AT-MIO-16 & LabVIEW 5.1 & Ni-DAQ 6.1.1 & Win95

I try to install a AT-MIO-16 with Ni-DAQ 6.1 and LabVIEW5.1 under Windows 95. I declared it in "System" after the LabVIEW and Ni-DAQ installation without any problem but it don't appear in "Measurement & Automation". What is the installation procedure to use my AT-MIO-16?

Greetings,
Below is a link to the Hardware Installation Wizard. This will walk you through the installation procedure for your board:
Hardware Installation Wizard
Furthermore, you will need to find the exact model number of your AT-MIO-16 so that you can add it in the Add/Remove Hardware Wizard. Below is a link to a KnowledgeBase that discusses finding this information:
How Can I Identify the Exact Model of My Legacy AT-MIO-16 Board?
Spencer S.

Similar Messages

  • Once running the labview program which contain DAQ Assistant ,the message of "ERROR-50405....." appear.

    Once running the labview program which contain DAQ Assistant and can be run without any error before, the message box of "ERROR-50405....." appear which capture down in the attachment. We use PCI6221 and LabVIEW 8.0 in Windows XP. I also found that the Device Manager of Window have recognized the PCI6221.
    Any help on this situation would be great.
    Attachments:
    labview error.JPG ‏145 KB

    Hi~
    This error is due to signal interference between the device and the computer. This could be environmental or due to the PCI Controller. You can on a different computer to see whether this problem persists.

  • How can I make LabView 6.1to detect DAQ NI-USB 6008

    I have a LabView version 6.1, recently I bought a new DAQ model NI-USB 6008, I could not use it with my Labview version. Please, how can I adapt my DAQ for version 6.1 or update my LabView to detect my DAQ? Please advise me to a free applicable solutions. Thanks very much

    The USB 6008 requires DAQmx which requires LabVIEW 7.0 or greater. The upgrade to 7.x (or the just released 8.0) is not free. The only other solution I've heard of is to use the Call Library Function Node to make your own calls to the DAQmx dll. This would not be for the faint of heart or anyone wishing to come up with a quick solution.

  • How can I use a GPIB and AT-MIO-16L with a common NI-DAQ?

    I'm using a GPIB card for recording data and a AT-MIO-16L for sending an analog output to my instrument. Earlier, both the devices (GPIB and AT-MIO-16L) were running correctly. Until I reformated my hard disk. Now I'm trying to install NI-DAQ 6.1.1 for AT-MIO-16L but that doesn't detect my GPIB card. On the other hand if I use NI 488.2 along with MAX 1.7 or MAX 2.2, I'm unable to use AT-MIO-16L. Is there a way I could get both my devices running on a common platform?

    NI-DAQ is not supposed to detect your GPIB and NI-488 software will not detect your daq board. When you installed MAX, was this from a LabVIEW driver install CD that also put a new version of NI-DAQ on your pc. Open MAX and check your currently installed versions of NI-DAQ and NI-488. They should both be listed. If you have a new version of NI-DAQ than 6.1, you can uninstall the newer version and install 6.1.

  • How can I create software start and stop trigger in LabView using 6023E series DAQ card? I don't want to use the external trigger.

    I am using 6023E DAQ card to collect the signals, such as AE, Force, Torque from the machine. I want to collect only some part of signal for example between start triger and stop trigger. I'd like to know how I can creat those triggers in LabView from one of the channels that I am acquiring at the same time. I found one or two library file that is only for start trigger. I know that this is availabe in some of DIAdem functions. Please let me know if you have done some example for this requirement.

    If you are wanting to create a software trigger based on an analog input voltage in LabVIEW, there are several options. One suggestion would be to compare the voltage values from one input channel to a number within a loop. If the input voltage crosses that threshold (is greater than the number), have a case statement that will acquire data from the other channels. This would simulate a software start trigger in LabVIEW.

  • Pins at a PCI MIO-16E-1 to Measure Frequency(DAQ-STC).vi?

    I want to measure frequency with the
    "Measure Frequency(DAQ-STC).vi".
    Can't find the appropriate connector pins
    in the manual of my PCI MIO-16E-1.
    Can someone confirm or correct me?
    Signal - PFI1/GPCTR1_SOURCE
    SignalGND - PFI9/GPCTR0_GATE
    PFI8/GPCTR0_SOURCE - PFI4/GPCTR1_GATE
    Thanks in advance
    Manfred

    Manfred,
    You can find this information by going to the http://www.ni.com/manuals site and viewing the E-series manual. There is a table which shows the pin number, name, and function for each pin.
    Pin 10 - PFI1/Trig2
    Pin 11 - PFI0/Trig1
    Pin 43 - PFI2/Convert
    Pin 42 - PFI3/GPCTR1_Source
    Pin 41 - PFI4/GPCTR1_Gate
    Pin 40 - GPCTR1_out
    Pin 6 - PFI5/Update
    Pin 5 - PFI6/WFTRIG
    Pin 3 - PFI9/GPCTR0_Gate
    Pin 2 - GPCTR0_Out
    Pin 4,39,35,36 - DGND
    Mark

  • Text file - Labview - Blinking LED (eg daq)

    Hello all, 
    I am totally new to labview. I'm supposed
    to read data from a Text File, then use the file in labview to generate
    an output when certain conditions are met. The output is in the form of
    a daq card (emant) which has LEDs and i'm supposed to make it light up.
    Help me.

    Hi Krum,
    Thanks for the post!
    I would recommend looking at the example finder, Help>>Find Examples. There are examples on reading from text file AND software triggered DAQmx tasks with pre-loaded waveforms (i.e. data from text file). I would try and produce some code, and then post it if/when you get stuck.
    Otherwise, maybe try asking some more specific questions.
    Kind Regards, 
    Kind Regards
    James Hillman
    Applications Engineer 2008 to 2009 National Instruments UK & Ireland
    Loughborough University UK - 2006 to 2011
    Remember Kudos those who help!

  • Labview 8 with 4350 DAQ board

    I upgraded from LabView 6 to Labview 8.  At the same time, I put the old 4350 board into this new WinXP computer. 
    The board works great in MAX, but LabView can't seem to find it.   And can't use all of my old data acquisition VIs.
    According to MAX, I have both the mx and legacy versions of NI-DAQ
    What else do I need to check?  or is all of this in incompatible combination?

    Hi Todd,
    You probably have an older version of the Traditional NI-DAQ driver. In order to use that hardware in LabVIEW 8, you will have to have the latest version of the traditional NI-DAQ driver - 7.4.1, which you can download here.
    I hope this helps.
    Regards,
    Natasa

  • Labview - paramétrage Assistant DAQ

    Bonjour,
    Je possède une carte 9401 montée sur un châssis 9172 et je souhaite brancher 2 codeurs en quadratures.
    Problème : L'assistant DAQ (dans labview), qui gère les deux codeurs en entrées, paramètre automatiquement le port A et B sur PFI0 et PFI2.
    Question 1 : Comment modifier ceci afin de pouvoir exploiter les deux codeurs sur des connexions différentes ?
    Question 2 : Quels ports utiliser ? ex : codeur 1 => PFI0 et PFI2 / codeur 2 => PFI? et PFI?
    Question 3 : Comment peut-on savoir sur quels pins brancher les codeurs ? Où peut-on trouver une doc technique qui montre sur quels pins de la carte on retrouve PFI0, PFI2, ... provenant du chassis ?
    Merci par avance,
    Cordialement,
    Eric
    Pièces jointes :
    labview.JPG ‏112 KB

    Bonjour,
    Voici deux exemples pour synchroniser vos compteurs:
    https://decibel.ni.com/content/docs/DOC-5706
    Malheureusement, vous ne pouvez pas faire de synchronisation avec du DAQ assistant. La synchronisation de voies entrée analogique/sortie analogique/Digital IO/compteur nécessite une programmation
    plus évoluée que l'assistant DAQ.
    De plus, la manière de programmer de la synchro diffère si vous voulez synchroniser des entrées analogiques ou des entrées numériques ou des compteurs.
    J'espère que les 2 exemples que je vous envoie aujourd'hui vous parleront. Il s’agit de la synchro de 2 compteurs.
    Dans le cas contraire, vous pouvez peut être demandé une formation (vu que vous êtes dans l'enseignement, vous avez des prix réduits)
    Cordialement,
    MatthieuR
    Matthieu RICORD
    National Instruments France
    #adMrkt{text-align: center;font-size:11px; font-weight: bold;} #adMrkt a {text-decoration: none;} #adMrkt a:hover{font-size: 9px;} #adMrkt a span{display: none;} #adMrkt a:hover span{display: block;}
    Été de LabVIEW 2014
    12 présentations en ligne, du 30 juin au 18 juillet

  • Use LabVIEW FPGA as a DAQ and detect peak

    Hi everyone, need your help now.
    I want to use Labview to encode a FPGA to achieve following function:
    1.Acquire data as a DAQ from a Photodetector 
    2.then use peak detect VI to measure the peak information
    3. some simple mathematical operations
    is it possible for me to achive all these only using one FPGA? and is it OK to connect DAQ's output and the input of the peak detect VI?
    thanks a lot. I am a beginner, so it confused me a lot.

    Hi
    What is you hardware? cRIO? FlexRIO?  And what your signal type? Anolog or digital?
    You can refer to the help of Peak detect.vi to comfirm if the data (sigle point integer or integer array ) can be wired directly. I am afraid you can not wire the FPGA IO OUT directly to the Peak detect.vi, but you can create a array for the data and then use the peak detect.vi
     

  • Is LabVIEW based on NI-DAQ ?

    I want to get NI-DAQ for Linux.
    Does Labview 7.0 full development version
    for Linux include NI-DAQ ?

    AndreyCherepenko wrote:
    > Thanks Methis.
    >
    > Comedi lack of something functionality, is't
    > reliability and is't ported to Windows yet.
    Comedi never will be ported to Windows I would assume. Its
    architecture is very Unix centric and porting to Windows
    would be basically impossible without a complete redesign.
    Comedi will be improved with new support for sure and it
    will only get more stable if users are using it and providing
    feedback and bugfixes.
    > I look for crossplatform library to communicate
    > with DAQ boards.
    There are two options for you. The NI Measurement Hardware
    DDK is supported on both Linux and Windows (and some other
    systems too including MacOS X and the NI realtime platforms).
    It is the low level and I mean "low level" API you
    are probably
    talking about and is basically the same on all platforms it
    supports.
    Another option might be to look into UEI as an alternative.
    Their hardware has Windows and Linux drivers which I would
    assume have the same API.
    > By the way. OpenG do not concern to low level.
    No, the OpenG library is a LabVIEW VI library to interface
    to the Comedi library which handles the low level stuff.
    It is possible to write a VI library which might call Comedi
    but is for the rest compatible to the NI-DAQ VIs.
    > It is just additional modules to LabVIEW.
    > Is free version of LabVIEW for Linux ?
    No, LabVIEW is a paid software license, Linux or not.
    Rolf Kalbermatter
    Rolf Kalbermatter
    CIT Engineering Netherlands
    a division of Test & Measurement Solutions

  • About using the labview in real time DAQ system

    Hi All
        I designed a DAQ board based on PCI bus by myself, using labview for my graphic display application software. DAQ board generate PCI interrupt every 20us(50kHz). then PC respond it and read the data from DAQ board, that means the sampling frquency is 50kHz. the DAQ driver is generated by NI-VISA. it goes well after installing. I am sure that VISA detecte the PCI interrupt and triger a PCI interrupt event every 50kHz.
        But I face a problem, labview can not respond reading data in a real time. so does labview can not be used in the real time system? or is there something wrong with other else? if that is true, how can I solve it?
        by the way, I read the VISA help document. found there are two ways to respond PCI interrupt. one is callback, the other is queuing. I use the second way. I beg your help.

    I think you can use buffered signals with some changes on your circuit, with real time can be hard to implement with not supported hardware.
    Best regards

  • Using Labview on a non-daq board device

    How would one go about using a device, connected through USB, in labview that doesn't have a daq board? I have a signal monitor that I've managed to get to work with C++ and was wondering if there was a way to integrate it with Labview at all. I hope that makes sense.

    If they've provided a DLL then you can use the Call Library Function Node to call the DLL. You should read the chapter in the LabVIEW Help on calling code from external languages. If it's a C++ DLL you may have problems because LabVIEW only supports C DLL, not C++. A common issue is name mangling. If you do a search on the NI site for "DLL name mangling" you will come across several Knowledge Base articles that discuss this issue. Another common problem is that if the DLL uses complex datatypes (such as structures with strings inside, or pointers to complex structures then you will need to write a wrapper DLL that converts simple datatypes that LabVIEW can handle to the complex datatypes that the DLL uses. Again, there is a wealth of information on the NI site on calling DLLs, so a search will yield lots of information.

  • Very Urgent !!!! Windows Crashing when running a LabVIEW Program using Comact DAQ Chassis

    I am  using a Compact DAQ Chassis with a AI and a DO Card. The chassis is connected to the USB post of the computer. ( There is no other device connected to the laptop.) When the program is running, WIndows crash and gives a stop error. This has happened several times. Please help.
    Thanks.

    Hi,
    I have a few questions for you, so that we may better troubleshoot your issue.
    1. Are you able to view the device in MAX and communicate with it?
    2. Could you attach a screen shot of the error you are receiving?
    3. Have you been able to use this cDAQ chassis without the modules in it? Do you see the same behavior?
    4. Have you tried using this chassis with another laptop? Do you see the same behavior?
    If you would like to speak with an Applications Engineer directly, please visit ni.com/ask and create a service request.
    Amanda Howard
    Americas Services and Support Recruiting Manager
    National Instruments

  • Controling heating/cooling element with labview and usb 6008 DAQ card

    Greetings All
    I'm looking for a heating/cooling type of element that I can control with labview and my usb-6008 card. Heating/Cooling will just be for clean water and the temperture range will be from 0 C to 100 degree C.
    Thanks
    The heating and cooling elements can be seperate products. Any recommendations

    A simple kettle element will of course be sufficient for upto 100°C
    To get the temperature down you need a cooling system, what springs readily to mind of course is a refrigerator.
    Just a note of warning, water and electricity are dangerous bed fellows.
    On that note perhaps one of those vortex air units would be safer - they blow hot in one direction and cold in the other, nominally to 100°C
    see: -
    http://www.airtxinternational.com/how_vortex_tubes_work.php

Maybe you are looking for

  • Can someone help me figure out why system crashed?

    I've got a desktop G5 running OS 10.3.9. Today I came home (9pm) and noticed that the fans were on full-blast, and my displays were dark (no "kernel panic" gray square). I rebooted and one of the monitors had a picture that was all crazy - I had to u

  • Implementing SSO in OBIEE 11g

    Hi All, We have a requirement to implement custom SSO with OBIEE 11g. Is configuration of SSO in OBIEE 11g similar to that of OBIEE 10.1.3 ? (10g steps mentioned below) 1. Changing Instanceconfig.xml 2. Adding a user "Impersonate " in Repository 3. A

  • How to use the discrete unit delay function with the simulate signal as the input?

    Hi there, I want to use the simulate signal as the input. First, i downsample the input with the downsampler.vi. Then I want to feed the output of the downsampled signal to the discrete unit delay block and display the delayed signal on the graph. So

  • Reports in Manager Self Service with  java.lang.NullPointerException

    Hi Everyone, I have been breaking my head with this problem for over a week. When initially installed the reports worked fine but now when I try and access the Report Selection I get the following java.lang.NullPointerException error. I am running EP

  • EAS issue

    Hi, we have installed EAS 11.1.1.3(64 bit) on weblogic 9.3.1 manually. But we identified one component was not deployed properly with weblogic n we were not able to solve it. as we dnt require EAS administration stuff we have not worried abt it, as w