ABB SattLine OPC

Hi
I have tried to communicate with the ABB SattLine OPC server (ADS.OPC.2 in figure 1).
I can read connect and read/write tags with the Matrikon OPC explorer,
but have problems with labview.
I can see and browse the server however I do receive a message which
says "the server is connected and can be browsed but it will not be possible
to retreive extended item information"...
I can see the tags but when I select the proper tag Labview just shuts down (figure2)
I have no problem can communicate with the same code with MATLAB OPC server
with MAtrikon opc server and the Labview OPC servers (simulators) no problem
at all, just in the case of the Sattline I have thi behavior.
Any comment would be highly appreaciated.
Cheers
Zoltan

Hi,
I still have problem to get arround this thing....No rpogress at all.. but here it is what I did:
1. I found the server explorer on the NI site and installed. I can read/write the data
ABB server (ADS.OPC.2) beutifully, see ( the figure attached).
2. In LAbview 8.0 with DSC 8.0 I tried two things:
2.a -  the same as before. If I try to use any of the OPC examples from the opc.dll
e.g. "Browse to OPC item.vi" I can open the browser, I can see the OPC server
I can even see the group and the tags, but when I click on any of the tags again
Labview crashes with the error message (see the figure). This is the same original problem...
2.b - Now still in Labview 8.0 where I have DSC 8.0 installed I added to a new project
New --> I/O server --> OPC --> and add the ADS.OPC.2 from the list of registered OPC servers and add
as a linrary to the project ( this is fine so far)
But when I right click on the newly added OPC1 and check the View I/O items I cannot see any tags.
(when I dod the same procedure with any other OPC server, e.g. MAtrikon no problem).
The same if I still go ahead an to add new variable I cannot see the tags from the server. Only
the NI OPC CLient Status group appears (which does not belong the the ADS.OPC.2).
3. Finally, I downloaded Labview 8.5. I do not have DSC 8.5 so I only tried method 2.a. That is the simplest
example from the opc.dll crahes Labview.
During all this time I have no problem to communicate in Labview with other simulated opc sertvers,
and at the same time I have no problem reading/writing data to the real ADS.OPC.2 using other
the Matrikon or the NI server Explorer...
I am running out of ideas ...:-(((
Thanks
Zoltan
http://www-staff.lboro.ac.uk/~cgzkn/ABC/errora1.jpg

Similar Messages

  • How to use DSC & OPC with mitsubishi PLC FX2N

    Hi I have  PLC of Mitsubishi FX2N /FX3U
    Communication board is FX 232 BD.
    Data register in PLC  D8120  For serial communication.I want to use this type of PLC with DSC & OPC 8.5 version but, I am not able to communicate this PLC with DSC as I want to use this to control hydraulic test stands.Also guide how I can use DSC for data acquisitions.Support india is trying this from last 2-3 weeks still they are not able to slove the problem so kindly help asap.
    Regards
    Nitin Badgujar.

    Labview application to Mitsubishi PLC communications, No Mitsubishi PLC OPC Server to communications.all the labview vi write....
    We are finish it
    see at
    http://www.abb-furnace.com/scada-system/labview-mitsubishi-fx2n-plc.html
    [email protected]
    [email protected]
    ==============================================
    Labview Applications Engineering
    Labview SCADA/HMI Systems
    Labview AB Rockwell PLC, Omron PLC,Mitsubishi PLC,Siemens PLC,Fatek PLC,Delta PLC
    Labview Vision, Vision Builder
    Labview Profibus,EtherNet/IP,EtherCAT,DeviceNet,Canopen
    http://www.abb-furnace.com/scada-system/scada-system.html
    ==============================================

  • Hi!! I need help: I'd like to know how to obtain a communicaion between a PLC of ABB model 07 KT 97 and Labview 8.

    Hi!! I need help: I'd like to know how to obtain a communicaion between a PLC of ABB model 07 KT 97 and Labview 8.I have to realize a scada system to control an electrical implant.I think that I need to learn more about OPC server: do you have some manual and tutorial to help me step by step in this configuration?And do you have some examples (one time PLC is connected and well configurated) to realize communication with Labview software?
    thank you so much!!
    please!!!Answer soon because I need help!!!

    Hi Leoeffe,
    I've found some documents that cam help you to understand how is possible to communicate
    unsing OPC Servers and ho use them in Labview 8.
    First of all I suggest to take a look to these documents:
    How Do I Use OPC in LabVIEW?
    http://digital.ni.com/public.nsf/websearch/EA15F53DB6FECCA5862567240064DF09?OpenDocument
    Connecting LabVIEW to an OPC Server through a DataSocket Connection
    http://zone.ni.com/devzone/conceptd.nsf/webmain/DF8C0A4BA2E2B22A86256A3700592BEA
    Using the LabVIEW Shared Variable
    http://zone.ni.com/devzone/conceptd.nsf/webmain/5b4c3cc1b2ad10ba862570f2007569ef
    You can also use the Labview DSC module:
    Developing Monitoring Applications with the LabVIEW DSC Module for Control Systems
    http://zone.ni.com/devzone/conceptd.nsf/webmain/199c3fb9456a16d986256b5200678917
    LabVIEW 8 DSC Simplifies Distributed Development
    http://zone.ni.com/devzone/conceptd.nsf/webmain/d76c3788a0c4c5668625708b0072987c
    Tools for Troubleshooting OPC Interface Problems
    http://zone.ni.com/devzone/conceptd.nsf/webmain/401CB3A4E216356286256BC7004B5831
    I hope all these tutorials can help you.
    Best regards,
    MarcoL

  • Has anyone done any control of an ABB robot with labview and robotstudi​o?

    I am busy with a piece of test equipment where I need to read data from and send position commands to a ABB robot. This robot uses their new IRC5 controller. I have got their OPC server but I am having difficulty in getting it to respond to the commands I am sending via OPC. I was hoping someone has done this before and can perhaps assist me in getting going.

    Hi,
    I'm trying the solution like your, but communication with  ABB.Robotics.Controllers.dll (. NET) and convert between C# to LabVIEW,
    it was success but i'm not fisnish yet to send position or command to the controller because some class not a public constructors.
    any update please let me know.
    Thank you.
    Attachments:
    ABB_IRC5 Robot Info.vi ‏59 KB

  • LabVIEW & ABB DCS

    Hi wanted to ask if LabVIEW 8.0 and its DSC module can be used to interface with ABB Distributed Control System (DCS) via OPC?
    If possible, anyone could offer any website for reference of information? Thanks.

    HWJ wrote:
    Hi to be more specific, the
    question should be if anyone knows which are the OPC
    servers that supports the ABB DCS systems?
    and is LabVIEW and its module able to program with this OPC server?
    Are there any specific OPC servers that can only be used? or any should do the job? ie SQL?
    I
    would think that the best way to find this out would be to contact ABB
    directly. If they do not have an OPC server for their DCS system then
    things are getting a little hairy I'm afraid. Maybe there are ABB
    partners out there that have developed such a solution if ABB didn't do
    it themselves but then the ABB sales people should know that too and
    they probably are quite willing to tell you if there are such solutions.
    Once you have an OPC server solution for your system LabVIEW DSC will
    simply need to be configured to connect to this server and access the
    tags yuou are interersted in.
    Rolf Kalbermatter
    Rolf Kalbermatter
    CIT Engineering Netherlands
    a division of Test & Measurement Solutions

  • How to read enumerated values from an OPC server via Datasocket

    Hi Labviewers,
    I am using LV8.2 and I am trying to find if it is possible to read enumerations from an OPC server via Datasocket, not just the values.
    I can successfully read a value for an OPC server via Datasocket and I get a value for example 3, is it possible to get the enumeration/string that corresponds to this value i.e. "Open".
    Many thanks in advance
    Dimitris

    Hi Sarah,
    With the input type as variant I get the following response:
    1                                     <-This is the current numeric value of the parameter
    4 Attribute(s):
       'Quality' -> 192
       'TimeHigh' -> 29861723
       'TimeLow' -> -665408304
       'Timestamp' -> 39.238E+3
    With the Input set to         Enum constant I get no values or strings coming back. With the Input set to                Ring constant I just get the numeric value   
    Dimitris   

  • Communication Problem in Mitsubushi PLC A2SH with OPC 4.5.1

    While communicating with Mitsubushi PLC A2SH thru OPC 4.5.1 , it displays time out error , the settings of the Com port of the system is Baud = 9600, Parity = odd
    Data bits = 8 Stop bits = 2, Flow Control = None . The same setting is done in the OPC & Mistubushi PLC Comm protocol. Iam using Labview DSC to communicate with PLC with OPC 4.5.1. How do i solve this Comm Problem in what steps.

    You might increase the 'Recieve timeout' from 250ms to some higher values on the object (driver) and you might increase in Options >> Serial Ports... >> Receive Gap from 20 to a bigger value like 50.
    Hope it helps.
    Roland
    PS: I've not tried it with this particular PLC, though.

  • How can i connect LabView to a PLC or Profibus without using OPC?

    I can access data from the PLC or through the Profibus using OPC. Unfortunately is this not fast enough since I need a faster sampling rate. Are there any faster ways to access the PLC data? I’m now using Siemens S7-300 and CP5613 with the driver S7-5613.

    Hi Boris.
    This tip can be very helpful to me, tanks!
    Best regards, Martin

  • Is it possible to query multiple items in a single OPC read?

    I am trying to read several data items at one time via OPC. Is this possible? If so, how? I have tried passing multiple URLs to specific items and a single URL header with multiple variable names. Both methods return an OPC error about invalid items. I am trying to do this to speed up OPC access times. Reading each item one-at-a-time is a little time consuming for our application.

    The only way to read multiple datapoints via OPC is to build an OPC item that contains multiple pieces of information. I checked this here, and I had no problem reading an array of data from an OPC Server with DataSocket.
    I read the "opc:/Matrikon.OPC.Simulation/Random.ArrayOfReal8" data item from a Matrikon OPC Simulation Server that publishes an array data item. The OPC Demo server is available for free download at http://www.matrikon.com/opc/htdocs/simx.htm. You can read this as an array of doubles in LabVIEW.
    For your application all you will need to read your data multiple items at a time is a server that can publish arrays.
    Hope this helps.

  • Dsc opc shared variables yields Server Failure

    I've been struggling with the transition from DSC 7.1 to 8+ ever since the release of version 8. I use the Allen Bradley OPC server supplied with the DSC module (Industrial Automation OPC Servers v 5.1) to communicate with a PLC 5/30 via Ethernet, or at least I did when I was using 7.1.
    Prior to today I always failed to get the shared variables that were bound to addresses in the OPC server to deploy, usually getting an error number that started with -19. However today I finally got it to deploy by keeping the I/O server and the shared variables in separate libraries within my project. Now that they deploy I find that I am unable to monitor them. I keep getting a Server Failure. I have browsed the forums here heavily, and the documentation all relates to remote OPC, which is not what I'm doing here (OPC client and server are on the same machine). I tried changing the login account for the Variable Engine service anyway, but that doesn't help, so I put it back.
    I have had some luck simply binding my front panel objects to the OPC server addresses using Datasockets, so it appears that my OPC server is working. However, Datasockets is not a viable option for me because there are times when my project needs to write to a large number of addresses in the PLC sequentially, which never works over datasockets (in my experience).
    We have continued to work in version 7.1 because of the challenges of moving to 8+, but since we can no longer purchase DSC runtime licenses for version 7.1 in order to deploy, it seems that we MUST move forward to 8+ or abandon LabVIEW altogether (which is certainly an option).
    For clarification, I am now working with version 8.2 (but I've been fighting with it since 8.0 without much success). If anybody out there can think of a critical step that I might have missed that might cause this, or if there is a known solution, I could really use (and would greatly appreciate) the help. Thanks!

    Nobody out there seems to have any answers for this, so I kept pounding on it (and pulling my hair out). In the end I finally succeeded in getting one of my old 7.1 DSC projects to run on 8.2. Here's what I did:
    1. I begin with a fresh installation of Windows. I tested it with both 2000 and XP Pro. Vista RC1 will absolutely NOT work!
    2. Install LabVIEW 8.2, DSC 8.2, and just the OPC server that I need from the IA OPC CD (in my case the Allen Bradley server)
    3. Open the IA OPC server editor, and create a new file with an object in it for my PLC (PLC 5/30, Ethernet in my case)
    4. Save, set it as the startup file
    5. Run LabVIEW, create an empty project
    6. Add an IO server
    7. Launch Multi Variable Editor, load project file created in step 6, and bind one variable to PLC address
    8. Save all. Uncheck auto deploy for the library, and deploy all.
    9. Launch variable monitor, browse to new variable, double click to monitor.
    10. This will ALWAYS fail with "server failure". Don't worry, just exit completely out of LabVIEW.
    11. Stop the Variable Engine service.
    12. Run OPC server editor again, and load up the lpd file from your old project. Modify if needed, save, and set as startup
    13. Start the Variable Engine service again.
    14. Launch LabVIEW
    15. Create a new empty project (I created mine in the same directory as my old 7.1 project resided)
    16. Add an IO server, and uncheck auto deploy for its library
    17. Save all
    18. Run Tools->DSC->Migrate->import scf
    19. Convert your old SCF file
    20. Add the new library to your project (it will be named LabVIEW)
    21. Uncheck auto deploy for the "LabVIEW" library you just added
    22. Right click on the "LabVIEW" library and do deploy all
    23. Save, and open the variable monitor
    24. Browse to a tag in the LabVIEW library, and double click
    25. This time it will actually monitor the variable, with a status of "Good"
    26. Now you can add your main front panel VI to your project, open it and run it
    27. Version 8.2 will select the proper legacy tag read/write VI's, whereas 8.0 does not. The writes however do not work. Replace them with shared variable writes. The reads work fine.
    28. The empty project that you created in step 5 is a throw away. It will never work anyway.
    29. So far the only variables that I can get to work at all are the ones that I import from an scf file, which is a pain, but if I must create all my tags in 7.1 and import them into 8.2 I will (for now). I may try exporting to Excel and copying variables that work in order to get functional new variables, since binding them in the editor does not work.
    I hope this helps anybody else out there struggling with moving to 8+ DSC. I saw a few posts with similar issues, but without ANY answers at all. It's a convoluted solution that doesn't make a lot of sense, but for me it is repeatable.

  • Problems using Modbus TCP accessed by NI OPC Server

    Hi there,
    i'm using NI OPC-Server to access a measurement module. The buildup is quite easy, my system with NI OPC, a modbus gate and there the module connected with RS485.
    There's a thermocouple to provide me some sample data.
    But there's the point. I know, my data is in the Holding Registers and I can access them, but every data type I'm trying doesn't bring my my data out, just any other (sometimes Huge with e34, sometimes very small like e-13...) sorts, i can't understand.
    The type provided by the module should be single precision.
    In Lookout the address used to be is 41000 in Labview it's just 999 and in the "target" OPC-Server I get some values at 401000 but not useful.
    I also get the same results accessing 301000 in different types.
    Read/Write or Read Only is equal.
    I've tried to tell my OPC that the values are Strings, Floats, Words, BCD and all other possible ways OPC offers me, but nothing results in a usable temperature.
    I hope I missed something and you could suggest it.
    Cateros
    Solved!
    Go to Solution.

    Thanks for your reply.
    in LabVIEW I'm using the provided Modbus Libraries. If I unbundle the Holding registers, my value appears at Holding Register [0], I'm type casting it to single and get the sample temperature. (Address 999->unbundle->typecast->value)
    In NI OPC, I'm reading ( [depends on zero based addressing]  300999/301000 equal to 400999/401000) an already typecasted Holding Register [1] compared to LabVIEW (and the value changes in the second or third digit behind the comma and they are changing at the same time). Data type in the tag is float.
     Another disturbing thing is even if I change in the options "using zero-based addressing in registers" my value does not change.
    If I'm reading two addresses close to each other (as you mentioned 401000-401001) I'm getting an unknown data type and no results. How do I read multiple addresses without such errors? And how do I specify a special register to read?
    Scaling should not be the problem, I am having three ways to get my value (FTP-Server on the gate (just a *.dat file with correct type), software the the module manufacturer (while measuring and configuring the module) and LabVIEW(as can be seen above)) .
    Sadly, I have not found any useable modbus documentation about the module (just it can use modbus, you have the registers, you could read/write and fine)
    When I'm adding a second couple to the module, in LabVIEW Values in Holding Register [2] and Holding Register [3] appear and are changing.
    Cateros

  • Lookout OPC Client – Asynchronous I/O and Update Rate serious problems (Sequence of data)

    I am using the Lookout OPCClient driver to connect to AB PLCs (EtherNet/IP protocol) and power measurement equipment (Modbus TCP protocol). The OPC server is the NI OPC Servers. The data that are read out from PLCs and PMs are energy meter readings, energy counters, power, voltage, current, frequency, power factor and el. energy quality measurements (THD). That energy meter readings are being stored in SQL database.
    I am experiencing a serious problem regarding the accuracy of the meter readings. Several times per day, randomly, meter readings are losing the time sequence. For example, sequence is: 167, after few seconds 165, 166.  In other words, present value followed by two previous old values. That generates a serious problem in our application that is expecting a naturally rising sequence of counter values.
    Analyzing further, I isolated the problem to the connection between Lookout OPCClient and OPC Server. I made a simple application in Lookout 6.7 (opcproc.lkp, attached) with OPCClient parameters: NIOPCServers, OPC2, Asynchronus I/O, Update rate: 10000, Deadband: 0.0, that is reading just one tag from NI OPC Servers demo application (simdemo.opf).
    By using OPC diagnostic tool from NI OPC Servers I record the sequence of OPC requests and responses.  I found out that OPCClient sends every 2.5 sec “IOPCAsyncIO2::Refresh2()” call that is request for refreshing of all items in one OPC group. Few milliseconds later OPC Sever responds with callback function “IOPCDataCallback:: OnDataChange()(Device Refresh)” that actually refresh the data.
    This periodic sequence is intrinsic to the OPCClient and cannot be disabled or changed (by my knowledge).  This sequence is periodically interrupted by “IOPCDataCallback:: OnDataChange()” caused by update rate parameter of OPCClient (client is subscribed to server for periodic update of changed items).
    In the case of demo application on every 4 refresh callbacks caused by refresh requests (2.5 sec) there is one update subscription callback determined by Update rate (10 sec).
    QUESTION 1:
    What is the purpose of update sequence and update rate when we have every 2.5 sec fresh values?
    PROBLEM
    The problem arises when we have a large number of items in OPC group. In that case the OPC Server starts to queue refresh requests because they cannot be fulfilled in 2.5 sec time because of large number of I/O points that must be scanned. At the same time update subscription callbacks are running at the period determined by Update rate. I observed in my production system that regular update callbacks has higher priority than refresh callbacks from the queue. That causes the loosing of timed sequence of data. After the update callback with fresh data, sometimes follow one or two refresh callbacks from queue with old (invalid) data. By adjusting Update rate parameter (1 hour, 2hours …) I can postpone the collision of data refreshes but I cannot eliminate it. Furthermore, the 2.5 sec automatic refresh are large burden for systems with many I/O points.
    QUESTION 2:
    Is there a way to disable automatic refresh request every 2.5 sec and just use update requests determined by Update rate?
    QUESTION 3:
    Is there a way (or parameter) to change the period of automatic refresh (2.5 sec)?
    This problem is discovered for Lookout 6.5, 6.6 and 6.7 so I could say it is intrinsic to OPCClient. If I use synchronous I/O requests there is not an automatic refresh, but that is not an option for large systems.
    Thanks!
    Alan Vrana
    System engineer
    SCADA Projekt d.o.o.
    Picmanova 2
    10000 ZAGREB
    CROATIA
    T +385 1 6622230
    F +385 1 6683463
    e-mail [email protected]
    Alan Vrana
    SCADA Projekt d.o.o.
    ZAGREB, Croatia
    Attachments:
    opcproc.zip ‏4 KB

    The physical connection from LV to the switch is (I believe) copper crossover to fiber converter into a switch.  Then, fiber from the switch to the end device (relay).  The relay has all of the typical modbus registries and has been verified by inducing signals in to the system and measured/polled in LabVIEW and observed Variable Monitor.  I am working with LV 8.2 and 8.5. 
    An OPC server would only add an additional translation of addressing within the configuration.  The only real draw back would be the network overhead required to do this processing and not being representative of the end design configuration.
    I will reiterated my question in another way:
    I must answer the question to management that relates to data collection, test results and analysis; how often are you polling the client in relation to the outcomes measured?  At this time I can not point at any configuration in the set up and execution that directs the data framing rate.  I only measure the traffic and work with results.  This needs to be clearly identified based on the relay modbus/tcp design capability of supporting an fixed number of client requests per second. 
    For testing purposes, I would like to be able to stress the system to failure and have prove capabilities with measured data.  The present problem is that I have no basis to establish varying polling rates that effect the measured data transmission. 
    This raises another question.  What handles the Variable Monitor data requests and how is this rate determined?
    Thanks for your interest in my efforts.
    Steve

  • DSC - OPC Connection - Can't read or write to tags

    I am working on controlling some motors over an OPC server.
    The PLC is an M258, and the OPC server is CoDeSyS OPC DA.
    When I use MatrikonExplorer, I can read the value of tags, and change their values as needed.
    Using an evaluation version of NI OPC client, I could see the tags, but their value was marked as "unknown" with bad quality. In their properties, the value of the tags is given as "BAD VARTYPE".
    I used DSC to add the codesys server to a library and imported all the relevant variables. When I try to read them in a VI, they give me error code: -1950679034, so that they have no value. And when I try to change a value, I can see that the value never changes.
    I would greatly appreciate any help you can provide.

    http://www.ni.com/white-paper/6417/en/
    Codesys isn't listed as a supported OPC Server.

  • OPC: what is the path to follow in LabVIEW 8.20?

    Hello:
    I started with OPC in Labview 6. The only two functions that I need is "read  multiple tags" and "write tag". The tags are either located on the same PC or on a different one. I use Labview as an OPC client. The number of tags that i need to acquire is in the range of 2000-5000, once per minute. In Labview 6 and 7, all experts in the discussion forum and at NI said that above 100 tags, it was impossible to use Datasocket (performance issue when too many tags) and that the preferred path had to be DSC. So I started using DSC. Now that I migrated towards LabVIEW 8.20 the people at NI say that the best option is to use.... Datasockets! The read/write tags vi having  disappeared the suggest me to make my own "read multiple tags.vi" and "write tag.vi" by encapsulating a "DS read/ write" in a for loop. As an entry to the loop, I would just wire the ref number that the connection ids that the Datasocket Open.vi supplies.
    So my first question: why is this old Datasocket mechanism again the path to follow in Labview 8.20?
    By curiosity I checked in Labview 8.20 what was embodied in the "read multiple tags.vi" that were shipped in the Labview DSC 7.1. And found that the very last layer of the Vi used... Datasocket read in a for loop.
    So my second question: why was the Datasocket mechanism so poor in Labview 6 and 7 (for more than 100 tags) and now is the preferred way to go?
    I cannot use the shared variable mechanism in my case because the entry of my application is a list of tags (2000-5000) to read and I just want an automated way to read these tags values in one take.
    As I need to install the compiled application on dozens of PC I would prefer not to be forced to buy the DSC licenses on each runtime machine hence Datasocket that does not require the DSC license might be a good choice?
    Thanks for all ideas and comments,
    Christophe

    I have an example of a DSC application in this thread. This is in DSC 7.0 format.
    http://forums.ni.com/ni/board/message?board.id=170&message.id=234478#M234478
    Here is the scf file. It might have some stuff added to it since the llb file was created.
    Attachments:
    d103210.zip ‏3 KB

  • Help Needed in establishing connection between Kepware OPC server and UDS 4

    Hi All,
    I am in the process of establishing connection between Kepware OPC server and UDS 4.0,
    Can anyone guide me through the process of configuring UDS 4.0 to establish conection with the Kepware.
    Any standard documentation on UDS 4.0 will be of great help.
    Thanks in advance,
    Shyam

    HI Rajesh,
    I am creating OPC DA instance and when i try to browse for the OPC servers available in the machine, the list is blank. i am not able to view any OPC servers.
    Actuallt the Kepware OPC server and UDS are installed in the same machine.
    Can you plz through some ligh on this
    Regards,
    SHyam

Maybe you are looking for

  • Release Value Contract Report

    Hi, As we can get individual customer released value contract amount through T Code VA43 and report Via T code Z_XX_SD_059 for mass customers which is usually not giving the correct amount of released from value contract. The report which is extracte

  • SSD Boot Drive for Mac Pro

    Apologies in advance, I'm really not great with this sort ofstuff. Basically, what I would like to do is add an SSD to my MacPro and use that as my boot drive.  Ihave a 1TB HDD which is currently doing everything but I'd like to use thispurely to sto

  • Remapping Macintosh keyboard for use with XP?

    Hi all, I am using a KVM to share my monitor, mouse, and standard white Mac keyboard between the G5 and a Windows XP machine. Been trying to find a simple means of remapping the keys in XP so that things like @ and " are swapped, amongst others. I've

  • Do we have to create indexes on ODS if we report on ODS

    Hello all, I have a report that runs on infocube and then there are RRI from this report to detailed report which run on 3 other ODS. So do i have to create indexes on ODS as well to improve performance? Also if we have to create indexon ODS how do w

  • Incident management error: You are not assigned a Business Partner

    Hi I am facing a problem while creating message as below error: You are not assigned a Business Partner I created the BP. which has clear identification too. Even this BP is maintained as Employee too. Expecting ur valuable suggestions. Regards, Siva