Hai,
I am using Industrial automation server with pci 485/2 card to interface
with Mitsubishi plc with RS485 communication module. I have done the communciation
format setup in plc using laddar diagram. But when I use Industrial automation
server explorer to check its not displaying any value all items are displayed
as bad value.
Then instead of connecting through the PCI 485/2 interface card, I converted
the rs485 informations from plc to rs232 using rs485 to rs232 converter.
Now the Value gets displayed but it doesn,t last long, after some time the
value disappers and once again the same bad value gets displayed.
Any suggestions
Thanks in advance,
S.Saravanan

The IA OPC Server is a package of a lot of OPC Servers. If none supports your PLC, you have to use other OPC Server. You cannot add one to IA OPC Server. It can't be upgraded.
NI recently released DSC 8.5 module for LabVIEW. In this module, there is a new OPC server called "NI OPC Server". Here is the list of all the PLCs it supports. http://zone.ni.com/devzone/cda/tut/p/id/6417
It seems that your PLC is supported. But this NI OPC Server can only work with DSC 8.5.
Contact your local NI people for more information.
Another choice is to use a 3rd party opc server.
Ryan Shi
National Instruments

Similar Messages

  • LabVIEW Run Time Engine and ActiveX Automation Server

    Hi,
    I have a question related to LabVIEW Run Time Engine and ActiveX Automation Server:
    We have a tool developed in LabVIEW and TestStand. End user interface is a LabVIEW GUI (it's an executable) which executes TestStand sequences. Some TestStand sequences call lower level LabVIEW VIs.
    Everything works fine with LabVIEW installed, but I was wondering if I could run this tool on deployment machine with only LabVIEW run time engine installed. We are using LabVIEW 6.1 and with only the run time engine installed, I get the error message: "Unable to launch the 'LabVIEW.Application' ActiveX automation server ". 
    BTW, we are planning to upgrade the versions soon.
    Is it possible to make things work only with the run time engine?
    Thank you.

    Thanks for the response, Brian.
    I did upgrade to LabVIEW 8.0 and TestStand 3.5. Everything works fine on the development computer where LabVIEW and TestStand is installed. On the target computer in the lab, I installed LV RTE 8.0 and TestStand 3.5, and now when a VI is called in a sequence file, I get the following:
    RunState.PreviousStep.Result.Error.Code  -18002 
    RunState.PreviousStep.Result.Error.Msg  "LabVIEW: The VI is not executable"
    So, the executable opens and works fine (which means that the LV RTE is installed properly), but when a sequence calls a low level VI, it does not make it through.
    comments/suggestions are appreciated. Thanks.

  • During iTunes installation "Registering iTunes automation server"... I am getting following error messag from "Microsoft visual C   runtime Library"... Runtime Error! Program: C:\program files (x86)\iTunes\iTunes.exe

    During iTunes installation, when it comes to installation phase "Registering iTunes automation server"... I am getting following error message:
    "Microsoft visual C++ runtime Library"...
    "Runtime Error! Program: C:\program files (x86)\iTunes\iTunes.exe"
    "R6034
    An application has made an attempt to load the C runtime library incorrectly. Please contact the application's support team for more information."
    My system is Windows 7 Enterprise - Service Pack1

    Check the user tip below.
    https://discussions.apple.com/docs/DOC-6562

  • ITunes 10.5.3 Installation on Windows XP SP3: hanging on "Registering iTunes Automation Server"

    I have uninstalled successfully iTunes 10.5.1 from my notebook and reinstalled iTunes 10.5.3.3. Unfortunately, in reinstallation process, iTunes is hanging on "Registering iTunes Automation Server" for over 3 hours!!!!!!!! Quicktime, Safari, Bonjour, Apple Application Support, Apple Mobile Device Support, Apple Software Update are all reinstalled successfully!!! WHAT's the problem for my notebook? How to overcome this issue??? Please help me !!!!!!!!!!!!!!!!!!!!
    System:Windows XP SP3
    Apple iPhone 4S, iPad 2, iPod Classic

    Noboday has ideas about this issue???

  • 64 bit vs 32 bit wrapper for automation server

    I have just istalled WCI 10.3.3 on a windows server 2008 64 bit server and most things seem to be working pretty well. One issue I am having is that automation server is not reporting any of its logging back to the portal. I can watch the jobs run in PTSpy, but no logs in the portal.
    I was looking at the startup log for automationserverwrapper and I see a block of the log that says the following:
    STATUS | wrapper  | 2015/01/26 16:52:32 | Oracle WCI Automation Service installed.
    STATUS | wrapper  | 2015/02/02 11:53:05 | --> Wrapper Started as Service
    WARN   | wrapper  | 2015/02/02 11:53:05 | The value of property 'wrapper.java.additional.2', '%JVM_2%' is not a valid argument to the jvm.  Skipping.
    WARN   | wrapper  | 2015/02/02 11:53:05 | The value of property 'wrapper.java.additional.3', '%JVM_3%' is not a valid argument to the jvm.  Skipping.
    WARN   | wrapper  | 2015/02/02 11:53:05 | The value of property 'wrapper.java.additional.4', '%JVM_4%' is not a valid argument to the jvm.  Skipping.
    WARN   | wrapper  | 2015/02/02 11:53:05 | The value of property 'wrapper.java.additional.5', '%JVM_5%' is not a valid argument to the jvm.  Skipping.
    WARN   | wrapper  | 2015/02/02 11:53:05 | The value of property 'wrapper.java.additional.6', '%JVM_6%' is not a valid argument to the jvm.  Skipping.
    WARN   | wrapper  | 2015/02/02 11:53:05 | The value of property 'wrapper.java.additional.7', '%JVM_7%' is not a valid argument to the jvm.  Skipping.
    WARN   | wrapper  | 2015/02/02 11:53:05 | The value of property 'wrapper.java.additional.8', '%JVM_8%' is not a valid argument to the jvm.  Skipping.
    WARN   | wrapper  | 2015/02/02 11:53:05 | The value of property 'wrapper.java.additional.9', '%JVM_9%' is not a valid argument to the jvm.  Skipping.
    WARN   | wrapper  | 2015/02/02 11:53:05 | The value of property 'wrapper.java.additional.10', '%BIT_MODE%' is not a valid argument to the jvm.  Skipping.
    STATUS | wrapper  | 2015/02/02 11:53:05 | Launching a JVM...
    INFO   | jvm 1    | 2015/02/02 11:53:10 | Wrapper (Version 3.2.3) http://wrapper.tanukisoftware.org
    INFO   | jvm 1    | 2015/02/02 11:53:10 |   Copyright 1999-2006 Tanuki Software, Inc.  All Rights Reserved.
    INFO   | jvm 1    | 2015/02/02 11:53:10 |
    INFO   | jvm 1    | 2015/02/02 11:53:10 |
    INFO   | jvm 1    | 2015/02/02 11:53:10 | WARNING - Unable to load the Wrapper's native library 'wrapper.dll'.
    INFO   | jvm 1    | 2015/02/02 11:53:10 |           The file is located on the path at the following location but
    INFO   | jvm 1    | 2015/02/02 11:53:10 |           could not be loaded:
    INFO   | jvm 1    | 2015/02/02 11:53:10 |             C:\bea\alui\ptportal\10.3.3\bin\..\..\..\common\wrapper\3.2.3\lib\native\win32\wrapper.dll
    INFO   | jvm 1    | 2015/02/02 11:53:10 |           Please verify that the file is readable by the current user
    INFO   | jvm 1    | 2015/02/02 11:53:10 |           and that the file has not been corrupted in any way.
    INFO   | jvm 1    | 2015/02/02 11:53:10 |           One common cause of this problem is running a 32-bit version
    INFO   | jvm 1    | 2015/02/02 11:53:10 |           of the Wrapper with a 64-bit version of Java, or vica versa.
    INFO   | jvm 1    | 2015/02/02 11:53:10 |           This is a 64-bit JVM.
    INFO   | jvm 1    | 2015/02/02 11:53:10 |           Reported cause:
    INFO   | jvm 1    | 2015/02/02 11:53:10 |             no wrapper in java.library.path
    INFO   | jvm 1    | 2015/02/02 11:53:10 |           System signals will not be handled correctly.
    That seems like it is trying to load the 32 bit into a 64 bit computer, but I know it is supposed to automatically choose the correct loader. Did I miss something on the install? Any help would be greatly appreciated.
    Thanks,
    Berney

    Pretty sure I figured this one out. I think there is a registry edit required. Jobs started showing up 3 hours later. Testing the registry edit now. at https://support.oracle.com/epmos/faces/DocumentDisplay?id=1424443.1
    Thanks Karl.
    Berney

  • OLE Automation Server

    Hi all.
    I've been asked to help in a project where the main portion of it is
    being written using labview (G), which I'm not familiar with.
    I've had a quick browse through the various labview manuals, and really
    don't want to go off at a tangent from what I need to do, meaning that I
    don't have time to become proficient with labview - the current
    "developer" does not describe himself as a "programmer", which is why he
    chose labview.
    Anyway, the job requires me to interface a Thompson Frame Grabber card
    (FGT) with labview. Thompson supply an SDK and the source for a
    Microsoft Visual Studio sample program. Unfortunately, no source for the
    SDK DLL/driver.
    Reading their French-glish manuals, the way they expect you to control
    the FGT card is via a supplied DLL. They do supply some guidance on how
    to do this, but the problem I have is that the DLL requires various low
    level capabilities to allow things like an overlay window, callbacks,
    etc. Given that such info seems to be rather difficult (tedious) to
    extract or have labview perform, I've decided I should write (using
    Delphi or C++) another component to talk directly to their DLL, and have
    labview control the new component that I write.
    Looking through the various manuals, I see that labview supports
    ActiveX, but I'm unsure wether that is restricted to just ActiveX
    controls specifically, or wether labview can interface with an
    Automation Server (OLE and ActiveX are built upon COM) ?
    If so, how does one "import" the Automation server's interface into the
    labview environment/IDE, so my "non-programmer" client to easily
    interface with an Automation Server ?
    The reason that I want to go with a standalone, out-of-process (OOP...?)
    Automation Server, as opposed to an in-process server, or an ActiveX
    control, is that (naive) attempts thus far with interfacing labview with
    the FGT DLL has lead to serious side effects, such as crashing the
    system. However, trivial trials using Borland C++ Builder to interface
    with the FGT DLL produced none of those stability problems.
    Another reason is that if I make an ActiveX control, the possibility of
    multiple use rears it's head, which the DLL and overlay functions do not
    support, nor make sense for it to.
    I will shortly install a temporary copy labview (5.1 ?) on my Dual boot
    Win98/Win NT4 system here, just to experiment with labview. But my
    client is using NT4 SP6, with a dual processor Xeon system (although
    we've removed one of the CPU's due to various weirdities with labview).
    Any additional pointers or confirmations would be most helpful.
    //)) //))| Richard RUDEK. MicroDek. Chatswood, Sydney. Australia. |
    //\\ //\\ |http://microdek.homepage.com/ |
    |________________________________________________________|

    > Reading their French-glish manuals, the way they expect you to control
    > the FGT card is via a supplied DLL. They do supply some guidance on how
    > to do this, but the problem I have is that the DLL requires various low
    > level capabilities to allow things like an overlay window, callbacks,
    > etc. Given that such info seems to be rather difficult (tedious) to
    > extract or have labview perform, I've decided I should write (using
    > Delphi or C++) another component to talk directly to their DLL, and have
    > labview control the new component that I write.
    >
    > Looking through the various manuals, I see that labview supports
    > ActiveX, but I'm unsure wether that is restricted to just ActiveX
    > controls specifically, or wether labview can interface with an
    > Automation Server (OLE and ActiveX are built upon COM) ?
    >
    > If so, how does one "import" the Automation server's interface into the
    > labview environment/IDE, so my "non-programmer" client to easily
    > interface with an Automation Server ?
    >
    > The reason that I want to go with a standalone, out-of-process (OOP...?)
    > Automation Server, as opposed to an in-process server, or an ActiveX
    > control, is that (naive) attempts thus far with interfacing labview with
    > the FGT DLL has lead to serious side effects, such as crashing the
    > system. However, trivial trials using Borland C++ Builder to interface
    > with the FGT DLL produced none of those stability problems.
    >
    > Another reason is that if I make an ActiveX control, the possibility of
    > multiple use rears it's head, which the DLL and overlay functions do not
    > support, nor make sense for it to.
    >
    > I will shortly install a temporary copy labview (5.1 ?) on my Dual boot
    > Win98/Win NT4 system here, just to experiment with labview. But my
    > client is using NT4 SP6, with a dual processor Xeon system (although
    > we've removed one of the CPU's due to various weirdities with labview).
    >
    If you inflate any arrays or strings before calling the DLL, then
    there shouldn't be any problem calling into the DLL. This is how
    the NI drivers are built. If you would rather, then you can use
    the ActiveX client functions. LV can contain controls, and can
    access any automation server. The function for importing is the
    Automation Open function. Its in the ActiveX palette. Popup on
    it to create an automation refnum, and type it to be the server
    that you are creating and registering.
    As for problems with the Dual processor, I now of a number of
    LV users that use dual processor machines with no problem. If
    you have problems, it is more likely to be a problem with a
    driver. If it is anything reproducable, then please report it
    to NI.
    Greg McKaskle

  • Install hanging when registering automation server

    I'm tearing my hair out, as well as getting my 4rse kicked by the other half!
    We've had iTunes up and running on our Vista Home Premium box for a while, then it just stopped working coming up with an error.
    So I've tried re-installing, but 7.3 keeps hanging when trying to register the automation server. Worst still I have to kill it with Task Manager and it leaves a partial install that refuses to uninstall!
    Any guidance would be much appreciated.
    Thanks,
    Stuart

    Registering Automation Server hangs are actually a 7.x.x.x thing rather than a 7.3.0.54 thing. I've seen them with 7.2.0.x too.
    Perhaps try this strategy.
    First download and then install the QuickTime standalone installer:
    Latest Quicktime Installers … get the one that doesn’t mention iTunes
    If that install goes through properly, then try another iTunes install.
    (The theory here is that if your QuickTime is already up to date, the iTunes installer bundle skips the QuickTime part of the install. If the iTunes installer is given less to do, sometimes it gets past the Registering Automation Server hang.)

  • Automation server error 0x800a01ad

    I've been able to batch delete, import, and export metadata from the XML file, but can't seem to import and export the binary thumbnails, raw books, and encrypted books.
    As soon as I set ImportFiles:Yes and ImportRawBook:Yes, error 0x800a01ad "Automation server can't create object" is thrown.
    Does anyone have any insight into this error message? I know it has been asked before about a comprehensive list of error messages, but Adobe seems unconcerned about supplying such resources to end users. I'm trying to gain enough knowledge to avoid the expensive per-incident support fees.

    Mike,<br /><br />We import our books with the batch tool. Below is an example of how we write our XML file. Maybe it can help you. /Fabian<br /><br /><?xml version="1.0" encoding="ISO-8859-1"?><br /><acs:Message<br />     xmlns="http://www.editeur.org/onix-international/ReferenceNames/"<br />     xmlns:acs="http://www.glassbook.com/metadata-0.1"><br />     <Product><br />          <NotificationType>04</NotificationType><br />          <ISBN>9172970278</ISBN><br />          <DistinctiveTitle>Gomstallet</DistinctiveTitle><br />          <ContributorStatement>Marten Sanden</ContributorStatement><br />          <PublisherName>eLib</PublisherName><br />          <SupplyDetail><br />               <SupplierName>eLib</SupplierName><br />               <Price><br />                    <PriceTypeCode>01</PriceTypeCode><br />                    <PriceAmount>39</PriceAmount><br />               </Price><br />          </SupplyDetail><br />          <acs:RawBook><br />               <MediaFileFormatCode>04</MediaFileFormatCode><br />               <MediaFileLinkTypeCode>06</MediaFileLinkTypeCode><br />               <MediaFileLink>\\server\folder\ISBN9172970278.pdf</MediaFileLink><br />          </acs:RawBook><br />          <acs:PublishInfo><br />               <acs:RightCopyCount>0</acs:RightCopyCount><br />               <acs:RightCopyInterval>0</acs:RightCopyInterval><br />               <acs:RightPrintCount>0</acs:RightPrintCount><br />               <acs:RightPrintInterval>0</acs:RightPrintInterval><br />               <acs:RightLendHops>0</acs:RightLendHops><br />               <acs:RightUseExprirationType>4</acs:RightUseExprirationType><br />               <acs:RightTimeAllowed>0</acs:RightTimeAllowed><br />               <acs:RightUseExprirationDate>12/31/1969</acs:RightUseExprirationDate><br />               <acs:RightUseExprirationInterval>0</acs:RightUseExprirationInterval><br />               <acs:RightReadAloud>-1</acs:RightReadAloud><br />               <acs:RightModifyRights>0</acs:RightModifyRights><br />               <acs:Copies>1000000</acs:Copies><br />               <acs:ContentType>1</acs:ContentType><br />               <acs:EncFileName>ISBN9172970278.pdf</acs:EncFileName><br />          </acs:PublishInfo><br />          <acs:DeploySite><br />               <acs:KeyName>local</acs:KeyName><br />               <acs:DeployType>1</acs:DeployType><br />               <acs:DeployFlags>1</acs:DeployFlags><br />          </acs:DeploySite><br />          <acs:Approval>1</acs:Approval><br />     </Product><br /></acs:Message>

  • How to use a third party automation server

    I would like to use the methods of another application. The application exposes the methods through an automation server. How can I use this automation server in Labview?
    Do or do not, there is no try

    Well, I am referring specifically to an application called RapidFET from FetCorp. The rapidFet probe is a box they sell that allows the user to access (SRIO) networks, "serial rapid IO". There is a large API with many methods that can used with SRIO and once you start the application I guess they run a automation server that exposes the methods for use in programs written in languages like visual basic, visual c++ and others; is that considered active x?
    Do or do not, there is no try

  • ActiveX Automation server error on deployed TestStand

    I'm trying to deploy TestSTand 2.0 + LabVIEW 6.1 on a PC under Win-2K.
    I created and deployed TS Engine and Operator Interface for LV.
    I try to deploy the "Auto.seq" test from the TS exemples.
    Of course, it works on my Development system.
    On the deployed system, I got an error : -18351; An error occurred reading an ActiveX Automation server type library.
    Step 'Read Database Option - Construct' of sequence 'Get Database Options' in 'SequentialModel.seq'
    Step 'Read Database Option - Read Options' of sequence 'Get Database Options' in 'SequentialModel.seq'
    After having ignored those 2 errors, the tests goes on normally and the report looks fine.
    I also get this error opening the database configuration:
    Step 'Read Database Option - Construct' of sequence 'Edit Database Options' in 'Database.seq'
    From answers already given for similar subjects, I've checked that TsDBOptions.dll is present and registered (done regsvr32...) on the PC.
    Can someone help ?
    Note: upgrading to more recent TS + LV versions is not a solution!

    Whether you are using database logging or not, you should not get an error like that when database options are loaded. From the kb's you specified it sounds like there was an issue with a COM/ActiveX server not getting registered in the past. Especially on machines in which TestStand was installed from a deployment rather than the main installer. Have you tried running the version switcher like the KB suggested? Did it succeed or give an error? If it gave an error what was the error? Could you perhaps try a fresh install of TestStand on a clean machine?
    -Doug

  • Reload automation server doesn't work for all steps

    Hi all,
    I'm creating ActiveX Servers using Visual Basic 6. In TestStand 3.1 I have steps that call methods from an automation server and I have steps that get properties of an automation server.
    When I create a new version of an automation server, I open one of the steps that use the automation server and press "Reload", so that is uses the latest version. TestStand Automatically updates all the rest of the steps that use the same automation server, but for some reason it only updates the steps that call a method and not the steps that Get a property. Why is this?

    Frank -
    When you configure a TestStand step to call an automation server, it stores the specific ID information for the server and the class and method/property that you are calling. If the server is created with MSVB the compatibility mode of the project defines whether MSVB alters this information after each recompile of the project. TestStand tries to find the server, class and method/property after you compile the project each time. If you take a look at the Compatibility Options for Visual Basic section in Chapter 5 of the TestStand 3.x Reference Manual you will find more information on this. The section describes the various compatibility modes Visual Basic projects. In a nut shell, it is recommended to use Project Compatibility while developing code and switch to Binary Compatibility when you release a system. When you switch to Binary Compatibility you should keep it there and only add new methods or classes. You should not change the names or prototypes of existing methods or properties for this breaks binary compatibility. In my previous development, it would have been nice if VB exposed the control of these IDs, but they do not.
    Scott Richardson
    National Instruments

  • Automation Server cannot create object_error in Java script

    Hi
    I am using window.open method to save contents of xml file in my local pc.
    I am getting this error (Automation Server cannot create object),for this,i need to change internet settings.
    But i dont want to change the internet settings as other pages are getting affected.
    Please guide me regarding this....

    Javascript is not Java.

  • ERROR: Automation server can't create object

    Hi,
    I am at my wits end, and I hope you can help me. I have
    compiled a Webhelp project that runs just fine in Firefox (with the
    exception of expanding text but blah blah blah... :P)
    When I compile the same project in IE, I get an page loading
    error that tells me that "Automation server can't create object"
    (with reference to 'whskin_pdfhtml.html' in a file path, and my ToC
    is not visible.
    My tester, who is on another machine in another location,
    tells me HIS ToC loads fine, but he gets an out of memory error at
    line 59.
    I have trawled thru these forums for an hour now, and I am no
    closer to solving this problem. I have tried creating a brand new
    empty project with one topic and I get the same error.
    Any ideas on what's happening?
    Of course, we have a demo tomorrow at 6am.
    thanks

    Guessing here.
    1] You have created webhelp pro when you don't have RoboHelp
    Server installed on the server.
    2] Your source has some output files in it. The topic
    concerned being the one that gives the memory error. This result is
    what you get when you view in RoboHelp an output file that has been
    imported into the source. I don't know whether it gives the same
    error in the output again.
    Or are you viewing the help locally instead of from a server?
    What version of IE.

  • Fresher with PG Diploma in Industrial Automation, seeking a job in labview

    Hello.,
    I'm a recent PG Diploma Graduate in Industrial Automation (Including LabVIEW) seeking for a job in LabVIEW Sector. I'll be greatful if someone could help me to know industries where i can apply for a job relating to PLC SCADA DCS or LabVIEW.
    Mail me at [email protected]
    Thanks in advance,
    -Siju
    Attachments:
    Siju_cv-21-1-2014.pdf ‏159 KB

    Hi Sir/Madam,
    I am recently Completed my  PG Diploma Graduate in Industrial Automation and System Design from National Institute of Electronics and Information Technology (NIELIT) Calicut,kerala with 72.2%. I am  good labVIEW programer and i am seeking for job in labVIEW Sector, can you  please help me to know the job vacencies in labVIEW Sector/Automation and i am also well good in PLC programming.
    Please find the attached resume.
    Thanks & Regards,
    Ravi Kumar
    +91-9000324146
    E-mail: [email protected]
    Attachments:
    resume ravi new formetpdf.pdf ‏65 KB

  • Itunes install hangs at "registering itunes automation server"

    Windows 8 - 64 bit
    Loaded latest Quick Time.
    uninstalled itunes ...rebooted...tried installing again but still hangs at "registering itunes automation server"
    When I click on "cancel" install...it starts to roll back and says "Files missing"
    Thanks

    For general advice see Troubleshooting issues with iTunes for Windows updates.
    The steps in the second box are a guide to removing everything related to iTunes and then rebuilding it which is often a good starting point unless the symptoms indicate a more specific approach. Review the other boxes and the list of support documents further down the page in case one of them applies.
    The further information area has direct links to the current and recent builds in case you have problems downloading, need to revert to an older version or want to try the iTunes for Windows (64-bit - for older video cards) release as a workaround for installation or performance issues, or compatibility with QuickTime or third party software.
    Your library should be unaffected by these steps but there are also links to backup and recovery advice should it be needed.
    tt2

Maybe you are looking for

  • Getting "No Object type found error" in BPM sceanrio.

    Hi Friends, I am doing File to RFC with response sceanrio using BPM. For this i configured one receiver step, one send synchronous step to send input message to RFC and one asynchronous send step to send the response to a file. I have configured 3 re

  • Ignoring characteristics in a BPS FOX formula

    Hello, I have a multiplanning area consisting of two planning areas. In the first one there are yearly data. In the second one there are monthly data. I have a FOX formula distributing the yearly data by a set of periodization keys into the planning

  • Can't see query results in the grid

    I am having a problem where some of my queries do not return results in the grid. Those same queries return results if I run them as a script. Or if I run them on a different server. And the same query run on someone else's SQL Developer also does no

  • Transport of Customizations from ECC 5.0 to ECC 6.0

    Hi, We have some customizations done in ECC 5.0, which we now want to implement in ECC 6.0 (Freshly Installed). Can we transport these customizations directly to ECC 6.0 (after checking the release notes to see if any functionality has changed betwee

  • Change Default Movement Type in a PM Order

    Dear Members, I configured an order type (from a Maintenance Order Category) and the default movement type for this order type is 261. However, the movement type I want for this order type is 311 (transfer posting - one step). Is it possible to chang