Fieldpoint configuration in MAX

I have an existing system using about a dozen FP-1600 modules with temperature modules FP-TC-120's.
MAX version 3.0.2
In all my legacy configurations the channel list in MAX is: ALL, and then Channels 0 thru Channel 8 with channel 8 being the cold junction reading. (my code parses off the last channel from the data).
We just added another FP-1600 module with another FP-TC-120. In MAX the channel list is now (for this module only) ALL, CJ Temperature, Channel 0 -7.
Also the channel icons are blue whereas all the old setups the channel icons were grey (I realize that the colors are user specific, but I am noting the fact that the new ones are different).
Since my code is expecting the CJC to be last in the list, is there a way for me to redefine this?
Lawrence M. David Jr.
Certified LabVIEW Architect
cell: 516.819.9711
http://www.aleconsultants.com
[email protected]
Attachments:
MAX.jpg ‏93 KB

The Item icons being blue vs. grey is simply an indication that you are actively subscribed and reading the items. When the icon is blue, you will notice that the channel data updates in the data screen. When the icon is grey, you will not see any updates. Note: there is a difference in behavior between the serial and ethernet modules. For the serial modules, when the icons are grey, no communication will be taking place on the serial port, because the serial communications are poll driver. For ethernet, as long as MAX is open, you will have active subscriptions (and ethernet activity) to all channels contained in your IAK file.
The channel names are listed in alphabetical order. You can easily rename the CJ Channel to Channel 8 to make it consistent with your previous code. Simply right-click on the Item and choose rename. However, it should be noted that despite the "different" channel order displayed, if you are reading the All channel in your code, it will still be in the order of Channel 0 through Channel 8 with 8 being the CJC. The display order in MAX does not affect the order of reading the channel.
Regards,
Aaron

Similar Messages

  • Is there a way to print my Fieldpoint configuration information

    Is there a way to print my Fieldpoint configuration information including communication parameters, module types and names, channel input ranges, etc. other than doing a screen dump for each configuration dialog?
    Anton

    Anton,
    Unfortunately I don't know of any other way to get a printout of all the FieldPoint configuration data.  The iak file is binary so you can't print that and a MAX report does not contain all the information.
    I think this would be a great idea for a product suggestion though.
    Regards,
    Simon H
    Applications Engineer
    National Instruments

  • How to Document a FieldPoint Configuration File (*.iak)

    Hello there,
    Is there a quick and easy way to generate a human readable FieldPoint Configuration File?
    I'm documenting an existing system from scratch and I can't see an easy way to do this, apart from captured screen shots from MAX - which is tedious! Perhaps I'm missing something but various PLC tools I've used in the past, have made this process very easy.
    Regards,
    ChromaBurst

    There is not a method to see the bit masks of the channels outside of Measurement & Automation Explorer, however, using the FP Get Configuration Info.vi you have the ability to see the item list.  I agree it would be nice to see more details of the .iak file in LabVIEW.  I will file a product suggestion for this, and if you would like to also file one follow the following link and select "Product Feedback":
    http://digital.ni.com/applications/psc.nsf/default?OpenForm&temp1=&node=
    Cheers!
    -Bob

  • Some questions about configuration in MAX.

    Hello,everyone!
    I have some questions about configuration in MAX(I am a jackaroo for motion control development),I hope I can get your help.
    I use PCI-7344+UMI-7764+Servo amplifier+Servo motor,my MAX version is 4.2 and I use NI-Motion7.5
    My question as following:
    1,In Axis Configuration,for motor type,why I must select stepper but not servo?my motor is servo motor!If I select Servo,my motor can't run,I don't know why.
     If I select stepper,though motor can work but I can't test encoder in MAX.
    2,In Stepper settings,for stepper loop mode,why I must select open-loop but not close-loop?If I select close-loop,the servo motor doesn't work too.
    3,If I want my two servo motors run at different velocity,How shoud I do?It seems I just can set the same velocity in MAX for my two servo motors.
     My English is poor,Pls pardon me!I come from China.
    Thank you for your help!
    EnquanLi
    Striving is without limit!

    Hi,Jochen,
    Thank you for your kindly help!
    The manufacturer of the drive and motor that I am using now is Japan SANYO DENKI,drive type is RS1A01AA,motor type is R2AA06020FXP00.
    And I use position control mode,thehe encoder's counts per revolution is 131072.I set the electronic gear ratio to 1:1 for drive.
    Now,I can use Close-Loop to control the motor but still has some problems.When I configure it to run in closed loop mode, the motors behave strangely and never move to the target position.When I configure it to run in closed loop mode, the motors behave strangely and never move to the target position.The detail situation is as following
    1,Motor can't run.
    2, Or motor moves to a position, then moves in the same direction agian and eventually stops.
    Except for the  two points mentioned above,"Following Error" is  occured frequently,I don't know why.
    I am still not clear why I must set the motor type be stepper in MAX .
    And I have another question:what the relationship between the steps and the counts?They have the proportion relations?I notice that there are a section said like this in help document: For proper closed-loop and p-command operation, steps per revolution/counts per revolution must be in the range of 1/32,767 < steps/counts < 32,767. An incorrect counts to steps ratio can result in failure to reach the target position and erroneous closed-loop stepper operation.
    I am verry sorry I have too many questions!
    I am very appreciate for your kingly help!Thanks again!
    EnquanLi
    China
    Striving is without limit!

  • Compact RIO NI-9082 Configuration in MAX Unable to Save

    Hi everyone,
    I've been trying to set up a new cRIO the NI-9082. Currently, I am able to see the cRIO under 'Remote Devices' in MAX and view configurations. However, two errors are occurring:
    1). When I try to change setting such as hostname and press 'save' a warning pops up saying "There was a problem saving the settings to the target. Make sure your hardware is powered on and hat it is connected to the network". I've attached an image below.
    2). At the same time, when I try to install software onto the cRIO by right-clicking 'software' and selecting 'add/remove software' and run the 'LabVIEW Real-Time Software Wizard', another error pops up: "Error: the harddrive n the remote system is either full or encountered an I/O error." I've also attached an image below.
    The cRIO is powered on with 'DISABLE RT' toggled OFF. It is connected to the network via an Ethernet cable. This connection looks fine however I look at it. (The Ethernet port connection light is flashing continuously indication activity etc.) It is from the PC which is connected to the same network, that I am trying to interface with the cRIO. The cRIO displays the correct IP address assigned through the network.
    Apologies if I haven't supplied sufficient information to solve this problem, but if anyone might be able to explain why I might be encountering these two problems under these circumstances, help would be extremely appreciated. Thanks!
    Solved!
    Go to Solution.
    Attachments:
    cRIoConfigProblem.JPG ‏229 KB
    MAXsoftwareInstallError.JPG ‏26 KB

    Hi Craig,
    Thank you for your reply! The firewall was an initial issue, so I had asked an administrator to disable it. This allowed me to proceed to my current stage where I am able to see the cRIO and its configurations in MAX; but encounter the problems mentioned in my main post. At least, I think its been disabled. In the attached FirewallOFF.JPG, everything does look turned off. However, in the attached FirewallMAXUnticked.JPG, MAX is not 'ticked' as an 'allowed program'; but when I proceed to add it, the error message shown pops up confirming MAX is already on the list of exceptions. If the firewall isn't the problem, do you have any other ideas what might be? 
    Regards,
    Ya-Wei.
    Attachments:
    FirewallOFF.JPG ‏110 KB
    FirewallMAXUnticked.JPG ‏108 KB

  • How can I export my configuration from MAX to another automation system through NI-DAQmx

    Hi,
    has someone of you an idea how i can export my configuration from MAX to another automation system through NI-DAQmx?
    We created a dll for the communication between the AUSY (not LabVIEW) and NI-DAQmx. The export file .nce is not in ascii format, so we can't use it or is there a way of solving our problem with it?
    Thanks for helping me
    Eddy

    I recently came across this, does it help at all?
    http://sine.ni.com/apps/we/niepd_web_display.display_epd4?p_guid=B45EACE3E7E556A4E034080020E74861
    ~~~~~~~~~~~~~~~~~~~~~~~~~~
    "It’s the questions that drive us.”
    ~~~~~~~~~~~~~~~~~~~~~~~~~~

  • Self Reading FieldPoint Configuration

    I have multiple compact FieldPoints configured all the same, and I want to create an application that is generic to install on each cFP-2020. How can program it to read it's own config information in order to read it's own module data?

    Jordan,
    When a FieldPoint RT controller is configured, a file named fpbank.ini is downloaded into the module. The fpbank.ini file contains the names of the devices (modules) and items (channels). If you examine the file, you should be able to determine what type of module is at what location. This file will only provide names, it does not contain the information on how any given channel is configured. However, this should be sufficient for your purposes. I must point out that NI does not provide any sort of guarentees that they will not change the file format in future firmware revisions, so you may need to periodically change your code when NI releases updates, but my personal opinion is that the file format is probably not going to change very much ove
    r time.
    Regards,
    Aaron

  • How to configure a compact Fielpoint to time server IP (LabVIEW 2013, cFP-2220, NI Fieldpoint 6.1, MAX 5.5.1)?

    Hi all,
    in old MAX versions there was a field, where one can type a time server computer's IP number to synchronize a Fieldpoint controller. How I can perform that in new environment? I can't find it neither in MAX, nor in system configuration.
    Thank you,
    Armen

    Hi Armen,
    I have suggested the following to one of my customers who had brought this up.
    The Time Server option will not be available in MAX 5.5, but may be readded in the future versions. But, there is a work around for this, where you can set the IP address of the Time Server to the cFP.
    1. Open Windows Explorer>>Type ftp:\\10.X.X.X (IP address of the cFP) in the address field >>Enter. This will open a window that displays the files on the cFP.
    2. Now, you will find ni-rt.ini file here, copy and paste it on your PC desktop.
    3. Open this ini file on the desktop using notepad and you will find Time_Server=10.0.0.1. So, change this to the IP address of the Time Server that you will be assigning. Save and close the ini file and copy and replace it in the cFP files, where you originally copied it from.
    4. Restart the cFP by right click the cFP in MAX>>Restart.
    5. Now, the cFP has been assigned the Time Server.
    6. Start the NI Time Service on your PC by following the information in the Help Tab in MAX>>Remote Systems>>select cFP detected.
    I have confirmed that the Time Server has been assigned to the cFP.
    Firstly, I did the above procedure and set the Time Server using my PC, which has MAX 5.5.
    Then, I have a Test PC with old MAX 4.6 and related cFP drivers. Here, when I opened the detected cFP I can see the Time Server under the Network Settings Tab, which was configured with the IP address I have set in the ini file. So, this proves that this works.
    So, kindly try the above and see if this helps to resolve the issue you are observing.
    MK

  • Having problems configuring and testing FieldPoint modules with MAX 3.0.

    I have a FP-1000 and FP-AO-200 connected together. MAX is able to find the FP-1000 and communicate with it. The FP-AO-200 POWER and READY lights are on.
    MAX does not find the FP-AO-200 when I invoke "Find Devices". I can manually define it using "Create New Device". When I attempt to test a FP-AO-200 channel using the Write function in "Items Configuration" I get the following error message: "The module or item addressed does not exist".
    I am also not able to write to any FP-AO-200 channels in LabVIEW 7.0.
    Any ideas what is wrong?

    I would check the pins on the FP-1000, between the modules for bent or pushed in pins. Then, I would make sure the AO module is seated correctly in the Terminal Base.
    If that's not it, try a different AO module and/or a different TB, to see which is the culprit. The AO module should show up when you do "Find Devices".

  • Modifying fieldpoint configuration in labview

    I try to solve a problem and up to now do not find any solution, could somebody help??
    I have an application working with fieldpoint module (one ethernet head FP-1601 with io modules FP-AI-100, FP-AO-210, FP-DI-300 and FP-RLY-420) this application is supposed to work on different machine (AI and AO range are differents) so I'm trying to find how to dinamically inside my application change the range of AI and AO as we normally set this in MAX.
    If this is not possible, could it be possible from inside the application to manage a set of different IAK files, those will be then pre-created with MAX for the differents machine?
    Thanks for any help!

    Changing the input configuration programmatically, thought if current or
    voltage input and ranges etc., isn't possible
    with the normal FieldPoint VI's in LabVIEW. These settings can only be
    altered and saved with the IAK- file, which needs to be available, when
    you try to connect to the FieldPoint System via Server (this is done at
    latest when you call the first FieldPoint VI). Some other
    attributes can be changed programmatically by creating a specific item.(How Can I Programmatically Change Configurations of a FieldPoint Module?   http://digital.ni.com/public.nsf/websearch/960F6F90436A1A1A86256FBA0062E463?OpenDocument) Which items these are, is specific to the FP- module.
    If your are familiar with FieldPoint programming using Datasocket, then
    you are able to change channel ranges programmatically (you don't need
    an IAK- File for that)
    Introduction to Using DataSocket Commands to Communicate with FieldPoint Ethernet Network Modules:
    http://zone.ni.com/devzone/conceptd.nsf/2d17d611efb58b22862567a9006ffe76/a6617392b393c4b886256acb005...
    Using Advanced DataSocket Commands with FieldPoint Ethernet Network Modules: http://zone.ni.com/devzone/conceptd.nsf/webmain/BE31272F09BBBE1C86256ADC00743576?opendocument#2
    Programmatically Changing the IAK Configuration File Used By Measurement and Automation Explorer?  http://digital.ni.com/public.nsf/websearch/AD7E2B97C60086B886256DDE006FBED2?OpenDocument
    Good luck,
    Stefan
    Impossible is nothing - nothing is impossible

  • Hardware Configuration in MAX when not logged in as Administrator

    I am attempting to load a .cfg file for a VME device through the Hardware Configuration option on MAX.  When you are not logged in as an administrator, the option is greyed out.  I do not have the option of always running this as an administrator.  However, I can set special permissions on certain folders or registry keys if necessary to allow non-administrators access to those locations in order to get the hardware configuration to work in MAX.
    Does anybody know what special permissions would need to be set?

    Hi Pual,
    What operating system are you using? I’m not sure if there are additional specific files or registry keys, but could you give your use full control over the Measurement and Automation Explorer program?  Let me know if you can test that out.
    Matt
    Applications Engineer
    National Instruments

  • Fieldpoint Configuration Not Updating in LV Project

    Using custom scaling.
    Change scaling settings for Channel 2 of cFP-AO-210, Apply, and Save.
    Open LV project.
    Add Targets/Devices
    Let project autodetect existing devices.
    Once found and loaded, open AO Channel 2 properties and look at scaling.
    They are the default settings, not my changed values.
    What's up with that?
    I am not saving to a different IAK file and reading the wrong one;  at least not intentionally.
    Just letting LV do its thing
    Does the field point data have to find its way to the cFP-2100 controller before this will work?

    Hey Wes
    So I'm kinda jumping in during the middle of your conversation here, but as I read back through the forum I have a number of questions. I know that you have configured your FP items in max with the scaling you want. I assume that you changed the individual channels on your AO, not the "all". You save your IAK file, and it successfully downloads to your controller. You then open LabVIEW, create a new project and import the IAK file. My first question is:
    Do you see the custom scale you created if you right click on the channel of interest in the project, go to properties and then look at the custom scaling tab? (Again, I assume you're not using the "all" channel).
    If not, I was able to have some luck scaling directly from the project instead of using MAX. So my second question is:
    Are you able \ willing to create the scales as part of the project instead of through MAX?
    Post back and let us know what you find. Thanks!
    Chris C
    Message Edited by Chris_C. on 03-05-2007 11:13 AM
    Chris Cilino
    National Instruments
    LabVIEW Product Marketing Manager
    Certified LabVIEW Architect

  • Missing IVI configuration in MAX

    Could somebody please enlighten me as to the specific combination of spells, incantations, gestures, and begging that will get the IVI configuration sub-tree to appear in NI-MAX?
    It has disappeared on me. Usually, I can reinstall stuff (MAX, the IVI Engine, etc) in various orders and eventually get it back again. But I seem to have lost the magic touch now.
    I swear to God, as soon as I find a few spare cycles, this whole IVI thing is out the window. It's just not worth the hassle. I can write my own instrument drivers. It's really not that hard.
    - Ron

    I'm running MAX 3.0.2.3005, which came with NI 488.2 2.20 (the last version I can find that doesn't have the new MAX.) I'm trying to recreate the configuration that I had working before. In particular, I'm trying to avoid the new IVI Compliance Package, because I know it doesn't let me set the voltage attribute on a power supply using the TestStand IVI Tools step.
    The file you mention does not exist. Various attempts at installing, removing, reinstalling and repairing NI 488.2 and IVI Engine 1.83 don't seem to create it. But there is no error message to report. Actually, the entire IVI Engine is apparently not being installed. Programs that use the IVI engine can't find it either.

  • Renishaw RGH24 Reference Mark Configuration in MAX?

    Hi,
    I am currently working on a dual-axis system, using two Renishaw RGH24 series readheads (one on each axis). The encoders are wired so as to output A+/A- B+/B- I+/I- and are powered with 5V and GND, all via a UMI-7764. The controlling card is a PXI-7350.
    The system is tuned and running well, but there is no specific "Home" or "Limit" output available from the readhead. I have fitted Renishaw adjustable "Reference Markers" to the system, and the encoders flash red when traversing the sensor, meaning they are "seeing" it.
    The problem I have is getting this information back into MAX, and subsequently LabView.
    Is it possible to configure MAX to use the I+/I- line as a "Home" reference, which, changes state as the readheads traverses the sensor?
    Regards,
    Laurence

    Let's try again!
    If this doesn't work I'll insert the web addresses to the Renishaw page where they can be downloaded...
    L
    Attachments:
    RGH24 Data Sheet3.pdf ‏143 KB
    RGH24 Installation Guide2.pdf ‏805 KB

  • Scale Type of DAQ virtual channels configured using MAX

    I configured some analogue input and output channels using Measurement & Automation Explorer, under Data Neighborhood. One of the attributes I could change is called "Scale Type". I'm wondering what it's for, or where I can find information about it. Thanks

    Amyz,
    The most helpful document I found was the DAQ Channel Wizard Tutorial: http://www.ni.com/support/labview/toolkits/chanwiz​/. Step 7 of analog input or output briefly describe the scale modes. Good luck with your application.

Maybe you are looking for

  • I want other fields of table bkpf in T-code FB03

    hi expert. i want other fields of table bkpf in T-code FB03 so i tried to find setting in spro(img) , but i couldn't find that. where is the that?  help me please..

  • Can Squiggly be used in Flash CS5?

    If the answer is yes, can you please provide some info on how to go about it. Thank you.

  • Attachments through presentations

    Hi, I needed to be able to attach files to an instance using presentations instead of the regular workspace attachments capability. After some research I found that ALBPM 5.7 had an example of something like this called FileChooserTest so I tried to

  • What is new features of iPhone software 1.1.4?

    I have 1.1.3 on my iPhone. I checked apple site and didn't find the new features. Where can I find new features of newer version of iPhone software? And do you recommend to update with newer version of software all the time it is newly available? Tha

  • BOE Metadata Integrator not collecting metadata from specified folder

    Dear All, I'm trying to schedule BOE metadata integrator job to collect metadata from BI4.0 SP4 server. In the parameters I have specified the sub folder name called Audit Reports. The job completed in 5 minutes but did not collect any metadata from