı pǝlɐıp ǝʌɐɥ noʎ ɹǝqɯnu ǝɥʇ'

Similar Messages

  • Budgeting and control system

    friends,
    we implemented fi, co, mm, sd, pp and project systems. we want to implement budgeting and control system. what is the exact flow of BCS in between these modules,
    regards,

    Hi,
    Prepare Funds Management Installation
    When implementing the Funds Management Government component, you should take care to carry out the individual steps in a particular order. You enter the required preconfigurations and functions at different points in the SAP System.
    So when implementing Funds Management, you should observe the following sequence:
    1. You use the "Enterprise Structure" to create company codes, FM areas, and controlling areas. For more information, see the Enterprise structure IMG in sections:
    a) "Define, Copy, Delete, Check Company Code"
    b) "Maintain FM Area"
    c) "Define, Copy, Delete, Check Controlling Area"
    2. You then assign an FM area to each company code and controlling area relevant to Funds Management.
    For more information, see sections:
    a) Assign company code to FM area
    b) Assign controlling area to FM area
    3. You create your G/L accounts in the General Ledger Accounting menu. For more information, read the chapter: Create G/L accounts in the G/L accounting IMG (FI-GL) under G/L account master records.
    4. Use Financial Accounting customizing to maintain the field status definition groups. These determine which fields in the account can accept input, must be maintained, or are hidden, when you are entering business transactions. For more information, read: "Maintain field status variants" in the Financial Accounting Basic Settings.
    Note that the additional account assignments "Commitment item", "Funds center" and "Fund" will only accept input if you mark the relevant fields as required or optional entries. This applies, however, only to G/L accounts whose commitment items are assigned with the 30 such as a revenue account. G/L accounts whose commitment items are assigned with a transaction other than 30 should have the error hidden.
    If you want to reference earmarked funds when posting a payment, you must define the additional account assignment "Earmarked funds" as a required or optional entry.
    5. Likewise, for Materials Management purchase requisition and purchase order postings which do not go into stock, you must flag the "Commitment item", "Funds center" and "Fund" fields as required or optional entries in order to be able to make entries in them. You can find more information in the Purchasing IMG in section "Maintain account assignment types" .
    6. If you want to integrate inventory management with Funds Management, there are different ways of controlling this, depending on the warehouse concept you chose. For more information, go to the Funds Management IMG and read sections Make Other Settings and Integration with Inventory Management.
    7. If you want to integrate Assets Accounting, you must go to the Funds Management implementation guide and flag as budget relevant the transaction types for the individual transactions (acquisitions and retirements). You can find more information in the IMG Funds Management Government in the section Flag Transaction Types as Budget Relevant.
    8. If you want to integrate Payroll Accounting with Funds Management, you must define funds centers and funds for the individual Infotypes. For more information, see the Funds Management IMG Funds Management Government in the section "Define Start Date for HR Integration (Without HR Commitments Scenario 2)".
    9. If you want to integrate Travel Management with Funds Management, the "funds center", "commitment item" and "fund" fields must be ready to accept input when you post in Travel Expense Accounting. You enter these settings in the Travel Management IMG Dialogue and settlement control -> Screen layout for trip data input -> Set up variable construction for account assignment objects.
    10. You switch to the Funds Management application menu, create your master data (commitment items, funds centers and funds) and then define your account assignment derivation.
    For more information on account assignment derivation in Funds Management, see component Funds Management (PSM-FM) under Account Assignment Derivation as well as section Define Account Assignment Derivation.
    For more information on creating master data, see the component Master data in the componentFunds Management (PSM-FM).
    11. You can then subsequently make the remaining settings via the Funds Management implementation guide. For more information, read the following chapters.
    Further notes
    The Funds Management application component can not be used simultaneously with the components Cash Budget Management and/or Project Cash Management if you use year-dependent master data in Funds Management.
    If you want to use Funds Management with Cash Budget Management and/or Project Cash Management you must note that Cash Budget Management and Project Cash Management only process 10 character commitment items.
    Regards,
    Eli

  • In TDMS, can central system and control system on different clients?

    I think they should be on the same client. Is that mandatory?
    Thanks!

    When you generate a RFC connection in TDMS there are four system entry, and you have to enter the client noumber also so i think you can keep differenct client for Central and Control System.
    Regards,
    Subhash

  • Process chain and Control M

    Hi Gurus
    We are designing process chain for our BW solution.
    We have identified the dependancies of various loads which includes flat file loads and loads from R/3.
    Now we would like to control ERP and BW jobs by Control M .
    I have the following questions:
    1. Which portion of BW process chain do we need to plug in to Control M. ? Do we need to connect the Meta chain to control M or different process chains to Control M?
    2.When we create Process chain for BW, what is the best practice? Is it good to create small chains and connect them via Meta chain? or we have to create small chains only?
    3. Can we include R/3 extraction Jobs and V3 Jobs in our BW process chain? so that they will trigger when we run the process chain?
    4. If we decide to run V 3 jobs after every half an hour on R3 side then how often we have to extract data to BW? and how to catch correct delta without missing single record?
    I would appreciate if you can help me with your knowledge.
    Thanks
    Kris

    Hi Kris,
    Control M is a third party scheduling tool provided by BMC software.
    1) You have option to either include a meta chain or individual chains in Control  M .
    2) It depends on how your data is extracted. If you have any dependecy jobs on sourcre system, then it is better to create small process chians and include them along with your dependecy jobs in Control M
    3)you can include R/3 dependency jobs and V3 jobs in Control M. Once those jobs are finished you can run BW process chains via Control M.
    4)You have several scheduling options availalbe in control M to take care of your BW and R/3 jobs.
    V3 jobs collect data from R/3 application tables and fill R/3 delta queue(RSA7). when you run BW process chain it will collect all the data available from R/3 delta queue.
    If both jobs are running at same time, then it is better to apply some wait time on BW jobs(in process chians).
    hope this helps

  • XI Sender file adapter - How to process data and control files.

    Hello all,
       I have the following requirement to fulfill: I am using an FTP client (XI Sender file adapter) to retrieve data from an FTP site. To make sure I am not picking up a data file that is currently being written to, 2 files are actually present on the FTP site (for each data file):
    1. abc.ctrl (control file with no data in it. Indicates that the data file has been completely written).
    2. abc.dat (actual data file).
      I want the file/ftp connector in XI to retrieve the data file (abc.dat) only if the control file (abc.ctrl) is present. After the processing of the data file is finished, both files (.dat and .ctrl) should be deleted.
      Is there an elegant and robust way to accomplish this?
    Thanks for your help.

    Hi Yves,
    in my opinion there's no problem with files currently being written in combination with a polling file adapter because the final file name should be available only when the file is transferred completely. I'm using different file sender adapters very often and never had any problems. After picking up the files I move them to the corresponding archive folders mentioned in the adapters so that a second processing cannot occur.
    Regards
    Ralph

  • Control Systems Engineer

    Control Systems Engineer
    Seattle Safety – Kent, WA 98032
    Seattle Safety is looking for a qualified individual to fill an opening for Control Systems Engineer. Seattle Safety designs, manufactures, and installs advanced crash test sled systems that are used in automotive and aeronautical industries. The duties of the Control Systems Engineer include:
    • Experience designing, testing, and optimizing industrial automation and control systems utilizing modern and classic control methodologies such as PID. Experience with neural networks.
    • Strong background in mathematics, physics, and signal analysis.
    • Electrical / Electronic design experience including automation.
    • Design, troubleshoot, and test software written in LabVIEW 8.6 & 2012 and C.
    • Help customers diagnosing electrical, software, and mechanical problems with their systems. This will sometimes involve working odd hours for customers on the other side of the planet.
    • Support installations of crash test equipment at on-site locations worldwide.
    • Provide round the clock technical support for team members locally and abroad in subject matters concerning performance, installation, and maintenance of software and data acquisition hardware.
    • Prepare and maintain software flowcharts, layouts, and diagrams as needed to demonstrate solutions to outside staff.
    • Work with current team members to restructure existing crash test software.
    • Supports all aspects of software application design, development, testing, deployment, and support.
    • Perform software testing at a unit and integration level to ensure expected behavior.
    • Comment code clearly and consistently throughout the development process.
    • Maintain professional relationships with suppliers and vendors in order to keep up with industry developments.
    • Candidates must be located in the US, the northwest would be ideal.
    Furthermore, the ideal candidate would possess the following skills:
    • Advanced or expert knowledge of LabVIEW.
    • Advanced or expert knowledge of C.
    • Expert knowledge of industrial controls.
    • Familiarity with a minimum one low-level programming language (C#, VB, Ladder, etc)
    • Familiarity with data acquisition concepts and hardware.
    • Discipline and organization with respect to software maintenance and version management. Experience with source configuration management tools a plus (CVS, ClearCase, Perforce, etc.)
    • Experience with sophisticated feedback control systems.
    • BSEE, BS Physics, and BSME are preferred but not required depending on experience.
    • Ability to work both alone and with colleagues to solve problems and to weigh the merits of differing approaches.
    Pay is commensurate with skills and qualifications of the applicant.

    Dear Sir/Mam,
    I’m particularly interested in the position of Control System Engineer, which relates strongly to my more than six years of experience in designing various applications for testing and automation. I am Certified LabVIEW Associate Developer & prepared for CLD also. Currently I am leading a team for the project for Machine Automation and remote diagnostics, and I believe I meet all the essential criteria of the position. My work at my current organization has been rewarding and productive. However, I wish to expand my career further, into the application designing and development role. The position also has a definite correlation with my practical knowledge and experience. You’ll see from my CV that I have been deeply involved in designing and development of various applications based on Programming techniques, hardware and network designing. I feel that I am well qualified to make an effective and useful contribution to design good application which will be market acceptable.
    I’m enthusiastic about the chance to participate in a meaningful role with an industry leader in the field.
    Thank you for your consideration of my application. Please contact me should you require any further information,
    Yours sincerely,
    Mohit Monga
    Mohit Monga
    Attachments:
    Mohit Monga_CV.doc ‏159 KB

  • Recent graduated Control-Systems (embedded) enginneer, with experience in France/lebanon/Switzerland Looking for a Job With Labview

    I am currently recently graduated from the University of Technology in Belfort-Montbeliard (France).
     Master’s grade of “Electrical and control systems engineering”.
    I am currently looking for a job in automation, control systems and electronic domain (I prefere LabView Developpement)
    Salim DARWICHE
    1 rue antonin artaud
    31320 castanet tolosan
    Tel: 0033.6.85485107
    Email : [email protected]
    Nationalities :
    - French
    - Lebanese
    Date and place of birth:
    April 18, 1986
    Toulouse,
    France
    Education
    2009
    Master in Electrical and Control Systems Engineering
    Option Embedded
    systems
    University of technology of Belfort-Montbliard france
    2006 University
    Diploma in Industrial and Maintenance Engineering
    DUT Degree Equivalent to 3 years of
    technical studies
    Institute of technology of Saida
    Lebanon
    Experience
    February
    July 2009 Galley-Technologies (Neuchatel-Switzerland)
    Mission:
    Development of
    Labview Modules for Pharmaceutics and Robotics
    industries
    Realization(s):
    Communication and data-Analyse Software using
    TCP/IP:
    - Development of a software (Labview Programming) that would permit data
    transfer between many pharmaceutical ovens, in order to analyse all production cycle, and test
    the conformity of the final products.
    5 Axis robot simulation software:
    Concept and development of simulation tool for a robot working cycle
    September 2007
    February 2008 Valeo VSS (Paris France)
    Mission:
    Qualification and management of
    automobile electronic components
    Qualification of specific electronic components
    Making sure that all electronics components will be qualified on time before the
    Start-of-Project
    - Discussion between me, Valeo supplier and Valeo Project Manager in order
    to grant Valeo quality standard Specifications or to approve supplier deviations.
    Management of electronic qualification documents on Valeo ePLM system.
    - Participating to
    daily quality reviews meetings and brainstorming in order to apply a PDCA (plan Do Check
    Act)
    Management of Valeo DSA products under IMDS Base
    - Management and
    declaration of Valeo Division Systems Access products under IMDS base (international Material
    data systems)
    - Creating MDS sheets then sending them to Automobile
    Constructors.
    February June 2006 United-Group Machinery
    (Beirut-Lebanon)
    Mission:
    Renovating a bag-filling
    machine
    Realization(s):
    Mechanical system
    - Drawing all parts of
    the machine (3D), assembly and motion using Autodesk Inventor.
    - Unmount, replacing bad
    parts then assembly of the machine.
    - Integrating of a weigher machine to the top of the
    bag-filling machine.
    Control system
    -Removing old control system and
    integrating a PLC and a control panel
    -Programming the PLC (Delta type) with Ladder
    diagram.
    Knowledge
    Languages
    French
    and Arabic: Native languages.
    English: fluent, TOEIC 890/990 Test of English for
    International Communication.
    Spanish: Intermediate.
    Automation
    - Labview,
    Matlab Simulink
    -Programming DSP Controller TMS320LF2407.
    -Programming in languages:
    assembler, C.
    - PLC Programming (Crouzet, Delta, tlmcanique, Moller) -Ladder, List,
    Grafcet-
    -Controlled systems: Continuous aspect
    Electronics
    -Programming in
    VHDL.
    -Programming of PIC 16F87X.
    -Simulation (Simplorer, Circuit maker, Electronic
    Workbench, Proteus, Kicad).
    Electrical
    - Machines D.C. current, synchronous,
    asynchronous, electrical supply networks.
    Various
    - CAD: AutoCAD, Autodesk
    Inventor, Mastercam, Programming of machines with numerical control CNC (languages Num, Fanuc,
    Fagor).
    -CAM: Ms-Project (Gantt, Pert, Kanban) 
    Message Edité par salimo le 11-04-2009 04:35 PM
    ~~~~~~~~~~~~~~~~~~Looking for a LABVIEW JOB (In EUROPE)>~~~~~~~~~~~~~~~~~~
    **The Best Way To Predict**The**Future Is To Invent It**
    Attachments:
    CV_Salim_Darwiche_S_12_10_09.doc ‏77 KB
    CV_SalimDARWICHE_EN_S.doc ‏229 KB

    Message Edité par salimo le 11-04-2009 04:36 PM
    ~~~~~~~~~~~~~~~~~~Looking for a LABVIEW JOB (In EUROPE)>~~~~~~~~~~~~~~~~~~
    **The Best Way To Predict**The**Future Is To Invent It**

  • Control Systems Developer (High Point, NC)

    Computerway Food Systems, located in High Point, NC, is looking for a Controls Developer to join it's team.
    CFS provides Inventory Management and Control Systems to the food industry.
    General Overview:
    The successful applicant will assist the Controls Systems Manager in designing, maintaining and supporting new and existing systems.  Daily responsibilities include coding, testing, documenting, training, and development support of these systems.  Applicants should possess a good understanding of electrical engineering principles, coding practices, operating systems, and networking. 
    This individual must be a team player and be able to communicate well with others.
    Helpful skills / knowledge :
    Electrical engineering / Control systems
    LabVIEW Programming language
    Familiarity with .Net framework / architecture    
    General understanding of Databases 
    CFS offers Competitive wages, paid vacation and holidays as well as medical, dental, profit sharing and 401K plan.  
    If interested in learning more, visit our website at www.mycfs.com to apply email resume to [email protected]

    Applicant must be a legal US resident.

  • SSIS and CDC - Incorrect state at end of "Mark Processed Range"

    The Problem
    I currently have CDC running on a table named subscription_events.  The corresponding CT table is being populated with new inserts, updates, and deletes.
    I have two SSIS flows that move data from subscription_events into another table in a different database.  The first flow is the initial flow and has the following layout:
    The Import Rows Into Vertica step simply has a source and a destination and copies every row into another table.  As a note, the source table is currently active and has new rows flowing into it every few minutes.  The
    Mark Initial Load Start/End steps store the current state in a variable and that is stored in a separate table meant for storing CDC names and states.
    The second flow is the incremental flow and has the following layout:
    The Import Rows Into Vertica step uses a CDC source and should pull the latest inserts, updates, and deletes from the CT table and these should be applied to the destination.  Here is where the problem resides; I
    never receive anything from the CDC source, even though there are new rows being inserted into the
    subscription_events table and the corresponding CT table is growing in size with new change data.
    To my understanding, this is how things should work:
    Mark Initial Load Start
    CDC State should be ILSTART
    Data Flow
    Mark Initial Load End
    CDC State should be ILEND
    Get Processing Range (First Run)
    CDC State should be ILUPDATE
    Data Flow
    Mark Processed Range (First Run)
    CDC State should be TFEND
    Get Processing Range (Subsequent Runs)
    CDC State should be TFSTART
    Data Flow
    Mark Processed Range (Subsequent Runs)
    CDC State should be TFEND
    Repeat the last three steps
    This is not how my CDC states are being set, though... Here are my states along the same process.
    Mark Initial Load Start
    CDC State is ILSTART
    Data Flow
    Mark Initial Load End
    CDC State is ILEND
    Get Processing Range (First Run)
    CDC State is ILUPDATE
    Data Flow
    Mark Processed Range (First Run)
    CDC State is ILEND
    Get Processing Range (Subsequent Runs)
    CDC State is ILUPDATE
    Data Flow
    Mark Processed Range (Subsequent Runs)
    CDC State is ILEND
    Repeat the last three steps
    I am never able to get out of the ILUPDATE/ILEND loop, so I am never able to get any new data from the CT table.  Why is this happening and what can I do to fix this?
    Thank you so much, in advance, for your help!  :)
    Edit 1
    Here are a couple of articles that sort of describe my situation, though not exactly.  They also did not help me resolve this issue, but it might help you think of something I can try.
    http://www.bradleyschacht.com/understanding-the-cdc-state-value/
    http://msdn.microsoft.com/en-us/library/hh231087.aspx
    The second article includes this image, which shows the ILUPDATE/ILEND loop I am trapped in.
    Edit 2
    Last week (May 26, 2014) I disabled then re-enabled CDC on the subscription_events table.  This didn't change anything, so I then disabled CDC on the entire database, re-enabled CDC on the database, and then enabled CDC on the
    subscription_events table.  This did make CDC work for a few days (and I thought the problem had been resolved by going through this process).  However, at the end of last week (May 30, 2014) I needed to re-load the entire table via
    this process, and I ran into the same problem again.  I'm still stuck in this loop and I'm not sure why or how to get out of it.
    Edit 3
    Before I was having this problem, I was having a separate issue which I posted about here:
    CDC is enabled, but cdc.dbo<table-name>_CT table is not being populated
    Could running these commands have created this problem for me on SQL Server?

    Hi Keolanui,
    Thank you for your question.
    I am trying to involve someone more familiar with this topic for a further look at this issue. Sometime delay might be expected from the job transferring. Your patience is greatly appreciated.
    Regards,
    Mike Yin
    If you have any feedback on our support, please click
    here
    Mike Yin
    TechNet Community Support

  • PI Control Error Between Process Variable and Set Point

    I've developed a PI program that uses measurements from a pressure transducer as the process variable to control air pressure released from a motorized valve. The program works great at lower pressures, but as the set point pressure increases the error between the process variable and set point increases. I've tried several things....adjusting the P seems to initially increase the overshoot but the process variable always settles down below the set point....tried adjusting the EGU min and max values but no real pattern develops with this. It appears as the process variable get closer to the max EGU value of 70000 pascals the error increases.
    I've attached three screen shots showing the process variable curve and setpoint value. The graph of interest is the one in the upper right hand corner.
    Any recommendation or advice would be appreciated.
    tks, Terry
    Attachments:
    Low Pressure.JPG ‏267 KB
    High Pressure.JPG ‏398 KB
    Mid Pressure.JPG ‏266 KB

    Kyle,
    First off....I appreciate your comments. No...there is no value is system represented as U16.
    Actually errors start to develop quite a bit before the maximum. If you look at the mid pressure.jpg file you'll notice that the set point (~28125 Pascals) and process variable (~25625 Pascals) are roughly off by about 2500 Pascals. Then if you look at the high pressure.jpg file you'll notice that the set point (~53000 Pascals) and process variable (~45500 Pascals) are roughly off by about 7500 Pascals. Therefore it appears as the setpoint pressure increases towards maximum the error tends to increase.
    I was curious about something....the set point value I'm inputting into the PID.VI , shown in the high pressure.jpg file, is from EGU to percent.VI. It would look exactly like the EGU to percent VI feeding the process variable input of the PID.VI with the set point value feeding the EGU to percent.VI input. Would I be better off feeding the actual set point value to the PID.VI input instead of percentage?
    Thanks, Terry

  • SAP TDMS add on setup on central/control , sender and reciever systems

    I found that SAP TDMS is shipped in the following add-ons:
    DMIS: Contains general functions, for example for the process monitor and for the technical data transfer
    DMIS_CNT: Contains TDMS-specific functions and some of the process types
    DMIS_EXT: For various additional process types (reduction scenarios) for SAP TDMS; currently, it contains only the process   type for business process library
    DMIS_BSC: For the process types to be used with SAP BI or CRM systems
    DMIS_HR: For the process types to be used in the context of SAP Human Capital Management (HCM)
    I have read TDMS master guide under section 3.4.1 Setting up the TDMS Server. There is a reference to SAP Note 970531 which is for DIMS setup and there is also reference to SAP note 970532 which is for DMIS_CNT setup.
    I would like to know if DMIS_EXT,DMIS_BSC and DMIS_HR need to be setup on TDMS central/control server , sender and reciever or only need to be setup on central/control server for respective scenario realization.
    Best Regards
    Mohammed Ashraf

    All the add-on components need to be installed in all the system (sender, receiver, central, control) in the landscape.

  • When I click to open firefox it says that "firefox is already running but is not responding. To open a new window, you must first close the existing Firefox process, or restart your system" and I've tried to shut down and restart my computer but it keeps

    when i click to open firefox it says that "firefox is already running but is not responding. To open a new window, you must first close the existing Firefox process, or restart your system." and I've tried to shut down and restart my computer but it keeps showing the same message. I've even uninstalled Firefox and then reinstalled in the hopes that the problem would be solved but it this message is still popping up. What can I do to solve this problem?
    == This happened ==
    Just once or twice
    == I was on facebook trying to upload pictures yesterday. ==
    == User Agent ==
    Mozilla/4.0 (compatible; MSIE 7.0; Windows NT 5.1; .NET CLR 1.0.3705; .NET CLR 1.1.4322; Media Center PC 4.0; InfoPath.1)

    Do you have a profile lock file in your profile folder? If so, delete it and see if TB runs properly:
    http://kb.mozillazine.org/Profile_in_use#Remove_the_profile_lock_file

  • I have 3dparty software wirelessly with a cryptographic authentication system without my consent (seems to be new technology developed by stanford) obtaining ownership of my iPhone 4s software and controlling it with remote device to jail break. Now what?

    I have 3rd party software wirelessly injected and used on my iphone with a cryptographic authentication system without my consent (seems to be new technology developed by stanford and apple security is not updated for this technology) obtaining ownership of my iPhone 4s software and controlling it with remote device to jail breaking my phone, adding and removing software, changing settings all from a remotely controled device from different location (I have a Mac address I'd of this device to know for sure). Almost undetectable. When I look at the legal section of my phone it shows a list of all the unauthorized 3rd party software "as is" copyright encrypted on the phone.  This is the most basic way to legally steal software of any kind.  Because of this legalality 3rd party ownership have total control of certain software correlated with hardware use including visualization technology, etc.  most people luckily will never have this happen to them so it's unlikely many readers have not a clue of what I'm saying currently.  Either way, without needing to obtain specific warranty of any kind "as is" copyright control makes system restores not a solution because the source code is not directly encrypted on the actual hardware device only a copy right notice must appear on the specific device 3rd party software validation making it extremely difficult for me to take control of the situation. Apple claims their iOS technology prevents this type copyright obstruction from being possible, however, according to my phone a new form of technology was used developed by Tom wu of Stanford university called the STANFORD SRP AUTHENTICATION TECHNOLOGY which uses Some form of cryptographic authentication system and uses quote "secure remote password" which seems to suceed in hacking iOS apple technology apple claims is not possible to jailbreak an unstolen phone or without the owners consent As well as loading the device with 3rd party copyright Notices to make all of this legalized. My phone shows atleast 30 pages worth of legalized 3rd party copyright permissions! Yesterday my apple care provider labeled me a jailbreaker and refused to look at my legal documented proof which completely blew my mind because it voides my apple care contract I spent 100 on. This employee did not take all factors into consideration and made quick assumptions as well as verbally speaking to me as I'm an automatic criminal. I left the store yesterday with no payed insurance help on a problem I had no control over and couldn't prevent, leaving with voided contracts. This is an apple users worst nightmare and I have spent days researching all of this like i am some kind of lawyer only to be able to use my phone the way it should and spent alot of money on.  I can legally backup any claim I have just wrote above currently and have a large source of data collected to prove apple is wrong in voiding insurance support on this issue. The problem lies in apple avoiding and not wanting to believe their software can legally be obtained ot "hacked". Yet still labeled a jailbreaker basically.. What should I do????? Been to local apple store 3 times and rebooted my phone as well sprint service restore 4 times and spoke with reps twiice on the phone. Spoke with my phone provider who said apple has full control over these matters so they can't help me.  My case is according to apple "still open"...Anyone else heard of this or of Stanford's office of technology licensing? Maybe I need to buy a blackberry again or just use a landline so I can stop being my own lawyer and focus on other productive areas in life instead of this horrible mess. I shouldn't have to prove to apple I not a jailbreaker they should have to prove I'm one before voiding support I desperately need!!

    Mullaly75 wrote:
    I assume u guys don't understand what open source software is
    Yes, I think most of us do understand what open source software is. It sounds as if you don't. Here's some information:
    Open-source software (OSS) is computer software that is available in source code form: the source code and certain other rights normally reserved forcopyright holders are provided under an open-source license that permits users to study, change, improve and at times also to distribute the software.
    Open source software is very often developed in a public, collaborative manner. Open-source software is the most prominent example of open-sourcedevelopment and often compared to (technically defined) user-generated content or (legally defined) open content movements.
    from http://en.wikipedia.org/wiki/Open_source_software
    Yes, Tom Wu of Stanford wrote a paper on something called Secure Remote Access Protocol. It's a form of Asymetric Key Exchange and has nothing to do with hacking anything. It's actually intended to protect data.

  • Firefox is OPEN and working fine, but when I click a link in Thunderbird I get 'Firefox is already running, but is not responding. To open a new window, you must first close the existing Firefox process, or restart your system.'

    If I click a link on my desktop or in any other program (while Firefox is open and running), I get this message: "Firefox is already running, but is not responding. To open a new window, you must first close the existing Firefox process, or restart your system." There's about a billion links for this if you Google it, but they all say that Firefox wasn't shut down properly. (OK, maybe not ALL of them, but if the needle is in that haystack, I haven't yet found it.) That's not the issue in my case since I haven't shut FF down at all.
    == This happened ==
    Every time Firefox opened
    == IDK

    This began to happen to me when I tried to run two separate profiles simultaneously on the same installation of firefox with -no-remote

  • I deleted the profile and firefox4 and then downloaded firefox4 again. But when i click firefox it says Firefox is already running, but is not responding. To open a new window, you must first close the existing Firefox process,or restart your system.HELP!

    somehow i couldn't get rid of one website called www.searchqu.com/405 set as my homepage... I tried all solutions given to change the homepage but whenever i restarted firefox that homepage used to come automatically.. So, I deleted the profile (even from recycle bin!!) and deleted the firefox and downloaded it again hoping to get my problems fixed (which didn't happen!) because i'm getting dialog box saying- Firefox is already running, but is not responding. To open a new window, you must first close the existing Firefox process, or restart your system.

    You don't say which operating system you have installed?
    Assuming it's Windows, right click a blank part of the Windows Taskbar and go to Task Manager. Then click the ''Processes ''tab, find '''firefox.exe''' and then right click it and choose '''End Process'''.

Maybe you are looking for

  • How do I create a folder for private documents which can be password protected?

    how do I create a folder which can be password protected please?

  • Help with Yosemite update

    I updated a mid 2011 IMac to Yosemite and now cannot access my photos.  It says because I need to update iPhoto, but when I try it says update available for this apple ID.  I have tried all of the obvious solutions to no avail.  I wouldn't have updat

  • Software downlaod failure L7590

    I am running windows7 home permium (64 bit).  I have an Officejet Pro L7590 and am trying to update the drivers.  The download fails every time.  Running the Install Wizard the failure message says "download cancelled". thanx b

  • Correct way (if any) in paragraphs

    If I have a paragraph of type, ranged left (example below) set out with no widows/orphans etc but I have a word starting on its own, what is the correct way to solve this? Start a new paragraph or leave it on its own? Sometime when i do this I get a

  • [Memory] Need Statements of Volatility

    Can you help me? Possibly point me in the right direction? We are looking for a Statement of Volatility for UCS 2100, 5100, 6100, B-series Blade and Nexus switches. Who handles Federal security concerns for Cisco UCS and Nexus? The SoV contains infor