Hello,
I am trying to create a digital signal and view it with the oscilloscope. I have started with an analog one, converted it with DWDT Analog to Digital and when I am trying to connect it with the oscilloscope (DAQ Assistant) via the NI PXIe-6363 card and SCB-68A connector, I have the following error:
What is wrong with my design?
Thanx a lot in advance!
Attachments:
error.PNG ‏39 KB

You're simulating an analog signal and the DAQ Assistant is configured to output a digital signal.
To create a digital waveform, look for an example or checkout functions available in 'Digital Waveform VIs and Functions' sub-palette.
Or you can also think of spending some money on buying 'NI Digital Waveform Editor'.
I am not allergic to Kudos, in fact I love Kudos.
 Make your LabVIEW experience more CONVENIENT.

Similar Messages

  • Vb6,card: pci6111,daq box:bnc2110,receive digital signal+react on it,how?

    want to send a digital signal from a function-generator into the daq-box (e.g. into ACH 2) and to react in my program on it, when the dig.signal makes the first step from 0 to 5 V e.g.must i change anything else on hw than connecting the function-generator to ACH 2? How can I react on it with my created CWDI1-Objekt. It doesn't work! Thnx a lot! p.s. other ideas are also wellcomed!

    Hi,
    I'm not understand the relationship between the components of your system (or even what they are!). You'll have to clear your system description a little bit.
    1.- You have a DAQ board, what model?. This is important since it will determine what VIs you can use. Are you using the board for Analog input, anolog output ...?
    2.- "The DAQ card relays the information to a digital oscilloscope", What do you mean by this?. Is the digital scope a hardware device or some sort of software component?.
    3.- ActiveX is used to communicate different software components, not to communicate with external instruments. Again, what is the o-scope?.
    4.- Initially you say that Win600 is a machine and then a program. Which one is it?.
    I think once this quest
    ions are cleared up we can start thinking of solutions.
    DiegoF
    National Instruments.

  • FPGA Digital Signal Output Problem

    Hi,
    I am having a problem outputting a signal through my PCI-7831 and would appreciate any advice anyone has as I am beginning to crack the wall where I am banging my head into it. 
    My software is LV7.1 with FPGA module 1.1.  I am controlling a VI compiled onto the PCI-7831 with a host VI in windows.  I am viewing the outputs I mention on a high end oscilloscope.  I'm relatively new to LV and very new to the FPGA module.
    The FPGA VI consists of 3 while loops though only 2 loops are not performing as expected.  The FPGA while loops in question contain a single sequence structure that has as their first frames an IRQ 0 and 1 respectively . 
    In the host VI I am waiting for IRQ, writing the value of 2 wait timers,  and acknowledging the IRQ in the first frame of a sequence.  The FPGA then sets the states of 2 DIO outputs to both high.  Then the timers keep both outputs high until the next frame is reached, then 1,0 is written, the second wait expires, and the loop repeats until the while loop conditions in the host VI are met and the sequence in the host VI indexes (this is about 1 second.)
    For the second loop, I am going to the next frame in the host VI. This host works the same as the above sequence but only 1 value is being written, 0,1.
    In any case, it works but has 2 bugs I can't reason.
    The last, and only the last, iteration of the "both high" period is wrong.  The 1,1 becomes 1,1, then 0,1 about halfway through the wait, then the 1,0 occurs properly, then the 0,1 period begins properly.
    The other bug is that at the beginning of the 1,1; 1,0 sequence the 1,0 is repeated twice.
    I am using these signals to control a custom high amplitude bipolar digital signal generator.
    I have posted my VI's if anyone would like to see them.
    Thanks,
    Ben
    Message Edited by bugsmashers on 07-21-2005 12:57 PM
    Message Edited by bugsmashers on 07-21-2005 12:58 PM
    Attachments:
    Preset_power_top_WHILE_loops1.vi ‏311 KB
    Digital Pulse Amplitude Control Preset Power.vi ‏216 KB
    preset_power_data_gen_FPGA.vi ‏684 KB

    Hi Ben-
    I took a look at your code, and I can explain the first error you are talking about, but I don't think I understand the second error.  For the first error, lets start on the last iteration of the first while loop in your host code.  It first waits on IRQ 0, then sets the 'high' and 'low' parameters on RT, then acknowledges IRQ 0.  At this point on the FPGA side, the top loop (1,1 loop) begins to execute and sets the lines to 1,1.  Meanwhile back on the host, your first loop completes and the second loop starts.  The first thing the second loop does is wait on IRQ 1.  It doesn't have to wait at all because IRQ 1 was set long ago when the FPGA program started, so it clears IRQ 1, and the second FPGA Loop immediately sets the lines to 0,1.  The next thing that happens is your top loop in FPGA (1,1 loop) finishes waiting for the time specified in 'high' and moves to the next sequence frame and sets the lines to 1,0, next the second loop finishes its wait ('Wait Zero') starts the loop over again, sends IRQ 1, which is handled by your second host loop, it acknowledges IRQ 1, and then your second FPGA loop sets the lines back to 0,1.  Long explanation, but I hope not too confusing.  Synchronizing the host and FPGA with everything happening in parallel can get to be a lot to wrap your brain around.
    One comment on the code - From your description and looking at the code it looks like the first pulse iterates for a given period of time, then the second.  The way you have it written right now the pulse period will not be very deterministic - especially if you are using windows as your host.  The reason is that every iteration of the pulse depends on an IRQ interaction, which means you are waiting on your host CPU to do something.  Granted, the host should react quickly, but it is not deterministic - if windows is your host, and you start dragging windows around, you'll notice your period become longer than 'high'+'low'.  A better architecture might be to send the number of iterates of the 1,1 - 1,0 loop you want to execute down to FPGA, and let FPGA count the iterations and report back when it's done.  Then start the second loop, or send all the info down to FPGA and let it control both loops.  If setting 'high', 'low', and 'wait zero' need to happen through out, use the read/write control to just update those on the fly from the host rather than making the FPGA halt while they are updated.  If determinism on the period length is not important for your code, or you designed it the way you did for other reasons, then ignore everything I just said .
    Good luck, sorry I couldn't help on the second problem, if it's still an issue, post back with a little more detail on what '1,0 is repeated twice' means
    Dustin

  • Is there a better way to generate custom timed digital Signals

    I am trying to generate digital output of high and lows with particular delays on different lines. Each daq assistant is activating single line on a port on USB 6501. There more complex high and lows that I need to generate with variable time difference between high and low. There is codebelow which accomplishes what I am trying to achieve but for executing a long pattern of high and low signal is very time consuming to do this way. I am sure there is a better way to do this, I  not a expert on labview so I haven't uncovered its full potential. Can anybody suggest a more effective and a quick way to do this. I would hgihly appreciate. Thanks!
    I have not shown in the code below but through DAQ assistant I have initialized lines to low level logic.
    Solved!
    Go to Solution.

    See the attached file
    Attachments:
    Digital Signal.vi ‏335 KB

  • How to input/output a digital signal and acquire an analog signal at the same time?

    Dasylab, version: 8.0.04
    Acquirement Card: PCI1002L
    When I use DasyLab to acquire the analog signals is no problem without digital inputs and outputs,
    and when I use DasyLab to input or output a digital signal is no problem also, but when I do that at the
     same time, DasyLab tell me the rate is too high and stop.
    so, I searched the manual book1 (user guide) for that, it showed me :
    To internally equalize measurement time and system time in the analog input, digital input and counter
    hardware modules, use the following settings:
       Synchronization: PC Clock
       Sampling rate: <= 5Hz
       Block size: =1
    the problem is, if I set the Sampling rate to 5Hz, the speed of the acquirement datas is not enough for my
    application.
    so, how to improve it? who can give me a example programm for me. thanks!
    by the way, I come from China, my English isn't good, I'm sorry.
    Allen, China.

    Hi,
    Have things changed over the years?
    I need to syncronise a digital output (Modul NI9474) and an analoge input (AI-Modul NI9203) module. I need to measure time intervals from a flank in signal A to a flank in signal B. I would like accuracies of the order of 1 ms. Currently, the signals are not synchronised, with errors of the order of 2 times the block length (block size x sample rate), sometimes much higher. The best I got so far was a block size of around 20 with a sample rate of 1 kHz.
    If I use the master and slave settings on the RTSL settings, my program doesn't run properly.
    If I use digital signals for input and output, I can syncronise them with RTSL settings and everything is good, but I can't always do that.
    Also, if I do anything in the GUI (such as scrollowing something or going to another window), my output gets screwed up properly.
    1. What can be done to synchronise AI with DO?
    2. Is there something that can be done to avoid messing up the output when something happens in the user interface? (I know that I am messing up the outputs as they make some valves switch and that is loud).
    Thanks in advance!

  • How do I convert analogue 5.1 surround sound into a digital signal? (Pioneer SE-DIR800C headphon

    I understand that my SB Audigy 2 card will only output 5. sound from games through its 3 analogue connectors. How do I convert this analogue signal into a digital one? What hardware do I need to purchase?
    I have read the thread on "Digital Connections, SPDIF and Dolby Digital Info", and also I've thoroughly read the "Creative Speaker Connectivity Guide".
    The reason I ask is that I have just bought a pair of Pioneer SE-DIR800C Surround Sound headphones. This are supposedly fantastic for recreating surround sound on headphones because there is a clever little decoder box. They accept a DTS / Dolby Digital signal via the digital co-axial and optical inputs, and there is a single analogue input which only accepts stereo sound.
    My XBox and PS2 will output true digital 5. sound via an optical cable and I am confident this will work perfectly with these headphones. I'm really looking forward to playing Halo in surround sound! But for gaming on my PC, I'll be limited to just an analogue stereo signal. Well, unless I can find some device that will convert my SoundBlaster's analogue 5. outputs into a digital signal, which I can then plug into the little decoder box for these headphones.
    So, back to my question:
    What hardware do I need to buy to convert an analogue 5. signal (via 6 x RCA or 3 x 3.5mm stereo ) into a true digital signal (via optical or co-axial SP/DIF)? Is it some type of headphone amplifier I need? If possible, please recommend makes & models of equipment.

    Thanks stefan
    OK, basically I have found 3 options for getting digital 5. out of a PC:
    a) Creative DTS-60 (approx $90). This converts the SB's analogue into digital, but it's not available in the UK and it also introduces a noticeable 50ms sound delay. Also, who wants an extra box hanging out of their PC?
    b) Buy a new sound card which has Dolby Digital Li've output. For example, ) BlueGears HDA X Mystique 7., or 2) Turtle Beach Montego DDL, or 3) Terratec Aureon 7. PCI (NOT the Space, FireWire or Uni'verse cards). I couldn't find the first two available in the UK so I have just ordered the Terratec card from Komplett.
    c) Buy a new motherboard that has built-in Dolby Digital Li've output, for example the ABIT Fatalty AA8XE. Unfortunately my PC is only just over year old and I'm not quite ready to replace it.
    I hope this info is useful for people. Maybe Creative will start making a card with DDL output too.Message Edited by NinjaHeretic on 2-22-2005 08:46 AM

  • How to check 6 digital signals change value at the same time with PCI-6229??

    I am using DAQ card PCI-6229.
    Channel 1 generate a digital signal.
    Channel 2,3,4,5,6,7 acquire digital signals.
    I want to check:
    1. Whether the rising edge of Channel 2,3,4,5,6,7 occures at the same time;
    2. The time delay from the rising edge of Channel 1 to the rising edge of Channel 2,3,4,5,6,7 is within a certain range.
    I know I can use counter to get the two edge seperation time delay. But I only have two counter, it is two time-consuming if I check one by one.
    I don't know how to check the rising edge of 6 different channels occure at the same time.
    Does anyone has any suggestions?
    Thanks

    Hello,
    You can use the DAQ card's digital input change detection circuitry to detect changes in the input, you can then use a counter to measure the relative time between samples. Please read Page 6-9 DI Change Detection Applications for more information. Let me know if this helps
    Christian A
    National Instruments
    Applications Engineer

  • My daq 6008 wil not drop the 5V after the VI is stopped, i have a digital signal going from the error out on the daq in the while loop to the error in on the daq outside the while loop and a boolean going to the data of the daq outside

    my daq 6008 wil not drop the 5V on a digital output after the VI is stopped, i have a digital signal going from the error out on the daq in the while loop to the error in on the daq outside the while loop and a boolean going to the data of the daq outside, but i can t seemto get it to work

    i attached the block diagram so you can have a look
    Attachments:
    PID Temp control.docx ‏120 KB

  • How to convert digital signal to analog

    Hi..
    I am using NI 9375 (DIO module) to read the output from flow sensor.
    The output of the flow sensor is in the digital signal.(Boolean=True/False).
    How can I convert the digital signal to the analog to get the reading of the flow sensor?
    I had tried before to convert the digital signal to the frequency so that I can make the conversion from frequency to the flowsensor reading,
    but it doesn't work.( I am referring to http://www.ni.com/white-paper/14549/en/ ).

    nhan91213 wrote:
    Hi..
    I am using NI 9375 (DIO module) to read the output from flow sensor.
    The output of the flow sensor is in the digital signal.(Boolean=True/False).
    How can I convert the digital signal to the analog to get the reading of the flow sensor?
    I had tried before to convert the digital signal to the frequency so that I can make the conversion from frequency to the flowsensor reading,
    but it doesn't work.( I am referring to http://www.ni.com/white-paper/14549/en/ ).
    FYI - If your flowmeter pulsing frequency is higher than 500Hz then you won't get reliable reading using your algorithm, and it will be very unreliable above 1kHz because fastest that loop runs is 1mS (1kHz).  In that case you could tie the timed loop  to a higher rate (hardware) clock source to go faster than 1mSec loop time.  If no hardware then I think you can use high resolution timer (in LV2014, not sure if it was also available in previous version) and a regular while loop with algorithm modification for a faster timing.
    New Controls & Indicators made using vector graphics & animations? Click below for Pebbles UI

  • How to convert a analog signal to digital signal

    Hello,
    How to convert an analog signal into digital signal such that every sample of analog signal corresponding to 1.2V will be represented as '1' in digital signal and other samples of analog signal(that are not 1.2v) will be represented(converted) as '0' in digital signal.
    And how to display both wavefroms or signals in graph indicators.
    Thanks.
    Solved!
    Go to Solution.

    If you have 1000 samples, and you want to convert to digital, you are going to get 1000 digital values.  Attached is what I mean.
    Unofficial Forum Rules and Guidelines - Hooovahh - LabVIEW Overlord
    If 10 out of 10 experts in any field say something is bad, you should probably take their opinion seriously.
    Attachments:
    Analog_to_Digital Hooovahh Edit.vi ‏52 KB

  • Is the lightning adapter also pass trough the digital signal? Or only the analog?

    I want to order a arcam dr dock. I am not sure, that it will work with the lightning adapter because it has only the 30 pin adapter and it will need the digital signal...

    In the meantime I can reply my question by my own. The lightning connector pass also the digital signal trough.
    So my new Arcam DrDock is working with new I Pad (4) with lightning adapter.

  • Can we design analog to digital signal conversion block diagram (ADC) in labview

    hi every one,i've doubt i.e can we convert function generator output (i.e analog signals) to digital signal in labview......can anyone help me how to create ADC circuit that means ADC Block Diagram in LABVIEW.....please give me solutions for my problem

    Hi guru,
    from signal generation VIs you get arrays containing float values (aka DBL). Those floats are just digital values made of 0s and 1s…
    Any value in your computer is digital!
    To provide a solution you need to rephrase your question! What exactly do you expect as result of your operation?
    Edit: kkkkkkk ur ckt ???
    Best regards,
    GerdW
    CLAD, using 2009SP1 + LV2011SP1 + LV2014SP1 on WinXP+Win7+cRIO
    Kudos are welcome

  • Counter Output as Sample Clock of Digital Signals

    I have a situation where I need to use a hardware counter as sample clock of digital output signals.
    How do you specify the "Counter Internal Output" signal as a sample clock of digital output?
    I want to do something like this:
      // Create counter task
      CNiDAQmxTask m_Task(_T("ATask"));
      m_Task.COChannels.CreatePulseChannelTicks(_T("Dev1/ctr0"), "", _T("20MHzTimebase"), DAQmxCOPulseIdleStateLow, 0, 10, 10);
      m_Task.Triggers.StartTrigger.ConfigureDigitalEdgeTrigger("PFI0", DAQmxDigitalEdgeStartTriggerEdgeRising);
      // Create digital output task                     
      CNiDAQmxTask m_Task2(_T("ATask2"));
      m_Task2.DOChannels.CreateChannel("Dev1/port0/line0", "", DAQmxOneChannelForAllLines);
      m_Task2.Timing.ConfigureSampleClock("XXXXXX", 0, DAQmxSampleClockActiveEdgeRising, DAQmxSampleQuantityModeFiniteSamples, 400);
    How do I specificy "counter 0 Internal Output signal" instead of "XXXXXX" above, i.e. the sample clock of the digital output signal. Can't find the name of the signal anywhere in the documentation and help files. I have a 6259 DAQ board. 
    /pek

    Thank you for your answers, but I can't get it to work.
    When I use "ai/SampleClock" as sample clock everything works correct. When I try to use a counter as sample clock the task completes imediately, before any digital signals has been sent/measured. The task even completes before I have started the trigger, which is very confusing. No error appears.
    I think that something is wrong about how I setup the counter. I use the code below:
    // Create counter task
    CNiDAQmxTask m_Task(_T("ATask"));
    m_Task.COChannels.CreatePulseChannelTicks(_T("Dev1/ctr0"), "", _T("20MHzTimebase"), DAQmxCOPulseIdleStateLow, 0, 100, 100);
    m_Task.Triggers.StartTrigger.ConfigureDigitalEdgeTrigger("PFI0", DAQmxDigitalEdgeStartTriggerEdgeRising);
    // Create digital output task
    // The code below works with "ai/SampleClock" as sample clock
    CNiDAQmxTask m_Task3(_T("ATask3"));
    m_Task3.DOChannels.CreateChannel("Dev1/port0/line0", "", DAQmxOneChannelForAllLines);
    m_Task3.Timing.ConfigureSampleClock("Dev1/Ctr0InternalOutput" /*"ai/SampleClock"*/, 0, DAQmxSampleClockActiveEdgeRising, DAQmxSampleQuantityModeFiniteSamples, 400);
    // Create samples
    CNiUInt32Vector ui_data;
    for(int i = 0; i < 200; i++)
      for(unsigned int j = 0; j < 2; j++)
        ui_data.Append(j);
    // Create digital writer
    CNiDAQmxDigitalSingleChannelWriter m_writer3(m_Task3.Stream);
    m_writer3.WriteMultiSamplePortAsync(true, ui_data);
    // Wait until task completes
    m_Task3.WaitUntilDone(-1);

  • DIGITAL SIGNAL GENERATION

    Hi!
    I want to generate a digital signal (0-5V) in order to turn on and off an hydraulic pump. The time on (high) and time off (low) are specified by a MatLab code, so that once the pulse has finished one cycle, the program should be go again to MatLab code and take two times again. Then it should generate the signal again.
    Thank you for the help.
    Miguel

    Thanks for the reply.
    I have a system with an hydraulic pump, power supply, transistor and computer. I would like to send a digital pulse from my computer (0-5V) to the transistor. The transistor then closes a circuit (power supply and pump), and the pump starts running.
    Then, I would like that each sample (each pulse) has specific width (time on), and also specific time off before it starts with other sample. These times (time on and time off) are computed by a MatLab code.
    I'm working with DAQmx drivers and I also have a BNC 2110.
    I also attach my code in Labview that I am trying to modify.
    Thanks a lot.
    Regards,
    Miguel
    Attachments:
    Gen Dig Pulse Train-Finite_original.vi ‏22 KB

  • Measure Frequency of Digital Signal from DAQ-Board

    I'm using a National Instruments DAQ board and I need to measure the
    frequency of a digital signal from my data acquisition board.
    I know the measure frequency.vi (In diagram - data acquisition -
    counter), but i don´t understand yours implementation mainly in input
    "counter". Because i don't understand the relationship of board channel (for
    signal acquiring ) and the measure frequency.vi.
    Thanks in advance,
    [email protected]

    Hi,
       Attached is a vi which models your signal, and provides a way to measure the average frequency over a window of time. It converts the signal to a sequence of periods. I usually start with this approach because you can save the data in a much more compact form if your sampling rate is high. Obviously over a specified period of time, if there are no zero crossings the frequency is zero, so I was a little incoherent before. The real issue is the latency caused by averaging. Your frequency measurement is most accurate half your window size before the current time, so smaller windows give you more up to date measurements, but also more noisy. If you need the most up to date measurement, then you have to use the time since the last crossing which is the case where the frequency never goes to zero. That's probably not a realistic situation. If you needed less latency, you could use a prediction algorithm.
    Also, there are a number of signal measuring and processing vi's that LV gives you, for instance pulse measurements that could be used to partially implement this or other approaches, but I normally steer clear of them unless they fit exactly due to having to convert back and forth to the waveform data type.
    Have fun!
    Attachments:
    DigRandFreq.png ‏62 KB
    DigitalRandomFreq.vi ‏34 KB