I am trying to record the actual time of the change in digital input pattern.

Hello;
You will probably need a combination of the digital board you have with a counter board.
Then you can catch the intial time that the application starts, and then to count the PCKL pulses with the counter. You will need to stop the counter when the pattern you are looking for is matched (you can configire the 6534 board to generate a pulse when the pattern is match, and use that pulse to stop the counter).
Since you know the TimeBase that the counter is using, to have the accurate time that the pattern was matched, you will need just to multiply the number of pulses the counter registered by the timebase, and add the initial time. I suggest you to work with the 660x counter board for that purpose.
Hope this helps.
Filipe A.
Applications Engineer
National Instruments

Similar Messages

  • Time between digital inputs?

    Hi, I would like to measure the time between a digital input being true.
    Basically I have a prox picking put a point on a rotating shaft (to determine RPMs).
    What I want to do is measure the time between consecutive input signals from the prox, divide 1 rev by the time, multiply this by 60 to get RPMs. Then compare that value to a set value ( say 300 RPM ). If it is equal or great, contine onto the rest of the program, if it is less than the set value, keep looping until it is greater than or equal to the set value.
    Thanks in advance for the help!
    Ryan
    LV 7.1

    If you need to measure accurately the rotation speed on a single turn, software timing may not be accurate enough, since the Window internal clock readings have lags (read "errors") of more than 10 ms (= 100 rps, about 2 rpm error), even when no other application is running. So either you count (and wait) for a given number of rotations, and calculate an average, or you use hardware timing with a counter on the DAQ card (if any)...
    Otherwise, if you only need an estimate of the rotation speed, you can read the digital line and wait for 2 consecutive changes. The period can be calculated from the time stamps. See the attached vi. Wait a few seconds to observe the variations generated by Windows.
    Merry Christmas, and Happy Wiring !
    CC
    Chilly Charly    (aka CC)
             E-List Master - Kudos glutton - Press the yellow button on the left...        
    Attachments:
    Rotation speed.zip ‏14 KB

  • Measuring times of digital events on a NI PCIe 6259

    I am trying to figure out how to acquire time stamps every time a digital input (Boolean) changes values relative to the beginning of a AO output. Ideally, I would like to reset the time stamp to 0 each time the AO output occurs (different trials). Both counters on the 6259 are free, however I am already using the ao/SampleClock in my VI. Thank you for any help.

    Hello Joes,
    Since you have 0-30 events which you want to measure the time of, it would be easiest to calculate the time in post processing. You can use a start trigger to trigger both the analog output and the digital input.  Using the start trigger will synchronize the start time. The high to low transitions can be found in the recorded data and the time can be calculated using the position in the data array and the delta time between samples.
    Eric
    Eric Liauw
    AE Specialist - Automated Test | CLD | CTD
    National Instruments

  • Digital Inputs do not record over long time periods

    I am running Signals Express 2009 with a USB-6009.  I have a project that needs to record the states of 8 digital inputs over a 24 hour period.  The inputs typically do not change state for long periods of time.  When I run the project it does record and gather data if I stop it "soon"(I have gone as long as 30 min.)  When I leave it running overnight it does not appear to record anything.

    If you have not already, you should try turning off display updates in the "Operate »Update Signal Views While Running" menu item.  Set this to Update None.  Also, turn off "Prepare log data for viewing" under the Logging part in the Tools » Options dialog.  
    When I ran your project overnight, it ran out of memory.  The first error it threw was "Not enough memory to complete this operation."  The problem was that SignalExpress saved a great deal of data in memory for easy displaying while it's running, but this grows too big when it runs overnight.  The second error was as follows:
    Logging Stopped:
    Logging was stopped because an error occurred with a Step in the Project. 
    If this error is because of a device buffer overflow, you can improve performance by turning off display updates using the "Operate »Update Signal Views While Running" menu item.
    You can also change the way signals are logged by changing the Logging Options in the Tools»Options dialog.  
    Turning off  the "Prepare log data for viewing" will greatly improve performance. 
    Mark E.
    National Instruments
    Schedule a Free 1-Hour online LabVIEW Tutorial with an NI Applications Engineer

  • How can i request the actual time code of digital video recorder, i am using RS232 interface for asking actual time code of digital video recording

    how can i request the actual time code of digital video recorder, i am using RS232 interface for asking actual time code of digital video recording

    If you have an RS-232 interface to the digital video recorder, it may be that you can send a command to the video recorder in order to get the time code sent back to your application - you would then read this as a string and then incorporate this data into your program.
    The best source of help will be any documentation you have relating to the serial (RS-232) interface with the digital video recorder. This documentation should have commands that you can send to the recorder and expected response strings that you should get back from the device. This task should be straightforward but can often be frustrating without documentation about the video recorder. This will not be something that you can "guess" - past experience in writing serial communication ap
    plications has shown that a good manual is your best friend.
    Failing this if you have any source code for example programs that have already been written to communicate with the recorder, you might be able to extract the relevant ASCII strings and use them within your application. This is true whether you are using LabVIEW or a text-based language.
    Jeremy

  • Digital input and digital output at the same time

    Hi all
    I have a PCI-6503 board. I have done 2 task that run simultaneously: the first one is port0_16 output and the second one is port2 input.
    I get sometimes (not every times...this is strange...) error-200587 saying:
    'Requested operation could not be performed, because the specified digital lines are either reserved or the device is not present in NI-DAQmx.
    It is possible that these lines are reserved by another task, the device is being used through the Traditional NI-DAQ interface, or the device is being reset. You might also get the error if the specified resource is currently in use by LabVIEW network variables bound to the DAQ Channel, or if the DAQ Channel is being used in any OPC Client software.
    If you are using these lines with another task, wait for the task to complete.  If you are using the device through the Traditional NI-DAQ interface, and you want to use it with NI-DAQmx, reset (initialize) the device using the Traditional NI-DAQ interface. If you are resetting the device, wait for the reset to finish.'
    In the attached VI i have recreated the basic structure of my real VI (the error is present even here of course...).
    How can i do?
    I want to have both digital input and digital output with the same PCI-6503 every single cycle... Is it possible?
    Please help me!!!
    Kind regards.
    I love the smell of napalm in the morning
    Attachments:
    DIO simultaneously error.vi ‏31 KB

    Hello Maverick,
    Did you have any luck with the example Raven sent you?
    In Raven's example, it properly passes the DAQmx task from one SubVI to another to avoid having to open the task again. These errors are likely to occur when you have multiple DAQmx calls in a VI that call the same task again without clearing the previously opened task. If at any given time you try to open a task that already is being used, you might receive an error "resource is reserved"... similar to your original example.
    If you are interested, here is an awesome link that gives a detailed explanation of the LabVIEW dataflow paradigm
    Learn 10 Functions in NI-DAQmx and Handle 80 Percent of Your Data Acquisition Applications
    Thanks and good luck!
    Jordan Randall
    National Instruments Italy

  • How can i measure the time between two successive rising edges ,using digital input ..

    Hello
    I'm trying to measure the time in seconds between each two successive rising edges on a digital input .
    Till now I have managed to detect the rising edge ,increment a counter with each rising edge ,and snap the time at which the rising edge happenned
    all I need now is to subtract the current rising edge time from the previous rising edge time in order to calculate (T) which can be 1/frequency and display it in realtime to the user.
    but I don't know how to do this
    Can somebody please help me !!!
    note: the time that I'm measuring ranges between 200 ms - 2 seconds
    Solved!
    Go to Solution.
    Attachments:
    Counter without time.vi ‏11 KB

    Cheers for that. It's always a good idea to post your SubVIs as well - the problem could be in one of those.
    To help you out:
    You already know how to use shift registers so why not use one again for time? Create a new shift register for  the time then simply compare the "rising edge time" to the the previous time stored in the shift register and then write the new time to the shift register.
    Just a few other pointers:
    1. You'll want to initialise your shift registers ie wire a constant to the left hand register outside of the loop. This will cause the register to be reset each time the program is run. This is so that your counter will start from zero each time you run your code.
    2. You don't need to use the "greater than?" compare function with boolean as they can only be true or false (1 or 0)! The "Equal?" function is what you should use here.
    3. Lastly, it's a small thing but you can use the same tunnel that feeds into a case structure in each of the cases - no need to create two tunnels for the true and false cases, use the same one.
    -CC
    "If anyone needs me, I'll be in the Angry Dome!"

  • How can I measure the time between each two successive rising edges ,using Digital Input ?

    Hello
    I'm trying two measure the time in seconds between each two successive rising edges on a digital input .
    Till now I have managed to detect the rising edge ,increment a counter with each rising edge ,and snap the time at which the rising edge happenned
    all I need now is to subtract the current rising edge time from the previous rising edge time in order to calculate (T) which can be 1/frequency and display it in realtime to the user.
    but I don't know how to do this
    Can somebody please help me !!!
    Solved!
    Go to Solution.
    Attachments:
    Counter without time.vi ‏11 KB

    Woah!  
    Sorry Apok, but your code is becoming way too complicated/messy. I don't think that all of those shift registers or boolean conversion/operators are needed at all.
    If you want to measure the timing between two button presses then this is a different (much less complicated) way. It simply records the timing of the button press into a shift register then compares the two.
    Spoiler (Highlight to read)
    Of course this is a very quick and basic solution just to show you that it can be much simpler than you are making it (remember to use the mechanical actions of the buttons to get the behaviour you want).
    A better way would be to use an event structure looking at value changes of the buttons to determine the timings between clicks.
    -CC
    "If anyone needs me, I'll be in the Angry Dome!"
    Attachments:
    Time between clicks.vi ‏9 KB

  • How can I measure time between transitions at digital input

    I am using LabVIEW 6.0 to measure the time duration between 2 transitions in a digital input port. I have a set up including an HP 34970A Data Acquisition unit with the 34907A Multifunction Module plug-in. The LabVIEW program is trying to poll the digital input for level changes and then using the Time function(Tick Count) to check the times at the transitions. However this method doesn't work reliably as I have to measure time periods of 500ms.
    Is there any good way of mesuring time period with the above setup. I don't have a module which connects to the internal multimeter in the 34970A. The other stuff I have are a HP 34903A(Actuator Module) and a HP 33120A(Function/Waveform Generator).
    Any method for m
    ore accurate time measurement with the above setup will be appreciated. If not, what else do I need to make accurate time measurements.

    Frankly I doubt that you're going to be able to measure time interval with much accuracy. You're periidically polling a static digital input and how often you poll is going to vary. You could try polling as fast as possible and eliminate as many background tasks as you can. If your tolerance for the measurement is plus or minus 100 msce, then maybe you'll get a decent measurement most of the time. If it's plus or minus 5/10 msec, then it will never happen. The pc's clock is just not that accurate and a software timed loop on Windows is not deterministic enough. Get a counter/timer board for something really accurate or use a scope to capture the waveform.

  • Acquire Analog and Digital inputs at the same time with 6025E card

    I have 6025E DAQ card, all the analog channels are used
    up. There are several digital signals, such as flowmeter. Can I acquire both kinds of data at the same time with my 6025E card? Thanks for your help.

    I suggest you search the examples that ship with LV
    Digital
    Find Examples>>>Hardware Input and Output>>>Digital Input and Output>>>8255
    for doing each type of I/O seperately.
    When you have found two examples. Just try to run the two at the rate use need in your final app.
    Post follow-ups Q's here. I am not personally familiar with that deveice so I can not speak from experience.
    I would generally expect that if you sample rate is low (i.e. <10Hz) you maybe happy with the results. If you want to run faster or have the PC do something else at the same time, the timing of the signals form the DIO lines may be suspect.
    So...
    It depends.
    Trying to help,
    Ben
    Ben Rayner
    I am currently active on.. MainStream Preppers
    Rayner's Ridge is under construction

  • Triggering an event with a digital input

    Hello all,
    I'm writing my first Labview program.  I used an architecture I found on the forums here, and it has been very helpful in getting me started.  This architecture uses two while loops, one containing an event structure and one containing a case structure.  (This is a queued state machine architecture, I believe).
    Part way through the programming, we decided we needed a sensor to make sure the part was in the test fixture during the test.  If the part is removed during the test, we'd like to safely stop the test.  So basically, I need to monitor a digital input (on an NI-USB-6525 module) and enter the "Stop" case if the digital input turns off.  I would also like to make sure this digital input is on before entering the "Start" case.  I don't care if the input changes state when the test is not running, nor do I care about its state during the "Exit" case.
    I'm really not sure how to add this functionality to my "stop" case.  I don't even know if it's possible.  I've been researching DAQmx events, but I haven't found an example or answer that aligns with my particular problem. 
    I've attached my code.  It's incomplete right now - I still have a large number of steps to add.  I wanted to get this issue figured out before I programmed any more steps.  A preview of the code showing the basic architecture is shown in the picture below.
    Does anyone have any ideas or suggestions for me, or questions if my problem is unclear?  Also, if you see anything else in my code that will be problematic, please let me know.
    Thanks in advance!
    Attachments:
    Main_Loop_072412.vi ‏195 KB

    I should also add that I looked into event dynamic registration, but it seemed incompatible with my issue.  I don't want my top loop to run only when an event triggers it - I want it to run all the time so that it can immediately respond to button presses. Also, most of the triggering I found was based on value change.  I care about the actual value, not just that it changed.
    I don't want to do anything that will bog the code down too much since it is important that the system respond immediately to inputs, especially to the stop or exit button presses.
    I'm sure I am missing something very basic here.  I'm used to ladder logic, where everything is simple and straightforward. 

  • Can you perform simultaneous timed digital input and output using a PCI-6120?

    Is it possible to do simultaneous timed digital input and output using a PCI-6120? It seems that timed digital operations require using the group read/write commands, which utilize an entire port. Since the PCI-6120 has only 1 digital I/O port, I would like to be able to use 2 lines as outputs and 1 line as input, and do both in a deterministic fashion. i.e. create a digital signal with known pulse widths and read an input line at a known time after the outputs were set. Is this possible to do with only one digital I/O port?

    Hello,
    This can be done in LabVIEW. There is actually an example that installs with NI-DAQ.
    Below is a link to a Knowledge Base that explains how to find the correlated digital I/O examples.
    http://digital.ni.com/public.nsf/websearch/B849664604EB34B886256D12005B5520?OpenDocument
    Just take a look at the example titled �Continuous CDIO with external clock (E).vi�
    Best regards,
    Justin Tipton
    National Instruments

  • I was given an assingment, but have no idea where to begin. The assingment is to create a text file using notepad with all of my digital inputs and some how make those imputs show up on my digital indicators on my control pannel

    I was given an assingment, but have no idea where to begin. The assingment is to create a text file using notepad with all of my digital inputs and some how make those imputs show up on my digital indicators on my control pannel.
    When it was explained to me it didn't sound to hard of a task, I have no LabVIEW experience and the tutortial sucks.

    StevenD: FYI, I did NOT give you the one star rating. I would never do that!
    StevenD wrote:
    Ow. Someone is grumpy today.
    Well, this is an assignment, so it is probably homework.
    Why else would anyone give HIM such an assigment, after all he has no LabVIEW experience and the tutorials are too hard for him?
    This would make no sense unless all of it was just covered in class!
    This is not a free homework service with instant gratification.
    OK! Let's do it step by step. I assume you already have a VI with the digital indicators.
    "...but have no idea where to begin".
    open notepad.
    decide on a format, possibly one line per indicator.
    type the document.
    close notepad.
    open LabVIEW.
    Open the existing VI with all the indicators.
    (are you still following?)
    look at the diagram.
    Who made the program?
    Does the code make sense so far?
    Is it a statemachine or just a bunch of crisscrossed wires?
    Where do you want to add the file read?
    How should the file be read (after pressing a read button, at the start of the program ,etc.)
    See how far you get!
    Message Edited by altenbach on 06-24-2008 11:23 AM
    LabVIEW Champion . Do more with less code and in less time .

  • Simultaneous Digital Input and Output from NI 9403

    Hi,
    I was wondering if it is possible to digital output through one line in this module(NI 9403) while simultaneously reading from 10 other lines?
    Basically what I need is for line0 to always be closed(true), and read lines1:10 - at very least 1sample/second.
    I have attached a stripped down version of my code illustrating my error. I thought I was getting the error because the two tasks were using different clock configurations, but I tried using the same inputs and that doesn't work for me.
    Any input is greatly appreciated.
    Thank you
    Attachments:
    Digital I-O.vi ‏22 KB

    Hi Matthew,
    The behavior you're seeing is expected for the 9403 module, since it is a serial module. The DAQmx help has the following restrictions in the Digital I/O Considerations for C Series Devices section.
    Timed digital input/output restrictions:
    You cannot use parallel and serial modules together on the same hardware timed task. 
    You cannot use serial modules for triggering. 
    You cannot do both static and timed tasks at the same time on a single serial module. 
    You can only do hardware timing in one direction at a time on a serial bidirectional module.
    So you can only do timed input or output at one time, but not both. However, based on the VI you attached and the description of what you want to do, you don't necessarily need both timed tasks in your loop. You can create a static output task to update that one line and after that, you can just start your timed input task on the rest of the lines. This should maintain the state on the DO line, since you're not acquiring from it.
    Cheers,
    Cristina
    Cristina

  • "External sample clock" and "Rate" for digital input acquisition

    Dear all,
    I want to acquire digital input (21 bits with external clock = 50 kHz) with a PCIe-6343 NI board. Using the  DAQ assistant under Labview, I selected the advanced timing with the sample clock time parametrized as External. However, it is also possible to select the Rate of the acquisition. In my case, i want to get the data at the rising edge of the external clock signal, so at a frequency of 50 kHz.  How can I do that ? I just need to put a Rate of 50 kHz ?
    thanks for your help.
    Cedric 

    Cedric,
    dddsdsds wrote: 
    [...]In my case, i want to get the data at the rising edge of the external clock signal, so at a frequency of 50 kHz.  How can I do that ?[...]
    You answered your question already. If you want to use an external clock, you have to configure the timing source of your task to be external. In order of proper buffer configuration, you should enter 50kHz as rate in addition to the external configuration, but this will not influence the speed of the acquisition (since it is "clocked" externally!)